Technical User Guide
6www.dol-sensors.com DOl 10 kit for water temperature
3 Installation
Installation, servicing and troubleshooting of all electrical equipment must be carried out by quali-
fied personnel in compliance with the applicable national and international standard EN 60204-1
and any other EU standards that are applicable in Europe.
The installation of a power supply isolator is required for each motor and power supply to facili-
tate voltage-free work on the electrical equipment. The power supply isolator is not included.
3.1 Circuit Diagram
Figure1: DOL 10.
oC kΩ* V oC kΩ* V oC kΩ* V
-40 82.50 8.08 13 22.03 5.44 33 12.24 4.03
-35 76.84 7.96 14 21.36 5.37 34 11.91 3.97
-30 70.60 7.83 15 20.71 5.29 35 11.60 3.91
-25 63.97 7.68 16 20.09 5.22 36 11.30 3.85
-20 57.18 7.49 17 19.48 5.15 37 11.01 3.79
-15 50.50 7.26 18 18.90 5.07 38 10.72 3.73
-10 44.12 7.00 19 18.33 5.00 39 10.45 3.67
-5 38.22 6.70 20 17.79 4.93 40 10.1 3.61
032.1 6.37 21 17.26 4.85 41 9.94 3.55
131.92 6.30 22 16.76 4.78 42 9.70 3.50
230.96 6.23 23 16.27 4.71 43 9.47 3.44
330.02 6.16 24 15.79 4.64 44 9.24 3.39
429.11 6.09 25 15.34 4.57 45 9.03 3.34
528.23 6.02 26 14.90 4.50 46 8.82 3.29
726.53 5.88 27 14.48 4.43 47 8.62 3.24
825.72 5.81 28 14.07 4.36 48 8.43 3.19
924.94 5.73 29 13.68 4.30 49 8.24 3.14
10 24.17 5.66 30 13.30 4.23 50 8.06 3.09
11 23.44 5.59 31 12.93 4.16 55 7.26 2.87
12 22.72 5.51 32 12.58 4.10 60 6.59 2.68
Table1: Sensor characteristics. *Zero power measurement