WIRELESS FLOOD
DETECTOR
«STZ-RK»
Installation Guide
1 Product Overview
1.1 Wireless flood detector «STZ-RK» (hereinafter, the Detector) is intended
for detecting leaks of water, water solutions, other current-conducting
non-aggressive liquids and generating an alarm message via a two-way
communication by the «Rielta-Contact-R» protocol. The Detector is intended to
operate as a component of any control panel (hereinafter, CP) supporting the
wireless exchange protocol «Rielta-Contact-R».
1.2 The Detector comprises a Signal Processing Module (SPM) and flood sensors
«DZ-3V» (FS). The SPM has two connecting blocks for FS hooking up: «Loop 1»
and «Loop 2». Not more than two FSs can be hooked up in parallel to each loop.
1.3 The Detector is able to operate in two-loop or single-loop mode. The last
mode presumes the «Loop 2» status is ignored. The operation mode choosing
is available during the detector logging in the CP.
1.4 Radio signals are exchanged within the 433.05 to 434.79 MHz frequency
range. The transmitter output power does not exceed 10 mW.
1.5 Two operating frequencies: main and reserve are used for the wireless data
exchange. The Detector switches over reserve operating frequency automatically.
1.6 Radio exchange sessions are initiated by the Detector at a preset
frequency. The frequency settings are 10, 15, 30 sec, 1, 5, 10 min, chosen in
the process of the the binding procedure. The SPM transmits alarm messages
to the CP immediately.
1.7 Independent power supply of the Detector is provided by power supply
batteries placed inside it’s case: the main one (CR123A) and the backup one
(CR2032). If the main power supply battery is low, the Detector switches over
to the backup power supply source automatically.
1.8 The Detector generates and transmits the following messages:
- «Norm in Loop 1» – under the absence of liquid between the FS contacts
plugged to «Loop 1»;
- «Norm in Loop 2» – under the absence of liquid between the FS contacts
plugged to «Loop 2»;
- «Alarm in Loop 1» – under the presence of liquid between the FS contacts
plugged to «Loop 1»;
- «Alarm in Loop 2» – under the presence of liquid between the FS contacts
plugged to «Loop 2»;
- «Tamper» – under the case tampering or SPM removal from the installation
surface;
- «Failure in Loop 1» under the break of communication bus SPM – FS,
hooked to «Loop 1»;
- «Failure in Loop 2» under the break of communication bus SPM – FS,
hooked to «Loop 2»;
- «Main Power Supply Low Battery» – under the main power supply battery
voltage drop over 2.8-0.4 V;
- «Backup Power Supply Low Battery» – under the backup power supply
battery voltage drop over 2.8-0.4 V.
1.9 The Detector is designed to operate continuously, around the clock.
1.10 The Detector provides immunity to electromagnetic interference.
1.11 The level of industrial interference generated by the Detector does not
exceed the norms established for the technical equipment operated in residential
buildings or connected to power mains of residential buildings.
2 Features
Table 1
Features Value
Assumed number of FSs in an alarm loop circuit, max 2 pcs.
Length of each alarm loop between the FS and the
SPM, max 5 m
Weight:
- SPM, max
- FS, max
0.1 kg
0.03 kg
Operating temperature minus 20 … +50 °C
Case dimensions:
SPM, max
FS, max
112 x 41 x 32 mm
65 x 22 x 16 mm
IP rating:
- SPM
- FS
IP30
IP67
Average service life 8 years
Battery life under normal climate conditions and speci-
fied broadcast period not more than 60 sec, not less:
- main power supply battery
- backup power supply battery
60 months
2 months
Figure 2
–
Flood Sensor «DZ-3V»
5 Sound and LED Indication
The Detector has the following indication modes:
-
«
Binding
»
procedure LED indication (procedure of logging in the CP);
- LED indication of the mode
«
Identification
»
– lights up by sending relevant
command from CP and remains active during 15 min or until the case is opened;
- LED indication of the Detector state – lights up and remains unchanged for
15 min after the case is closed under conditions:
- other LED indication types (except the sound alarm) absence;
- alarm
«
Tamper
»
message is not generated during this time period;
- the Detector state indication is ON upon the receipt of relevant command
from the CP.
LED indicator modes are listed in the Тable 3.
Тable 3
The Detector Mode Indication Note
Binding procedure
finished LED lighting red for 2
–
3 sec
«Binding» mode
LED blinking green with
0.25 sec period
The Detector
logging in the CP
in single-channel
mode
LED blinking green with 1 sec
period
The Detector
logging in the CP
in double-channel
mode
«Identification» Alternate LED red and green
alternate blinking
on command from
the CP
«Alarm in Channel 1»
«Alarm in Channel 2»
Single-shot LED lights up red
for 4 sec *
State indication
is on and
«Identification»
indication is off
Generation
«Alarm in Channel 1»
«Alarm in Channel 2»
Sound alarm dual switching **
State sound
indication is on
Fallback recovery
«Alarm in Channel 1»
«Alarm in Channel 2»
Single-shot sound alarm
switching **
3 Scope of Delivery
Each Detector unit package contains the items Table 2.
Table 2
Name Qty
Signal processing module «STZ-RK SPM»
Flood sensor «DZ-3V»
CR123A lithium power supply battery
CR2032 lithium power supply battery
Set of accessories:
Screw 3-3x30.016
Nylon wall plug NAT 5x25 SORMAT
Wireless flood detector «STZ-RK». Installation Guide
1 pc.
2 pcs.
1 pc.
1 pc.
6 pcs.
6 pcs.
1 copy
4 Design of the Detector
The external appearance of the SPM is shown in Figure 1.
The SPM comprises a base, a cover and a printed circuit board (PCB).
The front side of PCB (1) comprises: tamper (2), LED indicator (3), connecting
blocks (4) for connecting the FSs, main power supply battery holder (5), «RESET»
contacts (7), sounder (8), antenna (9). The backup power supply battery holder
and the tamper are located on the reverse side of the PCB. The PCB is fixed in
the base of the case by a latch (6) and grips on the reverse side of the base.
The case of the FS is watertight, it is
provided with sensing contacts and a
1.5 m cable for connecting to the SPM.
The FS is designed to be fastened to both
horizontal and vertical surfaces.
Figure 1
–
The Base with the PCB
The «DZ-3V» layout is shown in Figure 2.
Red
Black
WA1
XP2
HL1
GB1 +
–
XP1
1
2
34
965 78
«DZ-3V»
RESET
+ Line №2- -Line №1 +
Table 3, continuation
The Detector Mode Indication Note
Radio communication
quality appraisal See sect. «Radio communication quality appraisal»
«Failure in channel 1»
«Failure in channel 2»
Orange LED indication dual
blinking with 12 sec period *
State indication
is on and
«Identification»
indication is off
«Normal» Indication is off
*) – LED indication of the Detector state
**) – Sound indication of the Detector state
6
Binding with the CP
«
Binding
»
mode is used for logging the Detector in the CP and service
information exchange.
6.1 Prepare the CP in accordance with CP reference guide.
6.2 If it is necessary to log the Detector in double-channel mode, hook up TS
to the Detector as shown in Figure or short-circuit the terminals of the Detector
«
-
»
and
«
Channel 2
»
. For the single-channel mode neither hooking on, no short-
circuit is required.
6.3 Set the backup power supply battery to the holder plate on the PCB
other side.
6.4 Set the main power supply battery to the holder plate (6).
6.5 Periodical LED indicator blinking green is evidence of binding process.
6.6 In case of mentioned above LED indication absence, short-circuit
«
RESET
»
terminals for 2 – 3 sec.
6.7 Successful binding procedure complying is indicated by LED indicator
lighting red for 2 – 3 sec.
6.8 The time limit for the binding process of the Detector is 100 sec. To
restart the binding procedure, short-circuit
«
RESET
»
terminals for 2 – 3 sec.
7
«
Stand Alone
»
mode
7.1 The Detector changes to stand alone mode upon the expiry of 100 sec
binding procedure.
7.2 During operation in the stand alone mode the Detector has no
communication with CP and it’s state is displayed only by means of LED and
sound indication (see Table 3).
7.3 During operation in the stand alone mode LED and sound indication is
always ON under condition of
«
Tamper
»
message absence.
8 Communication Quality Appraisal
8.1 For radio communication quality appraisal it is necessary to:
- place initially backup and then main power supply batteries to the
correspondent holder plates;
- set the Detector on the assumed place of installation;
- push and then release case tamper.
8.2 After case tamper releasing the Detector generates case tamper
alarm message, transmits it via radio communication channel and represents
communication quality with CP by LED indication in accordance with the Table 4.
Table 4
LED Indication Radio
communication
quality appraisal
Recommendations
Color Mode
Green Three
blinks Excellent Install the Detector on
this place
Green Two blinks Good
Green One blink Communication
established Choose another place
for installation or use a
repeater*)
Red Four blinks No communication
*)
–
«Ladoga BRSS-RK-RTR»or «Ladoga BRSS-RK-RTR»ver. 1
9 Installation
9.1 Drill holes for fastening the Detector elements. You may use the FD and
the SPM base without the PCB for marking out the holes.
The FS should be located in the place, where the water spilled in the
detection zone close the sensor contacts. The FS installation with the terminals
downwards ensures generation of alarm signal over appearance the liquid sheet
with a thickness exceeding 1 mm. The FS installation with the terminals sidewise
provides easy access to the sensor terminals for removal of a liquid from the FS
surface between the terminals after the leakage elimination.
9.2 Fasten the FS on the mounting surface with screws or a water-resistant
glue. Fasten the SPM base on the mounting surface with screws. For the wall-
tamper monitoring, the second screw must be screwed in a hole under the wall
tamper. Install the PCB, connect the FSs to the loop terminals (the red wire to
the «+» terminal). Install the cover.
«RIELA» JSC, www.rielta.ru,
17 Chapayeva St., Saint Petersburg, Russia, 197101, [email protected],
tel./fax: +7 (812) 233-0302, 703-1360,
Technical support: tel.: +7 (812) 233-29-53, 703-13-57, [email protected]
Made in Russia Mod. 3 dd. 09.11.15
№ 00175
10 Troubleshooting
Table 5
CP Message Elimination Procedure
«Tamper» Check the security of the SPM fastening, close
it’s cover
«Alarm in Loop 1»
«Alarm in Loop 2»
In case there is no liquid (moisture) between the
FS contacts, check the absence of a short circuit
between the wires
«Failure in Loop 1»
«Failure in Loop 2»
Check the integrity of the wires connecting the
FS and the SPM and their fastening to the SPM
terminals
«Main power supply
battery fault»
Replace the main power supply battery and the
backup one
«Backup power supply
battery fault» Replace the backup power supply battery
11 Manufacturer’s Guarantees
11.1 The manufacturer guarantees conformity of the Detector to the
requirements of technical conditions provided the transportation, storage,
installation and operation conditions are observed.
11.2 The guaranteed shelf life of the Detector is 63 months since the date of
manufacture. The guaranteed useful life is 60 months since the day of putting
into operation within the limits of the guaranteed shelf life.
11.3 The detectors that are found non-conforming to the requirements of the
specifications will be repaired by the manufacturer, provided the installation and
operation rules have been observed.
Note – Warranty obligations do not apply to batteries.
12 Storage and Transportation
12.1 Factory-packed detectors can be shipped by any transport means
in covered vehicles (in railway, cars, trucks, sealed heated compartments of
aircraft, holds etc). The Detector is resistant to:
a) transport pounding with the acceleration 30 m/sec2with impact frequency
from 10 to 120 impacts/sec or 15000 impacts with the same acceleration;
b) the ambient temperature
minus
50 … +50 °С;
c) relative air humidity (95 ± 3) % at the ambient temperature +35 °С.
12.2 The uptime of the Detector after transportation under the conditions
different to exploitation conditions – not more than 6 hours.
12.3 The storage room shall be free from current-conducting dust, acid
vapors, alkali and gases that cause corrosion and destroy insulation.
12.4 The uptime of the Detector after transportation under the conditions
different to exploitation conditions – not more than 6 hours.
13 Acceptance and Packing Certificate
Wireless flood sensor «STZ-RK»,
batch number _________________,
has been manufactured in compliance with the existing technical
documentation, considered fit for operation and packed by the «RIELTA» JSC.
Person in charge of acceptance and packing
QC representative_________________ __________________.
Date, month, year

Other Rielta Security Sensor manuals

Rielta PYRONE-SH User manual

Rielta

Rielta PYRONE-SH User manual

Rielta Ladoga MK-RK User manual

Rielta

Rielta Ladoga MK-RK User manual

Rielta CELSIUS-RK User manual

Rielta

Rielta CELSIUS-RK User manual

Rielta Ladoga MK-RK version 2 User manual

Rielta

Rielta Ladoga MK-RK version 2 User manual

Rielta IPDL-Ex User manual

Rielta

Rielta IPDL-Ex User manual

Rielta OCHRANA ORLAN User manual

Rielta

Rielta OCHRANA ORLAN User manual

Rielta Ladoga MK-RK User manual

Rielta

Rielta Ladoga MK-RK User manual

Rielta Ladoga MK-RK User manual

Rielta

Rielta Ladoga MK-RK User manual

Rielta OCHRANA Ladoga MK-RK User manual

Rielta

Rielta OCHRANA Ladoga MK-RK User manual

Rielta STZ-RK User manual

Rielta

Rielta STZ-RK User manual

Rielta Ochrana FOTON-19RK User manual

Rielta

Rielta Ochrana FOTON-19RK User manual

Rielta STZ-RK User manual

Rielta

Rielta STZ-RK User manual

Rielta GRAN-RK User manual

Rielta

Rielta GRAN-RK User manual

Rielta FOTON-15A User manual

Rielta

Rielta FOTON-15A User manual

Rielta STEKLO-3M User manual

Rielta

Rielta STEKLO-3M User manual

Rielta FOTON-SH2 User manual

Rielta

Rielta FOTON-SH2 User manual

Rielta GRAN-RK User manual

Rielta

Rielta GRAN-RK User manual

Rielta ORLAN-D User manual

Rielta

Rielta ORLAN-D User manual

Rielta Pyrone-4RK User manual

Rielta

Rielta Pyrone-4RK User manual

Rielta FOTON-12-RK User manual

Rielta

Rielta FOTON-12-RK User manual

Rielta FOTON-SH1 User manual

Rielta

Rielta FOTON-SH1 User manual

Rielta FOTON-10M User manual

Rielta

Rielta FOTON-10M User manual

Rielta C.Nord CN-Glass User manual

Rielta

Rielta C.Nord CN-Glass User manual

Rielta UDAR User manual

Rielta

Rielta UDAR User manual

Popular Security Sensor manuals by other brands

ABB 2CSYD0103M Installation and user manual

ABB

ABB 2CSYD0103M Installation and user manual

SOMFY 5125850A installation guide

SOMFY

SOMFY 5125850A installation guide

Mitsubishi Electric PAC-USSEN001-FM-1 Installation instructions manual

Mitsubishi Electric

Mitsubishi Electric PAC-USSEN001-FM-1 Installation instructions manual

Olympia SECURE Series quick start guide

Olympia

Olympia SECURE Series quick start guide

elsner elektronik Sewi AQS/TH Modbus Technical specifications and installation instructions

elsner elektronik

elsner elektronik Sewi AQS/TH Modbus Technical specifications and installation instructions

DBI SALA EZ Stop User instruction manual

DBI SALA

DBI SALA EZ Stop User instruction manual

Fetal Doppler i100 Operation manual

Fetal Doppler

Fetal Doppler i100 Operation manual

SubSurface Instruments AQUA TRAC 300 user manual

SubSurface Instruments

SubSurface Instruments AQUA TRAC 300 user manual

D-Link MyDlink DCH-S150 Quick install guide

D-Link

D-Link MyDlink DCH-S150 Quick install guide

Risco WL X312 installation instructions

Risco

Risco WL X312 installation instructions

IMMAX NEO LITE user manual

IMMAX

IMMAX NEO LITE user manual

Risco iWAWE RWX95P quick start guide

Risco

Risco iWAWE RWX95P quick start guide

B.E.G. LUXOMAT PD9-M-2C Installation and operating instruction

B.E.G.

B.E.G. LUXOMAT PD9-M-2C Installation and operating instruction

Nice HSDIM24 Instructions and warnings for installation and use

Nice

Nice HSDIM24 Instructions and warnings for installation and use

HikRobot SC3000X Series quick start guide

HikRobot

HikRobot SC3000X Series quick start guide

STEINEL professional Series manual

STEINEL

STEINEL professional Series manual

Raptor 47HLB 80 installation guide

Raptor

Raptor 47HLB 80 installation guide

General png2000a user manual

General

General png2000a user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.