
,
,
,
7. 5 HV600/1000 (BIBO for option)
Control panel functions
The “Local/Remote” selection switch is for
LOCAL or REMOTE fan motor on/off control
selecting. And the control panel also
provides one voltage free contact output for
indication of fan motor run/stop status.
The “Auto/Manual” selection switch for
AUTO or MANUAL cleaning control model
selecting. When the selection switch is at
the "Manual" position, the collector will clean
continually. When the selection switch is at
the "Auto" position, the collector cleaning will
controlled by the Torit Delta P-C01 controller
on the panel, and the control panel can also
provide down-time cleaning.
Fan motor overload protection and overload
When the “Local/Remote” selection switch is
set at “Remote” position, the start/stop of the
fan motor can be controlled remotely. When the
remote control switch is closed the “Running”
green indication light will light up and the fan
motor will be powered up; when the remote
control switch is opened the “Running” green
indication light will go off, and the fan motor
dis-energized.
When the "Local/Remote" selection switch is
set at "Local" position all control operations
need to be carried out locally at the control
panel. The fan motor can be turn on and off by
pushing the "Fan Start" and "Fan Stop" buttons
respectively. When push the “Fan Start”
button, the “Running” green indication light will
light up and the fan motor will be powered up;
when push the “Fan Stop” button the
“Running” green indication light will go off
and the fan motor dis-energized.
When the "Auto/Manual" selection switch is set
at "Manual" position, the cleaning will process
continually. When the "Auto/Manual" selection
switch is set at "Auto" position the cleaning will
be controlled by the Torit Delta P-C01 controller
on the panel. At any time the cleaning pulse is
activated, the “Cleaning” indication light on the
Delta P-C01 controller will light up.
7. 6 HV600/1000 (BIBO for option)
Operation
Ensure that the control panel is correctly
installed onto the dust collector before
starting up (check main power supply
connections, all electrical cable connections,
fan starter/fan motor connections,
solenoid/diaphragm valve connections,
compressed air tubing connections, etc.) For
safety of personnel and equipment, ensure
that the control panel is properly grounded.
Turn the main power supply switch to
"ON" position. The Torit Delta P-C01
controller will power up. All operating
instructions for the Torit Delta P-C01
controller are mentioned in a separate
manual of Delta P-C01.
There is overload protection for the fan
motor, the setting of AMPs according to
the nameplate of the fan motor. When
the "Error" indication light lights up it
signifies that the fan motor is overloaded
and has stopped.
To terminate electrical power supply to
the pulsing control, please ensure that
the fan motor is shut down before
turning the main power supply switch to
the "OFF" position.
For HV 600/1000 BIBO model will add 2
valves to discharge the dust and
particles, and these 2 valves will working
alternately and the alternating time can
be setting in the Logo controller.