Note: -The lamp must be installed by professional electrician
-Ensure the power supply is switched off before fitting this product
-Do not touch the lamp when in use
-Keep away from hot steam and corrosive gas
May 20, 2021
Installation
1. Remove the luminaire from its carton and inspect it for damage. If you believe the product to be damaged DO NOT install the product.
Please return it to the place of purchase for a replacement.
2. An emergency sustained luminaire requires two main active supplies. Un-switched active and switched active.
3. The un-switched active is required to charge the batteries. The switched active illuminates the luminaire on mains.
4. Both the switched active and un-switched active must be on the same phase.
5. (For 24/7 operation of the luminaire, link switched active with un-switched active)
6. To ensure maximum battery service life the battery pack is supplied not connected to the emergency luminaire. Before connecting the
emergency luminaire to the mains supply the battery pack must be connected to the emergency inverter via the polarized plug fitted
to the battery pack.
7. To ensure maximum product service life and performance, mount the emergency luminaire away from any direct heat source where the
ambient temperature exceeds 40 deg. C.
8. To check the correct operation of the luminaire, allow the battery to charge for a minimum of 3 minutes, ensuring that the green
charging LED is constantly illuminated. Depressing the test switch will then illuminate the emergency LED light.
9. Discharge time for 90 minute.
10. The product has an indicator light, the test button is used to detect whether the lamp is operating normally, and when press the test
button, the luminaire is in emergency mode; when release the test button, the battery is charged.
11. When the battery is charged, the green indicator light on; when the battery is fully charged, the green indicator light is on, when the
luminaire is in emergency mode, the indicator light will extinguish.
12. Emergency light source:>410 lm, CCT: 6500K.
Testing procedure
When the Stellar V EMG Batten is permanently connected to the mains allow 24 hours to fully charge the batteries. Once the batteries
are fully charged the emergency luminaire is required to undergo a commissioning discharge test to confirm compliance as specified
in Australian Standard AS2293 part 2. The emergency luminaire must operate for a minimum of 2 hours in emergency mode. Further
compliance testing is required at intervals of not more than six months, however for these tests the emergency luminaire must operate
for a minimum of 90 minutes in emergency mode.AS2293 part 2 also sets out the mandatory requirements of recording of all tests and
their results, plus any maintenance actions carried on the emergency luminaires. Energetic Lighting has available an emergency lighting
maintenance LOG book for recording of this information.
Problem Solving
If you have installed and connected the Stellar V EMG Batten and the product fails to work properly, please use the following table as a
starting guide to solve the issue.