manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Eaton
  6. •
  7. Control Unit
  8. •
  9. Eaton Scantronic i-on10 User manual

Eaton Scantronic i-on10 User manual

Scantronic
Specications
Standards and Compliance
The installer must remove or adjust any compliance labelling if a
non-compliant configuration is selected.
Intrusion compliance: EN 50131-1:2007+A2:2017; EN 50131-3:2009;
EN 50131-6:2017+A1:2021; EN 50131-10:2014; EN 50136-2:2013;
BS8243:2010; PD6662:2017
Security grade: Grade 2.
Environmental class: Class II.
Protection: IP40, IK06.
Security
Access codes: 4-digit, giving 10,000 combinations. 6-digit, giving
1,000,000 combinations.
Code blocking: Blocked for 90 secs after 4 incorrect codes in series.
Proximity tag differs: 4,294,967,296.
General
Relative Humidity: 0 to 93%, non-condensing.
Operating temp. range: -10°C to +55°C.
Dimensions: 239mm (h) x 250mm (w) x 87mm (d).
Weight: 2.8kg (without battery).
Case material: Steel.
Electrical
This product complies with the requirements of EN50131-6Type A
power supply at Grade 2 and environmental class II.
Mains power supply: 230Vac + 10%/-15%, 200mA max, 50Hz.
Control unit internal mains fuse: T250mA.
Control unit power supply: 13.7Vdc, 1.0A max of which 180mA is
reserved for battery recharge and 820mA to power the system.
Control unit PCB current consumption: 40mA quiescent; 70mA max
(in alarm) excluding external devices and battery charging.
Standby battery: 12V, 7Ah, sealed lead acid. Min standby time:12
hrs. (see “Step 2: Check standby battery capacity”). Max recharge
time: 72 hrs.
12V aux: 600mA max*
12V bus: 400mA max*
12V to plug-by communicator: 400mA max*
*Maximum current before triggering over-current protection.
Output voltage range: 12V outputs are 9.5Vdc to 13.8Vdc.
Max p-to-p ripple voltage: 0.5V.
Low-battery fault at: <12V.
Aux power output fault at: <9V.
OP1-3: Open collector transistor, 500mA max.
Plug-by outputs: Open collector transistor, 50mA max.
Loudspeaker: 12Vdc, 280mA max. Min impedance 16 Ohm.
The information, recommendations, descriptions and safety notations in this document are
based on Eaton Corporation’s (“Eaton”) experience and judgment and may not cover all
contingencies. If further information is required, an Eaton sales office should be consulted.
Sale of the product shown in this literature is subject to the terms and conditions outlined
in appropriate Eaton selling policies or other contractual agreement between Eaton and the
purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR
IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OTHERTHAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING
CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE
OBLIGATION OF EATON. THE CONTENTS OFTHIS DOCUMENT SHALL NOT BECOME PART
OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including
negligence), strict liability or other-wise for any special, indirect, incidental or consequential
damage or loss whatsoever, including but not limited to damage or loss of use of
equipment, plant or power system, cost of capital, loss of power, additional expenses in
the use of existing power facilities, or claims against the purchaser or user by its customers
resulting from the use of the information, recommendations and descriptions contained
herein. The information contained in this manual is subject to change without notice.
© 2022 Eaton
Eaton, Security House, Vantage Point Business Village, Mitcheldean, GL17 0SZ.
www.myscantronic.com
Product Support (UK) Tel: +44 (0) 1594 541978 available 08:30 to 17:00 Monday to Friday.
email: securitytec[email protected]
i-on10 Control Unit
Installation Instructions
The i-on10 is a 10-zone grade-2-compliant control unit.The i-on10
provides a reliable, easy-to-install, wired solution for domestic and
small commercial applications.
Key features
•Supports up to 10 wired zones, all provided on-board.
•Compatible with a range of wired detectors, including PIR sensors
and door contacts.
•Supports up to four keypads connected to the system bus.
•Grade 2 compliant.
•Support for one full-set level and up to three part-set levels.
•Configurable through a keypad.
•On-board connections for wired siren/strobe unit.
•On-board open-collector output to operate an external auxiliary
device.
•Plug-by communicator port with 8 outputs to communicate with
an alarms-receiving centre (requires MISC-COMPACK12 and a
suitable standalone communicator, such as 0840UK-21).
•Metal case, fitted with a 1A power supply and space for a 12Vdc
7Ah backup battery.
•Back and lid tamper switches.
•Support for up to 10 users.
Safety Information
This product must be installed by qualified service personnel.
WARNING: BEFORE INSTALLING THIS EQUIPMENT, ENSURE THAT
THE MAINS SUPPLY FORTHE CONTROL UNIT IS DISCONNECTED
AND ISOLATED. All electrical connections must be carried out by a
qualified electrician and comply with current local regulations.
WARNING: When connected to the mains with power applied, mains
voltages are present on the shrouded heads of the terminal screws
of the mains connector (Figure 4).
WARNING: The mains cable to the control unit must use a double-
pole isolation device in accordance with EN 62368-1.
WARNING: Good practice requires that documentation is not stored
within the enclosure.
Caution: If you need to handle the PCB in the control unit, take
standard precautions to prevent damage by static electricity.
Installing the control unit
Step 1: Choose a location for the control unit
The control unit must be located:
•Within the protected area (but not in an entry or exit zone).
•Out of sight of potential intruders.
•Upright (battery at the bottom) on a wall or other flat surface (to
discourage tamper attempts from the rear).
Step 2: Check standby battery capacity
Check that the battery is able to power the system for at least 12
hours during a mains failure, including two periods of 15 minutes in
alarm. This is the minimum period for grade 2 compliance.
To do this, you will need to calculate the total current drawn
from the battery during a mains failure. Please refer to the
i-on10
Configuration Guide
for worked examples.
Step 3: Install cabling
Note the following (refer to the
i-on10 Configuration Guide
for
guidance):
•Normally, standard 7/0.2 un-screened alarm cable is suitable for
wiring to keypads and wired siren/strobe units.
•Screened cable may be needed if the cable runs near to sources
of electromagnetic interference.
•Keep cables to keypads separate from any other wiring.
•You can connect keypads using a daisy-chain (serial) or star
(parallel) configuration.
•Cables must enter the control unit using the dedicated cable-entry
holes (Figure 1).
•The maximum length of the cable to keypads depends on a
number of factors, including the number of keypads and whether
daisy-chain or star connections are used.
Step 4: Remove the lid of the control unit
Release the two screws on the front of the lid, then lift it off.
Step 5: Mount the control unit
Mount the control unit in the orientation shown in Figure 1 using the
three fixing holes and minimum 40mm long No8 (4mm) screws. Use
only the designated cable-entry holes.
L N
Mains cable
entry
Signal cable
entry
Mains
terminals
Fixing holes
Signal cable entry
Figure 1. Fixing holes and cable entries
Part number 14199588
Issue 2 24/01/22
Step 6: Position the communicator and fit the fourth
pillar
If a communicator is used, position it under the PCB.
Fit the supplied fourth pillar for the PCB (see Figure 2), and secure
the PCB to the pillar using the supplied M3x12 screw.
Figure 2. Fitting the fourth pillar
Step 7: Connect all wired devices
Connect all wired devices except the battery, as shown in Figure 3.
Step 8: Connect the battery
Note: Connecting the battery does not start the system.
Fit a 7Ah lead-acid battery in the bottom-left corner of the control
unit.
Connect the battery leads to the battery (red to positive and black to
negative), and connect the transformer lead to the PCB (Figure 3).
Step 9: Connect the mains cable
L N
WARNING: ENSURE THAT THE MAINS
SUPPLY IS DISCONNECTED AND
ISOLATED.
Connect the mains cable to the terminal
block (Figure 4) and fit a strain-relief tie.
Do not apply power until after the lid is
re-fitted.
Figure 4. Mains connections
Step 10: Re-fit the lid, switch on and configure the
system
WARNING: During initial power-up, keypad sounders and any
internal loudspeaker may give an alarm tone. If you are working at
the top of a ladder, make sure that the sudden noise does not startle
you and cause a fall.
Re-fit the lid, then switch on the mains supply to the control unit.
Go through the initial configuration prompts and set up the system
as described in the
i-on10 Configuration Guide
. You are prompted to
specify installer and user codes during initial system configuration.
PCB links and connectors
The following sections provide information about the links and
connectors shown in Figure 3.
a Plug-by communicator port
You can connect a plug-by communicator to this port using an
optional MISC-COMPACK12 wiring harness (available separately).
By default, outputs 1-8 are 0V when active, and 12Vdc when inactive.
Please refer to the
i-on10 Configuration Guide
for the default output
type used for each output and programming details.
Connect LF (Line Fail) to an output from the communicator that is
12Vdc when communicator detects that there is a communications
fault to the ARC, and 0V when no fault is present.
If a dual-path (landline and mobile) communicator is used, such as
a RedCARE STU, re-program one of the plug-by outputs to type ATS
Test, and wire that to the ATS Test input of the communicator. Also
connect Line Fail to the Line Fail output of the communicator, as
above.This is needed to comply with BSIA Form No. 175, April 2005.
The control unit generates an “ATE LF Single” alert if one network is
unavailable, or “ATE LF All” if both are unavailable.
Connect RR (Remote Reset) to an output from the communicator
that indicates to the control unit that a user can reset the system
after a system tamper. The input must be 12Vdc for at least 100ms to
indicate the reset, and 0v normally. For further details, see “Remote
Reset (Redcare Reset)” in the
i-on10 Configuration Guide
.
Note: During system commissioning, confirm with the ARC that the
communicator is working correctly.
b System bus
Up to four keypads can connect to the system bus. The installation
instructions supplied with each keypad provide details of how to
install the device. The address of each device is set by the control
unit, as described in the
i-on10 Configuration Guide
.
Please refer to “Step 3: Install cabling” for guidance about cabling.
See also “RS485 bus termination link”.
c Loudspeaker connections
If fitted, a loudspeaker mimics alarm tones and repeats setting and
entry tones. The loudspeaker must be a minimum of 16 Ohms.
Note:
•A loudspeaker is not a warning device as described by EN50131-4.
•You can set the loudspeaker volume from the Installer menu.
d Open-collector (wired) output
The open-collector transistor output can be used to switch external
equipment on or off. By default, the output is 12Vdc when inactive
and 0V when active (this can be reversed from the Installer menu).
e Siren/strobe connections
Please refer to the installation instructions provided with the siren/
strobe unit for connection details.
f Wired zone connections
You can connect up to 10 wired detectors (0 to 9) to the control unit
using the Fully-Supervised Loop (FSL), 4-wire Closed Circuit (CC) or
2-wire CC wiring method (Figure 5). You must use the same method
for all detectors. If 4-wire CC is used, the number of zones is halved
and are numbered 1-5. To maintain ten 4-wire CC zones (0-9), fit an
ADP-10CC board and configure the resistance setting of each zone as
2k2/4k7.
For any method, the total wiring and switch resistance must be less
than 100 Ohms (EOL resistor shorted in the case of FSL).
By default, the system assumes normally-closed contacts. Detectors
with normally-open contacts must be programmed with the
“Inverted” attribute set.
Please refer to the
i-on10 Configuration Guide
for wiring details if
you want to use two detectors per zone.
Z0
Z1
EOL
Zone 1
Zone 0
Z1
Z0
Z1
Z0
Tamper Zone 1
Alarm Zone 1
Zone 0
Zone 1
4-Wire CC Wiring2-Wire CC Wiring
FSL Wiring (default) Supported resistor values (± 5%):
EOL Alarm
2k2 4k7 (default)
1k0 1k0
2k2 2k2
4k7 4k7
Alarm
Alarm
Tamper
EOL Tamper
Z0
Z1
Tamper
Tamper
Alarm
Alarm
8k2
8k2
8k2
8k2
FSL Wiring, with 8k2 resistors
Figure 5. Zone wiring
g Kick-start link
Ordinarily, the control unit starts only after the mains supply is
switched on, even if a battery is connected. If you want to operate
the control unit temporarily using only the battery, start the control
unit by briefly shorting this link.
h Reset codes link
You can use this link to reset the installer and all user codes (e.g.
in the event that codes have been forgotten). All proximity tags are
also deleted. This link can be enabled or disabled by a setting in the
Installer menu. Please refer to the
i-on10 Configuration Guide
for
further details.
i RS485 bus termination link
If the control unit uses a single daisy chain to connect keypads and
is at one end of the chain, fit a jumper across this link in the control
unit and in the last keypad on the bus. RS485 termination can
improve performance in electrically noisy environments. The
i-on10
Configuration Guide
gives further guidance.
Maintenance
Inspect the control unit once or twice per year as part of general
inspection of the whole system. At the control panel, check for any
damage, test the battery, and check the action of the tamper switch.
Please refer to the
i-on10 Configuration Guide
for general guidance
about maintaining the whole system.
Figure 3. Control unit PCB
1
2
3
4
5
6
7
8
LF
RR
0V
12V
Z0
Z1
Z2
Z3
Z4
Z5
Z6
Z7
Z8
Z9
A
B
+12V
0V
0V
0V
A
B
+12V
0V
12V AUX
12V AUX
LS-
LS+
OP3
OP2
OP1
TR
BELL/SIREN
STROBE
12Vdc
0V
TR
eSiren/strobe unit. Note:
If a siren/strobe unit is not
fitted, connectTR to 0V.
cLoudspeaker
h Reset
codes link
a Plug-by
communicator port
For engineering use only
fZones 0 to 9
0V/12Vdc
outputs
dOpen-
collector output
bStstem bus
(Max 4 keypads)
Keypad 1
iRS485
termination
gKick-start link
Connect transformer
Connect battery lead
Fit supplied
pillar

Other manuals for Scantronic i-on10

1

Other Eaton Control Unit manuals

Eaton COOPER POWER SERIES Troubleshooting guide

Eaton

Eaton COOPER POWER SERIES Troubleshooting guide

Eaton Crouse-hinds series User manual

Eaton

Eaton Crouse-hinds series User manual

Eaton PKE-COM-RTU Manual

Eaton

Eaton PKE-COM-RTU Manual

Eaton RF96APM User manual

Eaton

Eaton RF96APM User manual

Eaton Crouse-hinds series User manual

Eaton

Eaton Crouse-hinds series User manual

Eaton Power Xpert PXGX Programming manual

Eaton

Eaton Power Xpert PXGX Programming manual

Eaton SystemStak DGM-5-30 Series User manual

Eaton

Eaton SystemStak DGM-5-30 Series User manual

Eaton SL7-AP Series Manual

Eaton

Eaton SL7-AP Series Manual

Eaton 9395 SSBM User manual

Eaton

Eaton 9395 SSBM User manual

Eaton HMIVU04CUNBE Manual

Eaton

Eaton HMIVU04CUNBE Manual

Eaton CEAG DLS/3PH-BUS-Module-inverse Service manual

Eaton

Eaton CEAG DLS/3PH-BUS-Module-inverse Service manual

Eaton MFD-TP12 Series Manual

Eaton

Eaton MFD-TP12 Series Manual

Eaton Crouse-hinds series User manual

Eaton

Eaton Crouse-hinds series User manual

Eaton Digitrip RMS 910 Manual

Eaton

Eaton Digitrip RMS 910 Manual

Eaton Vickers FCGT-02-A-11 Series User manual

Eaton

Eaton Vickers FCGT-02-A-11 Series User manual

Eaton Eaton 5PX Assembly instructions

Eaton

Eaton Eaton 5PX Assembly instructions

Eaton EWFFSC15 User manual

Eaton

Eaton EWFFSC15 User manual

Eaton Crouse-hinds series User manual

Eaton

Eaton Crouse-hinds series User manual

Eaton Form 4D Recloser Control User manual

Eaton

Eaton Form 4D Recloser Control User manual

Eaton BBA 16 Series Manual

Eaton

Eaton BBA 16 Series Manual

Eaton Powerware Series User manual

Eaton

Eaton Powerware Series User manual

Eaton OPTC4 LonWorks User manual

Eaton

Eaton OPTC4 LonWorks User manual

Eaton xComfort Room-Manager User manual

Eaton

Eaton xComfort Room-Manager User manual

Eaton Cutler-Hammer Digitrip RMS 510 Manual

Eaton

Eaton Cutler-Hammer Digitrip RMS 510 Manual

Popular Control Unit manuals by other brands

Avalue Technology ECM-TGU-B1 user manual

Avalue Technology

Avalue Technology ECM-TGU-B1 user manual

KSB BOAX- B operating instructions

KSB

KSB BOAX- B operating instructions

WABCO IR-2 Technical bulletin

WABCO

WABCO IR-2 Technical bulletin

homexpert evohome Installation & user guide

homexpert

homexpert evohome Installation & user guide

Panasonic AK-UCU500P operating instructions

Panasonic

Panasonic AK-UCU500P operating instructions

rtd cpuModules CMA34CR user manual

rtd

rtd cpuModules CMA34CR user manual

SonicWALL SonicWall M.2 installation guide

SonicWALL

SonicWALL SonicWall M.2 installation guide

Stahl 9191/20-00-50 operating instructions

Stahl

Stahl 9191/20-00-50 operating instructions

Maple Systems iR-AI04-TR Series Installation instruction

Maple Systems

Maple Systems iR-AI04-TR Series Installation instruction

VALSTEAM ADCA M3HP Installation and maintenance instructions

VALSTEAM ADCA

VALSTEAM ADCA M3HP Installation and maintenance instructions

resideo RV283P installation instructions

resideo

resideo RV283P installation instructions

Ditel Kosmos series instruction manual

Ditel

Ditel Kosmos series instruction manual

V2 Easy4 user manual

V2

V2 Easy4 user manual

KERAFLO AYLESBURY KB installation guide

KERAFLO

KERAFLO AYLESBURY KB installation guide

Novus DIGIRAIL-2A instruction manual

Novus

Novus DIGIRAIL-2A instruction manual

Lucent Technologies Stinger IP2000 Configuration guide

Lucent Technologies

Lucent Technologies Stinger IP2000 Configuration guide

Wieland gesis KNX FLEX-BAS installation instructions

Wieland

Wieland gesis KNX FLEX-BAS installation instructions

Autonics AiC-D Series user manual

Autonics

Autonics AiC-D Series user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.