1. Press simultaneously for 3 seconds.
2. Select the zone address of the receiver using and .
3. Press any key (except or ) to validate.
The multi-sensor sensitivity can be configured with a value ranging from 1 to 8 (1 = very sensitive, 8 = less sensitive).
A lower sensitivity can avoid detections due to air flows or other disturbances. The optimum value to avoid disturbances and to
optimize the presence detection is typically 3.
The user can adjust the sensitivity by using the infrared programming remote control (TCND-I-PR) without opening or removing the
multi-sensor.
With the remote control, the multi-sensor sensitivity can be adjusted from level 1 to 5. For an effective detection configuration, levels
from 6 to 8 are changed by controller settings.
For more information, please refer to the controller’s and infrared programming remote control’s documents.
The detection area changes according to the sensitivity level and movements: