The multifunction energy analyzer SMART X96 series is a top new-generation intelligent panel meter, used not only in the
electricity transmission and power distribution system, but also in the power consumption measurement and analysis in
high voltage intelligent power grid.
This document provides operating, maintenance and installation instructions for the Eastron SMART X96 series. The unit
measures and displays the characteristics of 1p2w, 3p4w and 3p3w supplies, including voltage, frequency, current, power
and active and reactive energy, imported or exported, Harmonic, Power factor, Max. Demand etc. Energy is measured in
terms of kWh, kVArh and kVAh. Maximum demand current can be measured over preset periods of up to 60minutes.
In order to measure energy, the unit requires voltage and current inputs in addition to the supply required to power the
product. The requisite current input(s) are obtained via current transformers. The SMART X96 can be configured to work
with a wide range of CTs, giving the unit a wide range of operation. Built-in interfaces provides RS485 Modbus RTU and
Ethernet TCP/IP communication. Digital input and outputs are provided for external signal counting and external device
control. 30 types parameters can be set for alarm.
The unit uses plug-in terminals for easy wiring and push-in mechanism for quick installation.
1. Unit Characteristics
1. 1 The Unit can measure and display:
●Line voltage and THD% (total harmonic distortion) of all phases
●2~63rd voltage IHD% (Individual Harmonic distortion) of all phases
●Line Frequency
●Phase Sequence
●Currents, Current demands and current THD% of all phases
●2~63rd current IHD% of all phases
●Active power, reactive power, apparent power, maximum power demand and power factor
●Max./ Min.Current and voltage, Max.current demand
●Import / export / total active energy
●Import / export / total reactive energy
●Total active energy of each phase
●Multi Tariff active energy
●DPF ( Displacement Power factor, Modbus read only)
●Voltage crest factor (Modbus read only)
●Current K factor (Modbus read only)
1.2 The unit has password-protected set-up screens for:
●Communication setting: Modbus address, Baud rate, Parity, Stop bit
●CT setting: CT 1 ( Primary) , CT2 ( Secondary), CT rate
●PT setting: PT1 (Primary), PT2 (Secondary) , PT rate
●Demand setting: demand method, Demand interval time
●Time setting: Backlit time, display scroll time, system RTC, Tariff Time
●System configuration: System type, System connect, Change password, Auto display scroll
●DI setting: DI filter time ,DI count,
●DO setting: Alarm setting, Delay time, HC(high value to close), HO (High value to open), LO(Low value to open), LC(low