Technical User Guide
DOL 53 www.dol-sensors.com 7
6 Troubleshooting instructions
Error Cause Remedy
Packaging is damaged. Damage in transit. Contact the supplier in case the sensor is
damaged.
No measured value at the con-
trol unit.
Electrical connection faulty or in-
terrupted.
Check installation for cable break.
DOL 53 aligned incorrectly, not
vertical.
Install DOL 53 in accordance with mount-
ing instructions, vertical ±30°.
Sensor element faulty or used
up.
Replace sensor element.
Sensing head faulty. Replace the sensor.
Incorrect measured value at the
control unit.
Loss of sensitivity. Check sensitivity with test gas.
Filter clogged. Replace filter.
Unexpected measured value at
the control unit.
Brief interference pulses <5 sec-
onds.
Interference caused by electrical equip-
ment, e.g. lighting, fans or heaters. Iden-
tify device and suppress interference.
Unstable measured value. Dynamic signal fluctuations with
a period of more than 5 seconds
can arise from turbulence with
fresh air.
No activity, continue to monitor.
Wet sensor. DOL 53 was cleaned with water. Wipe DOL 53 dry.
Condensation.
7 Maintenance
The sensor element must be replaced after 3 years of operation at the latest. End of service life see date on the
sensor element rating plate.
Carry out the daily visual inspection to detect operation readiness.
Have specialists carry out the annual inspection and sensitivity check.
Replace the dust filter in front of the sensor element if clogged. A clogged filter prolongs the re-
sponse time of the sensor element. This affects the sensitivity. The dust filter must always be re-
placed prior to checking the sensitivity.
DOL 53 must be removed during cleaning and disinfection. After removing the connector, screw
on the screw plug. A missing screw plug leads to corrosion of the connector.
Cleaning
Clean DOL 53 surface with lukewarm water. Check for mechanical damage.
Disposal
Dispose of the product in accordance with the applicable rules and regulations.