Delta DE212 GLOBAL User manual

r
Delta RC AS Tlf. +47 33 44 83 90 Document item no: 02974
P.O. Box 1065
Søndre Kullerød 4A Web site: www.deltarc.no
N-3204 Sandefjord E-mail: hello@deltarc.no
Norway
Delta DE212
Failsafe DP protection
Including wired deadman timer
for Airplane Refuelling Trucks and Dispensers
Installation Manual

Installation Manual for CU220 DP
DELTA RC AS Page 2 of 12
Document: 02974
Utgavestatus / Edition overview:
Rev.
Dato
Date 10.06.2019
Utført
Performed
Godkjent
Approved
Revisjons beskrivelse
Revision description
A
14.06.2019
ZB
Corrected page 6 and 8.
Contents
1. INTRODUCTION ................................................................................................................................................3
1.1 SYSTEM DIAGRAM .........................................................................................................................................3
2. INSTALLATION .................................................................................................................................................4
2.1 INTRODUCTION .........................................................................................................................................4
2.2 INSTALLING THE CONTROL UNIT ......................................................................................................................4
2.3 CONNECTIONS..............................................................................................................................................5
2.4 CU212 DP REED SWITCH CONNECTIONS...........................................................................................................5
2.5 CU212 DP CONNECTIONS ..............................................................................................................................6
2.6 DP, DIFFERENTIAL PRESSURE INPUT P3-2. .......................................................................................................7
3. TECHNICAL DATA ............................................................................................................................................8
3.1 GENERAL SPECIFICATION ...............................................................................................................................8
3.2 CONTROL UNIT,CU212-1S.............................................................................................................................8
3.3 DIMENSIONS,CONTROL UNIT ...................................................................................................................9
3.4 MAINTENANCE ...........................................................................................................................................10
4. SPARE PARTS. ...............................................................................................................................................10
5. WARRANTY CONDITIONS...............................................................................................................................10
6. ENVIRONMENTAL INFORMATION..................................................................................................................11

Installation Manual for CU220 DP
DELTA RC AS Page 3 of 12
Document: 02974
1. INTRODUCTION
Delta DE212 is a deadman system for aircraft refuelling trucks and dispensers. The DE212 system can operate
wireless or wired and different sensors can be connected.
This document describes the CU212-1S, the control unit installed in the drivers cabin. Connected to the wired
deadman and the DP sensor.
The wired deadman differs from the wireless as it needs a cable connection between the two units to carry the
needed signals.
The CU212 has a built in timer system, with timeout warning outputs for light and beeper. The standard timer
is set to 2 minutes with the warning signals 30 seconds before the refuelling will shut down.
With more than 15 years of experience in developing and producing deadman systems, the DE212 system has
all the security needed for a safe and reliable operation.
For special applications, the control unit has inputs for connection of wired deadman override and external
STOP.
The DE212 system is based on the latest technology and has the flexibility to meet new operational demands
by upgrading the software in the control unit.
1.1 SYSTEM DIAGRAM
12/24VDC Power input
Deadman valve
control
Emergency STOP
DP OK normal operation
DP warning light
Deadman warning light
CU212 System diagram
DP protection and wired deadman control
DP sensor/switch, input
Cable deadman input
Deadman override, input
External STOP input
DP reset/override, input

Installation Manual for CU220 DP
DELTA RC AS Page 4 of 12
Document: 02974
2. INSTALLATION
2.1 INTRODUCTION
The CU212 DP control unit is designed to monitor the DP Gauge modified by a switch or a sensor.
The control unit is available in two versions:
a) Art.no. 02358, prepared for reading of a DP reed switch NO or NC.
b) Art.no. 02865, prepared for reading of a DP proximity sensor or mechanical reed switch NO or NC.
2.2 INSTALLING THE CONTROL UNIT
The control unit should normally be placed in the drivers cabin. It must be installed outside EX area. Make sure
that the control unit is easy accessible for service.
The control unit CU212-1S, has two cable glands. One is for the input signal from the deadman handle, the
second is for input power and for output and input signals.
It is recommended to use 0,5 to 0,75mm2 cable, and to use soft and multicore cables.
When connecting the cables, take off the two connectors, from the printed circuit board, and connect the
cables to the connectors while they are free to move and easy to keep in the right position.
When all cables are connected, replace the connectors to the printed circuit board and fasten the front panel
to the bottom section.
The installation of the control unit is now finished.
The cable used for the deadman handswitch is normally a coiled cable, witch can be stretched to about 14m.
Normally on an installation, the coiled cable is connected to a connection box, positioned at a central place of
the dispenser, where the operator can reach all the needed positions by stretching the coiled cable. The cable
between the control unit and the connection box is not a part of the delivery.

Installation Manual for CU220 DP
DELTA RC AS Page 5 of 12
Document: 02974
2.3 CONNECTIONS
2.4 CU212 DP REED SWITCH CONNECTIONS
Valid for Art.no 02358, and SW/Program 02335. Only DP reed switch input, ON/OFF type.
The power supply can be 12 or 24VDC.
See figure below.
NOTE: Wired deadman
must be ON/OFF type
1. Deadman timer. ON= Enabled. OFF=Disabled
2. Not in use
3. Deadman override. ON= Enabled. OFF=Disabled
4. Not in use
1 Timer Beeper output
2 Timer Warning light output
3 DP warning light
4 Deadman valve output
5 STOP
6 DP working OK
7
(-)Minus-pole for input voltage
8 (+) Plus-pole 12 or 24VDC
9 Do not connect
10 DP Reset/Override switch
Control unit board
1
2
3
4
5
6
7
8
9
10
Connector P1
Input voltage fuse, 5A auto fuse
Total load for all outputs at P1
and P3 are: 5A.
5
4
3
2
1
Connector P3
1
2
3
4
5. GND
4 Wired Deadman
3 External STOP
2. DP ON/OFF Switch
1 Deadman Override
SW2
OFF ON
1
2
3
4
1
2
3
4
5
Connector P2, not in use.

Installation Manual for CU220 DP
DELTA RC AS Page 6 of 12
Document: 02974
2.5 CU212 DP CONNECTIONS
Valid for Art.no 02865, and SW/Program 02864. For Reed switch or Namur sensor NG500A, Ex certified.
The power supply can be 12 or 24VDC.
See figure below.
º
NOTE: Wired deadman
must be ON/OFF type
R9, See note 1
Standard factory setting
SW2 switches:
1. Deadman timer. ON= Enabled. OFF=Disabled
2. Not in use
3. Deadman override. ON= Enabled. OFF=Disabled
4. Not in use
1. Timer Beeper output
2. Timer warning output
3. Extra function
4. Deadman valve output
5. STOP
6. Not in use
7.
Minus-pole for input voltage (-)
8. Plus-pole for input voltage (+)
9. Do not connect
10. DP Reset/Override switch
Control unit board
1
2
3
4
5
6
7
8
9
10
Connector P1
Note 1: R9 is a reference resistor for
the DP sensor.
Voltage measured between P3-2 and
P3-5 should be within 2,0 to 3,0V
with correct sensor in normal
vorking operation mode.
5
4
3
2
1
Connector P3
1
2
3
4
1
2
3
4
5
1. Do not connect
2. Do not connect
3. GND
4. DP OK, normal operation
5. DP Warning Light, sensor
activated.
Connector P2
5. GND
4 Wired Deadman
3 External STOP
2. DP Sensor/Switch
1. External Override
SW2
OFF ON
1
2
3
4
Input voltage fuse, 5A auto fuse
Total load for all outputs at P1, P2
and P3 are: 5A.

Installation Manual for CU220 DP
DELTA RC AS Page 7 of 12
Document: 02974
2.6 DP, DIFFERENTIAL PRESSURE INPUT P3-2.
This function is added in order to prevent refuelling after a high DP signal is detected. The
input signal can be generated by a ON-OFF switch or a Namur inductive proximity sensor.
On CU220 art.no. 02865, the input terminal P3-2 is prepared for both versions.
The difference of the two types of sensors require two different way of connections:
a) DP, ON-OFF sensor. This is a mechanical switch or a reed relay. One solution has a
NO (normally open) situation when the DP is not activated, and the other has a NC
(normally closed) situation when the DP is not activated. In both cases a reference
resistor, Rref, must be connected, see below.
b) Namur inductive sensor, see connection diagram below.
NC
R ref
1
2
5
4
3
P3
R ref
1
2
5
4
3
P3
NO
1
2
5
4
3
P3
GND
GND
GND
+
+
+
Namur sensor
NG500A
Connection of NO normally open sensor Switch.
Input voltage not active DP; 2,6V. Active DP; 3,6V
No polarity requirements.
Connection of NC normally closed sensor Switch.
Input voltage not active DP; 2,6V. Active DP; 3,6V
No polarity requirements.
NOTE: Rref is 2,8kohms (0,5W) Must be connected
close to the switch, for failsafe installation.
Connection of Namur, inductive sensor NG500A.
Input voltage not active DP; 2,6V. Active DP; 3,6V
29.03.2019
(1)
(2)

Installation Manual for CU220 DP
DELTA RC AS Page 8 of 12
Document: 02974
3. TECHNICAL DATA
This equipment is designed for failsafe operation, meeting the stringent requirements for safe operation.
It is in accordance to EU’s demands to CE-label the equipment.
3.1 GENERAL SPECIFICATION
* Temperature Range: Operational and storage: -25 to +65º C.
* Shock Resistance: 2 m free-fall on concrete floor.
3.2 CONTROL UNIT,CU212-1S
* Power Supply: 11 to 35 VDC. Voltage above 35VDC shuts down the receiver.
* Power Consumption: Standby: 22 mA.
* Outputs: Semiconductor output. Temperature and overload protected. Output
voltage is equal to power input; 12/24 VDC. Each output, max 3,5A
total load, 5A. Fused inside by 5A slow blow Auto fuse.
* Deadman output. Active when deadman switch is operated.
* Warning light output, active during operation of the deadman
* Beeper warning output
* STOP output. When control unit is powered, this output is active,
output is12/24V. When STOP is detected, this output is switched off, 0V.
* Optional inputs *The CU212-1S is programmed to operate with a none failsafe handswitch.
* Deadman override, low input activates the override function
* External STOP, low input actives STOP of deadman function.
* Connections: Screw terminal on PCB connector.
* Indicators: Green light diode that indicates power on.
Yellow light diode that indicates active deadman.
* Housing: ABS polycarbonate, class IP52.
* Dimensions: L:160 mm, W: 80 mm, D: 60 mm.
* Weight: 0.7 kg

Installation Manual for CU220 DP
DELTA RC AS Page 9 of 12
Document: 02974
3.3 DIMENSIONS,CONTROL UNIT

Installation Manual for CU220 DP
DELTA RC AS Page 10 of 12
Document: 02974
3.4 MAINTENANCE
This equipment should be kept as clean as possible at all times.
Physical damages that may result in cracks or holes on the cabinets should be repaired as soon as possible by
competent personal. This, because there is a large risk of humidity, dirt and oil entering the unit. If the unit is,
for example, exposed by hydraulic oil, it may cause severe damage on the circuit board. Hydraulic oil and
other thin oils are largely penetrable, especially when the equipment housing is damaged. Dirty equipment
should therefore always be cleaned.
As a rule, the equipment should be sent to service as quick as possible when such damages occurs, without
waiting till the equipment does not work any longer - it might be too late to do any repairs.
4. SPARE PARTS.
The following spare parts are available: NOTE: Not Atex approved parts.
Order number
Unit name
Unit description
02978
CU212-DP RP
Control Unit with 2 min. timer. For Proximity sensor and reed switch
02358
CU212-DP R
Control Unit with 2 min. timer. For reed switch
02865
PCB RP
PCB, with 2 min. timer. For Proximity sensor and reed switch
02366
PCB R
PCB, with 2 min. timer. For reed switch
5. WARRANTY CONDITIONS
Complaints
When receiving the product the buyer must inspect it, and eventually complain any obvious faults or missing
items within 8 days from reception. Acceptance of complaint will otherwise not be considered. Complaints of
any faults that could only first be discovered after mounting and testing the product must be reported
immediately after recognition.
Warranty
The warranty covers only damages caused by material faults and manufacturing errors.
The guaranty ceases 12 months after the delivery date.
Delta RC AS AS or appointed repair workshop, is bound to repair and replace defect parts in its products, free
of charge, in its main workshop during its normal working hours. Packages being sent to and from Delta RC AS
are in the responsibility of the purchaser, as he is also economically responsible for paying the transportation
charges, toll, insurance and other related charges.
Should the warranty repair be done at the customer's location, there will be charges for cost of travelling,
accommodation and dieting, conforming to the government’s assertions. There will also be an additional
charge of 50% of travelling time by the current repair regulations.
The warranty is cancelled if:
a) There has been done any modification or attempts in the product without a
written permission from Delta RC AS A/S.
b) The product has been handled wrongly or has not been maintained properly.

Installation Manual for CU220 DP
DELTA RC AS Page 11 of 12
Document: 02974
c) The payment conditions have not been fulfilled.
Repair work
Repair work done after the warranty period is charged at full cost. Packages being sent to and from Delta RC
AS’s workshop are on the purchaser's cost and risk.
If the repair work is done at the customer's location, by Delta RC AS serviceman, there will be charges for
costs of travelling, accommodation, dieting, travelling time and hours of work.
Warranty exceeding 3 months after repair work is limited to cover only the fault that was repaired. A new fault
after the repair must be pointed by the customer.
Any other defect or missing part during this period is not covered by the warranty. Should Delta RC AS offer a
service unit during the warranty time, the purchaser pays for the transportation, insurance and a weekly rent.
6. ENVIRONMENTAL INFORMATION
Care has been taken while producing this units, to ensure that all excess materials are disposed
properly, and recycled accordingly. Please help us with this process in the future.
This means:
Do not dispose this devices into the trash when discarding.
To minimize pollution and ensure environment protection, please recycle properly, to ensure the
smallest possible environmental footprint.
The PCB (Printed Circuit Board) in this units should be disposed as E-waste.
E-waste is electrical and electronic equipment of any kind that has been discarded. This includes
practically anything powered by an electrical source (e.g., from a power socket or a battery).
The batteries should be disposed properly at a battery recycling facility.
The housings should be disposed as general waste.
Please look for these symbols at the recycling facility:
PCB’s Batteries Housings
European Union (EU) Waste of Electrical and Electronic Equipment (WEEE) directive.
The European Union’s WEEE directive requires that products sold into EU countries must have the
crossed-out wheelie bin label on the product (or the package in some cases). As defined by the
WEEE directive, this crossed-out wheelie bin label means that customers and end-users in EU
should not dispose of electronic and electrical equipment or accessories as household waste.
Customers and end-users in EU countries should contact their local equipment supplier or service
centre for information on the waste collection system in their country.

Installation Manual for CU220 DP
DELTA RC AS Page 12 of 12
Document: 02974
Check our website for updates: www.deltarc.no
Delta RC AS
Tel +47 33 44 83 90
P.O. Box 1065
Søndre Kullerød 4A
E-mail: hello@deltarc.no
NO-3204 Sandefjord
Norway
www.deltarc.no
Delta RC AS reserves the right to make changes without further notice to the product, to improve reliability,
functions and design. Delta RC AS does not assume any liability arising out of the application or use of the
product if used according to this document.
This manual is printed on chlorine-free recycleable paper
Other manuals for DE212 GLOBAL
3
Table of contents
Other Delta Timer manuals
Popular Timer manuals by other brands

Intermatic
Intermatic GRASSLIN DTAV40VM Series Installation & operating instructions

Toshiba
Toshiba TCB-EXS21TLE instruction manual

Accusplit
Accusplit Alliance AL530 operating instructions

Bachmann
Bachmann 852.103 Technical description

Sylvania
Sylvania SA 170 user manual

NSi INDUSTRIES
NSi INDUSTRIES TORK R5M4HW manual

Schluter Systems
Schluter Systems BTEET operating instructions

Hengstler
Hengstler tico 735 operating instructions

Drayton
Drayton Lifestyle LP111Si installation instructions

SOMFY
SOMFY Chronis io user manual

Vaillant
Vaillant timeSWITCH 150 Operating and installation instructions

Altronics
Altronics Redback A 4510 operating manual