Installation Manual
Note: -The lamp must be installed by professional electrician
-Ensure the power supply is switched off before fitting this product
-Do not touch the lamp when in use
-Keep away from hot steam and corrosive gas
May 20, 2021
4
4. Connect the live, neutral and earth wires as shown.
Then connect terminal C between emergency and battery Terminal C
1
2
3
OFF ON
PIN1 PIN2 PIN3
Power for
20W
Power for
40W
OFF OFF OFF 10W
ON OFF OFF 14W
OFF ON OFF 20W
/
/
20W
/
/
OFF OFF ON 30W
ON ON ON 40W
(switched active)
Terminal block
L
N
L1
L1
N
L
INPUT CABLE
4X(0.75-2.5mm²)
Outer insulation
Inner insulation
30±3mm
8±2mm
(Un-switched active)
3
3. Take down the terminal cover.
Fix the batten base onto the required place
with appropriate screws.
2. Remove Packaging, carefully pull end caps as shown in picture A and gently lift off the LED
module. Disconnect terminal A and terminal B.
Picture A
LED MODULE
Terminal B
1.Disconnect mains supply before installation
or removing cover.
8
8.Push the end cap back as shown in picture C.
Picture C
9
9. Reconnect mains supply.
5
5.Screw the terminal cover back to batten base
6
6.To set the colour temperature, simply move the dip switch located at the back
of LED module to the desired colour temperature.
Dip switch
5700K/4000K/3000K
7
7.Fasten terminal A between driver and LED module. LED module back to batten base.
Terminal A
Surface Mounted
BOLT-EM-60
Voltage: 240V~ Lumen (±10%): (10W-20W) Warm White 3000K - 900lm/1800lm
(10W-20W) Neutral White 4000K - 1000lm/2000lm
(10W-20W) White 5700K - 1000lm/2000lm
Dimmable: No
Power: 10/20W CCT: 3000K, 4000K, 5700K Lifespan: 40,000hrs
IP Rating: 44 Beam Angle: 120° Weight: 1.82kg
Frequency: 50Hz CRI: ≥80 Power Factor: 0.9
Emergency Specification Features
Compliance: Fully complaint to AS/NZS 2293 standards
Battery: LiFePO4 battery type, 6.4V, 7 Hour Charging Time, 1.5 Hours Discharging Time
Battery Capacity: 1500 mAh at 0.2 CmA
Emergency: Sustained
Rated Duration: 90 min
Classification: C0: D50, C90: D32
BOLT-EM-60-TRIO
Order Code Product Code Description
66007 BOLT-EM-60-TRIO Multi Watt and TRIO technology emergency LED wide batten
Thank you for purchasing your new Bolt Emergency LED wide Batten, Please take the time to read and understand the instruction sheet
below. Failure to do so may void warranty.
Note: The light source of this luminaire is not replaceable; When the light source reaches its end of life, the whole luminaire shall be
replaced.
29-31 Richland St. Kingsgrove. Sydney NSW 2208 Australia
Phone: 02 9554 9600 | Fax: 02 9554 9433
[email protected] | www.domuslighting.com.au
Installation Manual
Note: -The lamp must be installed by professional electrician
-Ensure the power supply is switched off before fitting this product
-Do not touch the lamp when in use
-Keep away from hot steam and corrosive gas
May 20, 2021
Surface Mounted
4
4. Connect the live, neutral and earth wires as shown.
Then connect terminal C between emergency and battery Terminal C
1
2
3
OFF ON
PIN1 PIN2 PIN3
Power for
20W
Power for
40W
OFF OFF OFF 10W
ON OFF OFF 14W
OFF ON OFF 20W
/
/
20W
/
/
OFF OFF ON 30W
ON ON ON 40W
(switched active)
Terminal block
L
N
L1
L1
N
L
INPUT CABLE
4X(0.75-2.5mm²)
Outer insulation
Inner insulation
30±3mm
8±2mm
(Un-switched active)
3
3. Take down the terminal cover.
Fix the batten base onto the required place
with appropriate screws.
2. Remove Packaging, carefully pull end caps as shown in picture A and gently lift off the LED
module. Disconnect terminal A and terminal B.
Picture A
LED MODULE
Terminal B
1.Disconnect mains supply before installation
or removing cover.
8
8.Push the end cap back as shown in picture C.
Picture C
9
9. Reconnect mains supply.
5
5.Screw the terminal cover back to batten base
6
6.To set the colour temperature, simply move the dip switch located at the back
of LED module to the desired colour temperature.
Dip switch
5700K/4000K/3000K
7
7.Fasten terminal A between driver and LED module. LED module back to batten base.
Terminal A
Warning:
If the product is not installed as per the Installation Manual, then the warranty and liability for the product will be voided.
ALL MAINTENANCE, SUCH AS BATTERY CHANGE ON THIS LUMINAIRE, TO BE PERORMED BY QUALIFIED PERSONNEL
ONLY. DE-ENERGISE ALL SUPPLIES BEFORE MAINTENANCE.
29-31 Richland St. Kingsgrove. Sydney NSW 2208 Australia
Phone: 02 9554 9600 | Fax: 02 9554 9433
[email protected] | www.domuslighting.com.au
Installation Manual
Note: -The lamp must be installed by professional electrician
-Ensure the power supply is switched off before fitting this product
-Do not touch the lamp when in use
-Keep away from hot steam and corrosive gas
May 20, 2021
Installation
1. Remove the luminaire from its carton and inspect it for damage. If you believe the product to be damaged DO NOT install the product.
Please return it to the place of purchase for a replacement.
2. An emergency sustained luminaire requires two main active supplies. Un-switched active and switched active.
3. The un-switched active is required to charge the batteries. The switched active illuminates the luminaire on mains.
4. Both the switched active and un-switched active must be on the same phase.
5. (For 24/7 operation of the luminaire, link switched active with un-switched active)
6. To ensure maximum battery service life the battery pack is supplied not connected to the emergency luminaire. Before connecting the
emergency luminaire to the mains supply the battery pack must be connected to the emergency inverter via the polarized plug fitted
to the battery pack.
7. To ensure maximum product service life and performance, mount the emergency luminaire away from any direct heat source where the
ambient temperature exceeds 40 deg. C.
8. To check the correct operation of the luminaire, allow the battery to charge for a minimum of 3 minutes, ensuring that the green
charging LED is constantly illuminated. Depressing the test switch will then illuminate the emergency LED light.
9. Discharge time for 90 minute.
10. The product has an indicator light, the test button is used to detect whether the lamp is operating normally, and when press the test
button, the luminaire is in emergency mode; when release the test button, the battery is charged.
11. When the battery is charged, the green indicator light on; when the battery is fully charged, the green indicator light is on, when the
luminaire is in emergency mode, the indicator light will extinguish.
12. Emergency light source:>410 lm, CCT: 6500K.
Testing procedure
When the Stellar V EMG Batten is permanently connected to the mains allow 24 hours to fully charge the batteries. Once the batteries
are fully charged the emergency luminaire is required to undergo a commissioning discharge test to confirm compliance as specified
in Australian Standard AS2293 part 2. The emergency luminaire must operate for a minimum of 2 hours in emergency mode. Further
compliance testing is required at intervals of not more than six months, however for these tests the emergency luminaire must operate
for a minimum of 90 minutes in emergency mode.AS2293 part 2 also sets out the mandatory requirements of recording of all tests and
their results, plus any maintenance actions carried on the emergency luminaires. Energetic Lighting has available an emergency lighting
maintenance LOG book for recording of this information.
Problem Solving
If you have installed and connected the Stellar V EMG Batten and the product fails to work properly, please use the following table as a
starting guide to solve the issue.
29-31 Richland St. Kingsgrove. Sydney NSW 2208 Australia
Phone: 02 9554 9600 | Fax: 02 9554 9433
[email protected] | www.domuslighting.com.au
Installation Manual
Note: -The lamp must be installed by professional electrician
-Ensure the power supply is switched off before fitting this product
-Do not touch the lamp when in use
-Keep away from hot steam and corrosive gas
May 20, 2021
Construction site issues that may affect product performance and service life.
IMPORTANT NOTE: Continuously switching the power supply to the emergency luminaire during or after the installation could cause
the emergency luminaire to discharge its battery. This can impact negatively on the battery service life. It is not recommended that any
emergency lighting product be connected to the power supplyif such conditions are prevalent. Exposure of the emergencylighting products
to harsh operating conditions may result in the product warranty being voided.
Fault Possible cause of fault Solution
Green charge indicator LED is not lit a) AC Supply is not connected
b) AC Supply is switched off
c) AC Supply is on a switched active circuit, but the
switched active circuit is switched off
Connect AC Supply Switch on AC supply
Change to un-switched active AC supply
Green charge indicator LED is lit
but the emergency LED does not
illuminate when the test switch is
depressed
a) Emergency LED or inverter is damaged
b) Battery is damaged
c) Battery is not connected to the emergency
inverter.
Replace luminaire Replace battery pack
Connect battery pack
Emergency LED illuminates, but
only temporarily when test switch
is pressed or when the main power
supply is turned off
a) Battery not fully charged
b) Battery pack is damaged
Allow battery to charge for 24 hours and
re-test Replace battery pack

This manual suits for next models

1

Other Domus Lighting Equipment manuals

Domus NEO-SM-TILT-10-WHT User manual

Domus

Domus NEO-SM-TILT-10-WHT User manual

Domus MURO-26S-B-W User manual

Domus

Domus MURO-26S-B-W User manual

Domus BLAZE-PRO Series User manual

Domus

Domus BLAZE-PRO Series User manual

Domus BOLT-120-TRIO User manual

Domus

Domus BOLT-120-TRIO User manual

Domus BOLT-EM-120-TRIO User manual

Domus

Domus BOLT-EM-120-TRIO User manual

Domus BOLT-60 User manual

Domus

Domus BOLT-60 User manual

Popular Lighting Equipment manuals by other brands

Life 39.9F70020C quick start guide

Life

Life 39.9F70020C quick start guide

EuroLite LED ML-20 user manual

EuroLite

EuroLite LED ML-20 user manual

LIGMAN OD-50141 installation manual

LIGMAN

LIGMAN OD-50141 installation manual

Home Accents Holiday 1002461144 instructions

Home Accents Holiday

Home Accents Holiday 1002461144 instructions

Experia IRiS Ripple Light instruction manual

Experia

Experia IRiS Ripple Light instruction manual

Erco Gecko Mounting instructions

Erco

Erco Gecko Mounting instructions

Inter-lux ZTA.100.Surface Installation and maintenance instructions

Inter-lux

Inter-lux ZTA.100.Surface Installation and maintenance instructions

Whelen Engineering Company TN Series installation guide

Whelen Engineering Company

Whelen Engineering Company TN Series installation guide

IKEA BJÖRKSPIREA manual

IKEA

IKEA BJÖRKSPIREA manual

Toolland PM 6640 instruction manual

Toolland

Toolland PM 6640 instruction manual

GTD GTD-LP200 user manual

GTD

GTD GTD-LP200 user manual

LIVARNO home 1105-W-UK manual

LIVARNO home

LIVARNO home 1105-W-UK manual

ProLights EclPar IPMFC user manual

ProLights

ProLights EclPar IPMFC user manual

Velvet EVO Series user manual

Velvet

Velvet EVO Series user manual

IDTOLIGHT GENT installation instructions

IDTOLIGHT

IDTOLIGHT GENT installation instructions

MAYTONI S35 installation manual

MAYTONI

MAYTONI S35 installation manual

MaxLite MLFP14DP4535 user manual

MaxLite

MaxLite MLFP14DP4535 user manual

SLV Elektronik 550621 instruction manual

SLV Elektronik

SLV Elektronik 550621 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.