Setting 2 Group (PRG Button Push for 10 Sec.)
No Menu Code Unit Step Min Max Default Custom Setup
4 0061 Lock Function LOC
OFF (0) : Lock cancel
LC 1 (1) : Setting 2 group lock
LC2 (2) : Setting 1,2 group lock
LC3 (3) : Setting 1, 2 group, temp. setup lock
OFF (0)
4 0062 SensorType IN
TH 1(0) : DPR-TH01 (-50~105°C)
TH2 (1) : DPR-TH02 (-50~150°C)
420 (2) : 4-20mA signal input (In case of connecting with press.&humidity sensor)
ST 1(3) : OUT1 set temperature (ST1) display
ST2 (4) : OUT1 set temperature (ST2) display
STD (5) : ST 1 or ST2 (※1)
TH 1
(0)
4 0063 Max. Sensor Input Range SH °C 1 SL 999 10 5
4 0064 Min. Sensor Input Range SL °C 1 -199 SH -50
4 0065 Unit of temperature UNT oC(0) : Celsius oF (1) : Fahrenheit oC(0)
4 0066 Decimal Point Display(※2) DP 0. 1
(0) : Decimal point display 1(1) : Do not display decimals 0. 1
(0)
4 0067 Sensor Correction(※3) COR °C 0.1 -19.9 19.9 0.0
4 0068 Sensor Input Filter SFT Sec 0.1 0.1 5.0 2.0
4 0069 Sensor Value Display Cycle SDT Sec 0.1 0 5.0 0.5
4 0070 Operation Cycle Output at Error
Occurrence #1(※4) CL1 Min 1 0 999 OFF(0)
4 0071 Operation Ratio Output at Error
Occurrence #1(※4) DU1 % 1 010 0 50
4 0072
AnalogueTrans.
Output(4~20mA) Mode
(-A1 model)
AOM
PV (0) : CurrentTemp. H(1) : Heating proportional control
C(2) : Cooling proportional control
ST 1
(3) : Set valueTemp.#1 ST2 (4) : Set valueTemp.#2
PV (0)
4 0073 Setup Value Unication Mode (※5) STO OFF (0) : Output #1, #2 separation mode
0N (1) : Unication mode OFF (0)
4 0074
Output #2, Select Extended
Function.
(Display TY2 as OFF)
N2
OFF (0) : Control output operate as the function set at TY2
T1M (7) :Timer output (Regular cycle timer output)
DFH (8) :Timer output (Regular cycle timer output : heater defrost)
DFG (9) :Timer output (Regular cycle timer output : hot gas defrost)
OFF (0)
4 0075 Output #2,Timer OFF Time
(Defrost Cycle) OF2 Min 1 0 999 360
4 0076 Output #2, Timer ON Time
(DefrostTime) ON2 Min 1 0 999 30
4 0077 Alarm Range High Limit (※7) ALH - 0.1 ALL SH 30.0
4 0078 Alarm Range Low Limit (※7) ALL - 0.1 SL ALH - 10
4 0079 Alarm Sensing Hysteresis AHY K 0.1 0 99.9 1. 0
4 0080 Communication Address (※8) ADR - 1 -64 64 1
Automatic reset alarm Manual reset alarm(※6)
AL1(1):
Output ON at sensor alarm +
high limit alarm
AL4 (4):
Output ON & manual reset at
sensor alarm + high limit alarm
AL2 (2):
Output ON at sensor alarm +
low limit alarm
AL5 (5):
Output ON & manual reset at
sensor alarm + low limit alarm
AL3 (3):
Output ON at sensor alarm +
high/low limit alarm
AL6 (6):
Output ON & manual reset at
sensor alarm + high/low limit alarm
(※1) STD : Sensor Value Display Value : Display set value of output 1,2 as present value by input ON/OFF.
(※2) Decimal Point Display : Decimal point display : It sets the current value display unit as 0.1/1. i.e. In case of setting as ‘1’, it displays the current value with cutting the decimal place.
(※3) Correct Temp. Sensor : Correct deviations of temperature sensor. e.g) if displayed temperature is 19°C and actual temperature is 18°C, it is corrected by inputting -1.0°C
(※4) Control Output Operation at Error Occurrence : When error occurs, control output repeatedly operates OFF/ON until error is reset.
e.g) In case of setting of operation cycle : 60minutes, ON ratio 20%, it repeatedly operates a cycle of OFF (48 minutes) / ON (12 minutes).
(※5) Setup Value Unication Mode : In case of setting this function as ON, setup value is unied and controlled as 1 case.
(※6) Manual Reset alarm : In case of selecting manual reset alarm, it is reset by re-inputting power or pushing PRG button rapidly 2 times.
(※7) In case of occurrence of high or low limit alarm, it doesn’t aect control output #1 at all.
(※8) Communication Address : Master mode address is to -1 from -64.
Communication Table
No Menu Unit Type Size (Word) FX MMI Scale
4 0101 Product status codes Digital INT 16 Refer to bit status below
Bit 0 Output 1 ON / OFF status Digital Bit 0 : OFF 1 : ON
Bit 1 Output 2 ON / OFF status Digital Bit 0 : OFF 1 : ON
Bit 8 Defrost output ON / OFF status Digital Bit 0 : OFF 1 : ON
Bit 12 Min. range alarm Digital Bit 0 : Normal 1 : Alarm
Bit 13 Max. range alarm Digital Bit 0 : Normal 1 : Alarm
Bit 14 Sensor (disconnection, short-circuit) Alarm Digital Bit 0 : Normal 1 : Alarm
Bit 15 EEPROM alarm Digital Bit 0 : Normal 1 : Alarm
4 0102 Current temperature value (PV) °C Analog INT 16 -50 ~ 105 -500 ~ 1050 1/10
4 0103 FND display current temp. value (PV) °C Analog INT 16 -50 ~ 105 -500 ~ 1050 1/10
4 0104 Output 1 (ST1) settings (*read only) °C Analog INT 16 -50 ~ 105 -500 ~ 1050 1/10
4 0105 Output 2 (ST2) settings (*read only) °C Analog INT 16 -50 ~ 105 -500 ~ 1050 1/10
4 0107 Command of compulsory defrost with manual Analog INT 16 1 : START (Auto-reset)
4 0108 Command of compulsory defrost termination Analog INT 16 1 : STOP (Auto-reset)
Change of BPS
Default value of this model is 4800bps and it should be changed separately.
1. Entry into parameter relating to BPS
Press PRG + SEL + ▲ + ▼ buttons simultaneously
for 5 seconds as shown in the figure
2. BDR BDR Communication Speed (Press the SEL button eight times)
Adjust BPS using ▲ / ▼ buttons from the BDR parameter
(
48 : 4800bps, 96 : 9600bps, 19 2 : 19200bps, 384 : 38400bps)
3. Store set value (Press the SEL button for three seconds)
Transmission line connection Multiple line
Communications method RS485 (2-wire, half-duplex)
BPS BPS default 4800 BPS
Parity, Data, Stop bit None, 8 Data, 1 Stop
ProtocolType Modbus RTU Mode
Function Code Read HOLD REGISTERS (0x03) / Preset Single Register (0x06)
Poll interval 100msec
Communication
FX3D
OUT1
OUT2