※1) ON delay time : It outputs after setting delay time in spite of output condition. During ON delay time, output lamp is turned on with output after flickering in fast cycle
※2) Min OFF Time : It lets output not occur within min. OFF time after it is turned off. During min. OFF time, output lamp is turned on with output after it flickers every 1 second intervals
※3) Min ON Time : It is for avoiding frequent ON/OFF of control output and maintains ON condition in spite of OFF condition during Min ON Time after being turned on.
(In case of sensor error, OFF at once)
※4) Output at Sensor Error : In case of sensor error such as open wire/short, it sets ON/OFF status of the related output.
※5) Manual Output Mode : OFF : Output by PV / ON : Output by MVI,MV2 (-R4 model)
※6) Manual Output Value Setup : It outputs continuously regardless of PV. if manual output value is ON when manual output mode is ON. (-R4 model)
Setting 1 Group (PRG Button Push for 3 Sec.)
No Menu Code Unit Step Min Max Default Custom Setup
4 0016
E V 1
Output
#1
Select ControlType TY1
OFF (0) : Display
C(1) : Cooling mode
H(2) : Heating mode
AL I (3) : Deviation high limit alarm
AL2 (4) : Deviation low limit alarm
AL3 (5) : Deviation high, low limit alarm
AL4 (6) : Deviation high, low limit reverse alarm
AL5 (7) : Absolute value high limit alarm
AL6 (8) : Absolute value low limit alarm
SBA (9) : Sensor open wire alarm
C (1)
4 0017 Control Deviation Value DF 1 K 0.1 0.1 99.9 2.0
4 0018 Select Deviation Value TP 1 P (0) : Deviation PN (1): ± Deviation P (0)
4 0020 ON DelayTime (※1) DT 1 Sec 1 0 999 1
4 0021 Minimum OFFTime (※2) FT 1 Sec 1 0 999 5
4 0022 Minimum ONTime (※3) NT 1 Sec 1 0 999 5
4 0023 Output at Sensor Error (※4) SF 1 OFF(0) 0N (1) OFF(0)
4 0024 Alarm Deviation Value H Y 1 K 0.1 0.0 99.9 1. 0
4 0025 Alarm Option A P 1 ALA(0): General alarm, ALB(1): Maintain alarm,
ALC(2): Standby alarm, ALD(3): Maintain & standby alarm ALA(0)
4 0026 High limit by user setup U H 1 %, °C 1 U L 1 10 5 10 0
4 0027 Low limit by user setup U L 1 %, °C 1 -50 U H 1 0
4 0028 Manual Output Mode Output (※5) M D 1 OFF(0) : Output by PV
(Present Value)
ON(1) : Output by MV2
(-R4 model) OFF(0)
4 0029 Manual Output Value Output (※6) M V 1 OFF(0) : Always output OFF ON(1) : Always output ON OFF(0)
4 0031
E V 2
Output
#2
Select ControlType TY2
OFF (0) : Display
C(1) : Cooling mode
H(2) : Heating mode
AL I (3) : Deviation high limit alarm
AL2 (4) : Deviation low limit alarm
AL3 (5) : Deviation high, low limit alarm
AL4 (6) : Deviation high, low limit reverse alarm
AL5 (7) : Absolute value high limit alarm
AL6 (8) : Absolute value low limit alarm
SBA (9) : Sensor open wire alarm
H(2)
4 0032 Control Deviation Value DF 2 K 0.1 0.1 99.9 2.0
4 0033 Select Deviation Value TP 2 P (0) : Deviation PN (1): ± Deviation P (0)
4 0035 ON DelayTime (※1) DT 2 Sec 1 0 999 1
4 0036 Minimum OFFTime (※2) FT 2 Sec 1 0 999 5
4 0037 Minimum ONTime (※3) NT 2 Sec 1 0 999 5
4 0038 Output at Sensor Error (※4) SF 2 OFF(0) 0N (1) OFF(0)
4 0039 Alarm Deviation Value H Y 2 K 0.1 0.0 99.9 1. 0
4 0040 Alarm Option A P 2 ALA(0): General alarm, ALB(1): Maintain alarm,
ALC(2): Standby alarm, ALD(3): Maintain & standby alarm ALA(0)
4 0041 High limit by user setup U H 2 %, °C 1 U L2 10 5 10 0
4 0042 Low limit by user setup U L 2 %, °C 1 -50 U H 2 0
4 0043 Manual Output Mode Output (※5) M D 2 OFF(0) : Output by PV
(Present Value)
ON(1) : Output by MV2
(-R4 model) OFF(0)
4 0044 Manual Output Value Output (※6) M V 2 OFF(0) : Always output OFF ON(1) : Always output ON OFF(0)