Introduction
The multifunction energy analyzer SMART X96-RC is innovative instrument for measurement of electrical parameters.
The meters are particulary suitable consuption analysis and ocntrol, with an excellent quality and stability. The meters
directly connected with Rogowski Coil for current measurement, without external integrator. The connectios are very quick
and easy, very useful for retrofitting applications on existing switchboards or energy audit. The meters are the ideal
instrument to establilish the measurement points on the plant. Built-in interfaces provides RS485 Modbus RTU.
SMART X96-RC series is a top new-generation intelligent panel meter with , used not only in the electricity transmission
and power distribution system, but also in the power consumption measurement and analysis in high voltage intelligent
power grid.
This document provides operating, maintenance and installation instructions for the Eastron SMART X96-RC series. The
meters measure and display the characteristics of 1p2w, 3p4w and 3p3w supplies, including voltage, frequency, current,
power and active and reactive energy, imported or exported, Power factor, Max. Demand etc. Energy is measured in terms
of kWh, kVArh and kVAh. Maximum demand current can be measured over preset periods of up to 60minutes.
The unit uses plug-in terminals for easy wiring and push-in mechanism for quick installation.
1. Unit Characteristics
1. 1 The Unit can measure and display:
●Active power, reactive power, apparent power, maximum power demand and power factor
●Max./ Min.Current and voltage, Max.current demand
●Import / export / total active energy
●Import / export / total reactive energy
●Total active energy of each phase
●DPF ( Displacement Power factor, Modbus read only)
●Voltage crest factor (Modbus read only)
●Current K factor (Modbus read only)
1.2 The unit has password-protected set-up screens for:
●Communication setting: Modbus address, Baud rate, Parity, Stop bit
●CT setting: CT 1 ( Max current input)
●PT setting: PT1 (Primary), PT2 (Secondary) , PT rate
●Demand setting: demand method, Demand interval time
●Time setting: Backlit time, display scroll time, system RTC, Tariff Time
●System configuration: System type, System connect, Change password, Auto display scroll
1.3 CT and PT
CT1 (Max value): 3 selectable scaless 1000A/ 5000A / 20000A.
PT1 (primary voltage): 100V ~ 500,000V
PT2 (secondary voltage): 100 to 600 V AC (L-L)
1.4 RS485 Serial-Modbus RTU
____________________________________________________________________________________________________________________