dormakaba Installation manual Configuration of system doors
1. Remove the existing SLI license card and insert
the SLI-A application card.
‣ The SLI LED starts flashing when the
application has been loaded from the card to
the control unit.
→The SLI card is empty.
2. Remove the application card and insert the license
card again.
‣ The LED SLI lights up when the application
has been saved on the license card.
→The license card now contains the license and
the 2 additional functions.
3. Dispose of the SLI application card in an
environmentally friendly manner.
4. Document the use of the applications in each
system door’s inspection log.
5 Configuration of system doors
5.1 Configure the system doors
1. Press and hold the S4 service button on the SCU
with the license card for 12s.
‣ The LED indicator lights up solid blue for 4
seconds on all emergency buttons.
‣ The LED configuration and DCW® LED on the
STV xxx board flash slowly (2.5 Hz).
‣ The connected components are detected
and displayed on the relevant system door’s
illuminated ring (lights up blue).
2. Check if the connected components are displayed
with the correct address.
Display example for illuminated ring display in a
multi-door system with 4 doors:
System door 1:
SCU 1 STV 1 SCU 1 STV 1
or
(Display for use with (Display for use with
SCU-UP and SCU-TL) SCU-DR)
System door 2:
SCU 2 STV 2
System door 3:
SCU 3 STV 3
System door 4:
SCU 4 STV 4
3. Press and hold the S4 service button on the SCU
with the license card for 3s.
‣ The LED display turns permanently green
on all emergency buttons. The locks are not
activated yet.
4. Briefly push the key on each system door to the
left.
‣ The LED display changes to red.
→The locks are activated.
5. Check and document the unit’s correct function
(see also operation manual).
6 Parameterization of system
doors with TMS Soft®
The functions of the components and the SafeRoute®
system can be adapted with TMS Soft®. For more
information, see the TMS Soft® handbook and the
help function in TMSSoft®.
6.1 Requirements for parameterization
• The control unit must be connected to the TMS
Soft® computer via LON/LAN or directly via the
RS232 interface.
• The system doors must be inserted in TMSSoft®.
• The multi-door application must be activated (see
TMS Soft® > Communication, here: Applications
column).