manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Eaton
  6. •
  7. Accessories
  8. •
  9. Eaton Cutler Hammer CurrentWatch EGF Series User manual

Eaton Cutler Hammer CurrentWatch EGF Series User manual

IN ORDER TO AVOID ELECTRIC SHOCK OR OTHER POSSIBLE INJURY:
• DO NOT USE THIS PRODUCT FOR HUMAN SAFETY APPLICATIONS.
IT WAS NOT DESIGNED, TESTED OR RECOMMENDED FOR THIS
USE.
• DO NOT USE THIS PRODUCT IN HAZARDOUS LOCATIONS (E.G.
EXPLOSIVE ATMOSPHERES). IT WAS NOT DESIGNED, TESTED OR
RECOMMENDED FOR THIS USE.
• ENSURE THE PRODUCT IS PROPERLY WIRED TO THE CORRECT
POWER SUPLLY FOR THE APPLICATION. REFER TO THE
SPECIFICATIONS AND WIRING DIAGRAMS IN THIS MANUAL.
MODELS COVERED IN THIS MANUAL
Catalog Number Description
EGF1NCLA050 120V AC, N.C. SPST Relay, 50 mA Setpoint
EGF1NOLA050 120V AC, N.O. SPST Relay, 50 mA Setpoint
EGF1NCLA100 120V AC, N.C. SPST Relay, 100 mA Setpoint
EGF1NOLA100 120V AC, N.O. SPST Relay, 100 mA Setpoint
EGF1NCLAT3 120V AC, N.C. SPST Relay, 5/10/30 mA Setpoint, Tri-Set
EGF1NOLAT3 120V AC, N.O. SPST Relay, 5/10/30 mA Setpoint, Tri-Set
EGF2NCLA050 24V AC/DC, N.C. SPST Relay, 50 mA Setpoint
EGF2NOLA050 24V AC/DC, N.O. SPST Relay, 50 mA Setpoint
EGF2NCLA100 24V AC/DC, N.C. SPST Relay, 100 mA Setpoint
EGF2NOLA100 24V AC/DC, N.O. SPST Relay, 100 mA Setpoint
EGF2NCLAT3 24V AC/DC, N.C. SPST Relay, 5/10/30 mA Setpoint, Tri-Set
EGF2NOLAT3 24V AC/DC, N.O. SPST Relay, 50/10/30 mA Setpoint, Tri-Set
INTRODUCTION
The CurrentWatch™ EGF Series is a family of
ground fault (earth leakage) sensors. Ground
fault sensors help protect people, products, and
processes from damage by ground fault
conditions by monitoring all current-carrying
conductors in grounded single- and three-
phase delta or wye systems.
The EGF Series with mechanical outputs are
available in solid-core housings with a choice of N.O. or N.C. SPST
latching relays. All mechanical models can be ordered with a fixed
setpoint or with a “tri-set” option, which provides three factory-set, field
adjustable setpoints.
Note that this manual only covers EGF Series models listed in the
above table. This installation manual does not cover EGF Series
models with auto-reset.
QUICK INSTALL GUIDE
The below steps can be followed to quickly install a CurrentWatch™
EGF Series switch.
1. Run all current carrying conductors through sensor window, using
an auxiliary current transformer if conductors do not fit
2. Mount the sensor to a surface if needed
3. Connect output and power wiring
a. Use up to 14 AWG copper wires
b. Ensure power and load matches those shown on the sensor
label
4. Test the unit
a. Pressing the “TEST” button will test the sensor’s internal
circuits
b. CAUTION: The output and any connected loads will switch
during the test process
INSTALLATION AND MOUNTING
Considerations for all EGF Series sensors…
• Run wire to be monitored through the aperture (opening) in the
switch body, making sure all wires are oriented so that current
flows in the same direction (see “Principal of Operation” section
on reverse side)
• These sensors can be located in the same environment as motors,
contactors, heaters, pull-boxes and other electrical enclosures
• Mounting can be done in any position or hung directly on a wire
with a wire tie
• Be sure to leave at least one inch distance between sensor and
other magnetic devices
Considerations for wiring EGF Series sensors…
• Use up to 10 AWG copper wire and tighten terminals to 4.5 inch-
pounds torque
• Connect power wiring to terminals 1 and 2, making sure that the
power supply matches the power rating on the sensor label
• Connect output wiring to terminals 3 and 4
PRINCIPAL OF OPERATION
Under normal conditions, the current in one wire of a two wire load is
equal in strength but opposite in sign to the current in other wire. The
two wires create magnetic fields that cancel, a condition known as
“Zero Sum Current.” If any current leaks to ground (Ground Fault), the
two currents become unbalances and there is a net resulting magnetic
field. The EGF Series sensor detects this minute field and change the
output state. This concept extends to three phase systems such as 3-
wire Delta and to 4-wire Wye.
Single Phase
(Phase to Neutral or
Phase to Phase)
Three-Phase Delta
(Includes Neutral if
Load Uses Neutral)
Three-Phase Wye
(Include Neutral if
Load Uses Neutral)
Three-Phase Load
(Using Auxiliary CT)
P51923 Rev 01
Effective: April 2007 Page 1
WARNING
Questions? Call our Sensor Application Engineers at (800) 426-9184.
490050021
Installation Instructions
CurrentWatch™ EGF Series Ground Fault Sensors
120V AC or 24V AC/DC, N.O. or N.C. SPST Latching Relay Output
P51923 Rev 01
Effective: April 2007 Page 2
Questions? Call our Sensor Application Engineers at (800) 426-9184.
4,000 ohms should provide a load of 30 mA at 120V AC, or a night light
bulb of 4 watts should relate to 33 mA. With the load energized and
passing through the sensing aperture, turn the potentiometerclockwise
until the sensor trips. Then, back one-eighth of a turn and the setpoint
should be correct.
When used with an external current transformer (CT), the sensor will
be set to trip at a point much lower than without the CT. This set point
adjustment should be done with the load passing through the CT in that
application.
POWER SUPPLY NOTES
All low-current ground-fault sensors are sensitive devices that require
reasonable care in system design to avoid false trips caused by high
electrical noise levels. Keep in mind that the best way to reduce noise in
a system is to suppress it at its source.
• Keep the sensor power isolated from noisy circuits
• Do not power the sensor with the same circuit that switches
contactors or other high current inductive loads
SYSTEM GROUNDING
Good design practice and code require that all AC power systems be
grounded. The EGF Series sensors are designed to work on grounded
AC power systems. They may not operate properly on ungrounded
systems.
SPECIFICATIONS
Specification Value
Power Supply 120V AC (Operates from 66-132V)
24V AC/DC (Operates from 19.2-28.8V)
Voltage Range Up to 1,500V AC (Monitored Circuit)
Power Consumption 2.5W
Output Latching Electromechanical Relay
Normally Open Models Latch Closed Upon Sensed Fault Current
Normally Closed Models Latch Open Upon Sensed Fault Current
Output Rating 1.0A @ 120V AC
2.0A @ 30V AC
Response Time At 5% Over Setpoint: 200 ms
At 50% Over Setpoint: 60 ms
At 500% Over Setpoint: 15 ms
Setpoint Range Selectable by Model
Fixed Setpoints: 50, 100 mA
Adjustable Setpoints: 5, 10, 30 mA (By Jumper)
Setpoint Adjustment See “Adjust Setpoint” in “Operation” Section
Frequency Range 50-400Hz (Monitored Circuit)
Housing UL94 V0 Flammability Rated
Dimensions Case: 2.5 in. H x 2.8 in. W x 1.5 in. D (64x71x38mm)
Aperture: 0.75 in. (19mm)
LED Green = Power Supply Energized
Red = Relay Has Operated
Environmental Operating Temperature: +5 to +158° F (-15 to +70° C)
Humidity: 0-95% RH, Non-Condensing
Approvals UL Recognized
490050021
WIRING
Use up to 14 AWG copper wire and tighten terminals to 4.5 inch-
pounds torque. See diagram below.
Power
Connect power wiring to Terminals 1 and 2. Be sure that the power
supply matches the power rating on the sensor label.
Output
Connect output wiring to Terminals 3 and 4.
Reset Switch
Connect a momentary dry contact to the Reset Terminals 5 and 6. Limit
wire run to 200 feet of 18 AWG or larger wire.
Momentary Reset
Only close the reset terminals momentarily—the sensor will not work
properly if the reset terminals are closed (shorted) continuously. Limit
wire run to 200 feet of 18 AWG or larger wire.
Parallel Reset Connection
Multiple sensors may be connected to the same reset switch in parallel.
Only the sensors that have detected a fault and have latched will
be reset. A sensor will not reset unless the fault has dropped below
setpoint.
OPERATION
The EGF Series latching ground fault sensors operating in one of two
states: Reset or Latched. If control power is removed, the sensor
remains in it’s last state (latched or reset).
Reset
The sensor has not detected a fault and the output is in the “normal”
position. For Normally Open (N.O.) sensors, the contact is normally
open in the reset condition. For Normally Closed (N.C.) sensors, the
contact is normally closed in the reset position.
Latched
Upon detecting a fault or when the TEST switch is pressed, the output
will switch and “latch.” The output will remain latched until the ground
fault is removed and the output is reset by a momentary dry contact on
Terminals 5 and 6.
Testing
To test operation, gently press the TEST button. This simulates a fault
and tests the internal switching circuits. After the test is complete,
reset the sensor with a momentary dry contact on Terminals 5 and 6.
CAUTION: Any circuit connected to the sensor will be operated.
Adjusting Setpoint
While not as precise as having it set at the factory, the setpoint can be
adjusted in the field. See wiring diagram for location of potentiometer.
The best way to adjust the trip point is to develop a load of the
magnitude at which you want the sensor to trip. A resistor of
Red Status LED (On When Tripped)
Setpoint Adjustment
(Located Under Label)
Test Button
(Caution: Will Activate Output Relay)
External Reset Button (5 and 6)
Output (3 and 4)
Power Supply Input (1 and 2)
Power (Green) LED
(On if Power is Applied)
123456
GR TEST

This manual suits for next models

16

Other Eaton Accessories manuals

Eaton EAFR-01 User manual

Eaton

Eaton EAFR-01 User manual

Eaton CBMD-02 Series Manual

Eaton

Eaton CBMD-02 Series Manual

Eaton xComfort CTEU-02/0 Series User manual

Eaton

Eaton xComfort CTEU-02/0 Series User manual

Eaton CurrentWatch ECSJ Series Manual

Eaton

Eaton CurrentWatch ECSJ Series Manual

Eaton xComfort CSEZ-01/18 User manual

Eaton

Eaton xComfort CSEZ-01/18 User manual

Eaton Series NRX Manual

Eaton

Eaton Series NRX Manual

Eaton Crouse-Hinds GHG 515 User manual

Eaton

Eaton Crouse-Hinds GHG 515 User manual

Eaton SVPD Series Operating instructions

Eaton

Eaton SVPD Series Operating instructions

Eaton E67 Series Manual

Eaton

Eaton E67 Series Manual

Eaton Crouse-hinds series User manual

Eaton

Eaton Crouse-hinds series User manual

Eaton ALL-PRO MSS1301LW User manual

Eaton

Eaton ALL-PRO MSS1301LW User manual

Eaton CurrentWatch EPRM Series User manual

Eaton

Eaton CurrentWatch EPRM Series User manual

Eaton iProx Series Instruction manual

Eaton

Eaton iProx Series Instruction manual

Eaton GHG 521 User manual

Eaton

Eaton GHG 521 User manual

Eaton CurrentWatch EAC Series Manual

Eaton

Eaton CurrentWatch EAC Series Manual

Eaton xComfort Manual

Eaton

Eaton xComfort Manual

Eaton Crouse-Hinds GHG 514 User manual

Eaton

Eaton Crouse-Hinds GHG 514 User manual

Eaton Water Guard CWGE-0 Series Manual

Eaton

Eaton Water Guard CWGE-0 Series Manual

Eaton Comet Series Manual

Eaton

Eaton Comet Series Manual

Eaton E52 Series Manual

Eaton

Eaton E52 Series Manual

Eaton GridAdvisor II Series User manual

Eaton

Eaton GridAdvisor II Series User manual

Eaton E65 SM Series Manual

Eaton

Eaton E65 SM Series Manual

Eaton CEMU-01/03 User manual

Eaton

Eaton CEMU-01/03 User manual

Eaton IntelliView Series Manual

Eaton

Eaton IntelliView Series Manual

Popular Accessories manuals by other brands

Honeywell RPW314 Instruction leaflet

Honeywell

Honeywell RPW314 Instruction leaflet

ipf electronic OT0591A4 manual

ipf electronic

ipf electronic OT0591A4 manual

Siemens HFPO-11 installation guide

Siemens

Siemens HFPO-11 installation guide

Nordic OY1500 product manual

Nordic

Nordic OY1500 product manual

Netio PowerBOX 3PF manual

Netio

Netio PowerBOX 3PF manual

3M MODULE A125 installation instructions

3M

3M MODULE A125 installation instructions

ACADEMY Summit Classic Deluxe Tripod 12 Leg Kit manual

ACADEMY

ACADEMY Summit Classic Deluxe Tripod 12 Leg Kit manual

SkyLink PS-SD1-CH manual

SkyLink

SkyLink PS-SD1-CH manual

JUKI UT59 specification

JUKI

JUKI UT59 specification

NAIM ARO manual

NAIM

NAIM ARO manual

Viking DDWB301CRSS installation instructions

Viking

Viking DDWB301CRSS installation instructions

ASM Posirot PRAS2 instruction manual

ASM

ASM Posirot PRAS2 instruction manual

PCB Piezotronics IMI SENSORS 640B06 Installation and operating manual

PCB Piezotronics

PCB Piezotronics IMI SENSORS 640B06 Installation and operating manual

Aeotec MULTISENSOR 6 manual

Aeotec

Aeotec MULTISENSOR 6 manual

Minebea Intec Contego installation manual

Minebea Intec

Minebea Intec Contego installation manual

iNels RFDSC-71N manual

iNels

iNels RFDSC-71N manual

Proxitron LIA 010 user manual

Proxitron

Proxitron LIA 010 user manual

Panasonic AY-PB2003 operating instructions

Panasonic

Panasonic AY-PB2003 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.