Technical User Guide
DOL 140 4-20 mA www.dol-sensors.com 3
LED/LIGHT PROTOCOL Functional graph
LED Status
Green Red
ON Operation OK
Flash Outside normal range
(below 10 % RH or exceeding 95 %
RH)
ON Connection error
Load error, see load graph
Flash Sensor defect
Over or under voltage alarm
Overload
4 Maintenance
Clean the sensor with water and a brush without using:
• High-pressure cleaner
• Highly compressed air
• Solvents
• Corrosive/caustic agents
• Alcohol-based disinfectants
During cleaning and disinfection, the sensor should be removed and the sealing plug for the ca-
ble should be mounted. Alternatively, the sensor protective cap can be mounted. The sensor
must be placed with the tip pointing upwards during disinfection.
After the sensor has been exposed to water and condensation, it requires a period where the relative humidity
is lower than 80 %RH in order for it to measure correctly.
Do not bend the sensor as this would inflict permanent damage on the electronics of the sensor.
5 Technical data
Measurement range % RH 0 - 100
Accuracy % RH ± 2% RH (40–85 %) ± 3% RH (10-95 %) at 0-40 °C
Output signal V 0.16 mA / % RH
Time constant T63 20 s at 0.5 m/s air speed
Supply voltage V DC 11 – 30
Max. current mA 35
Load See figure regarding load resistance and supply voltage
Max. output current mA 20
Cable 2 m 3 x 22 AWG / 0.34 mm2
Max. cable length 200 m 1.50 mm2
Temperature, operation and
storage
°C -40 to -60