MAU-00046AD - Page 6
6. Performance & Product Specifications
Nova AVR 500 Nova AVR 625 Nova AVR 1250
UPS power rating --- VA 500VA 625VA 1250VA
UPS power rating --- W 250W 360W 660W
Input mains voltage range 165-253V±5% 165-280V±5% 160-290V±5%
Output voltage in mains mode 184-253V±3% 184-253V±3% 184-253V±3%
Output voltage in bat mode 230V + 15/-20%
(184-264V)
230V + 15/-20%
(184-264V)
230V + 15/-20%
(184-264V)
Output frequency in bat mode 50/60Hz±1Hz 50/60Hz±1Hz 50/60Hz±1Hz
Deep discharge protection 4 hours 4 hours 4 hours
UPS backup time 10 minutes for 1 sets PC 15 minutes for 1 sets PC 15 minutes for 2 sets PC
UPS output waveform Quasi-sine Quasi-sine Quasi-sine
Input/Output cord IEC 10A IEC 10A IEC 10A
Input protection Fuse 5A/250V Fuse 5A/250V Circuit breaker 10A/250V
Recharge time 8 hours to recover 80%
after complete discharge
8 hours to recover 80%
after complete discharge
8 hours to recover 80%
after complete discharge
Battery Sealed lead acid battery
12V/4.5Ah x 1
Sealed lead acid battery
12V/7.2Ah x 1
Sealed lead acid battery
12V/7.2Ah x 2
Operating temperature 0-40°C 0-40°C 0-40°C
Relative humidity 10-90% 10-90% 10-90%
Product size 113 x 241 x 145mm 350.5 x 125 x 143 mm 376.5 x 170 x 188 mm
Product weight 4.6 Kg 5.9 Kg 11.2 Kg
7. Trouble Shooting
Nova AVR 500
Condition Item need to check
LED (green) is off, UPS has no output Check if the UPS is correctly plugged to the AC power
available and press On/Off switch about 1 second.
UPS has little or no backup time Charge UPS during 8 hours and try again.
Green ON and beep keep alarm
1. Potential internal failure. Restart UPS. If green LED
still light and beep keep alarm, call for assistance.
2. Check if load short. Take off load and then
restart UPS. If UPS still work abnormally. Call for
assistance
Green Blinking and keep alarm UPS lightly or heavily overload, reduce load. Reset
circuit breaker or change fuse on UPS if necessary
Nova AVR 625/1250
Condition Item need to check
LED (green) is off, UPS has no output Check if the UPS is correctly plugged to the AC power
available and UPS is turned “ON”
UPS has little or no backup time Charge UPS during 8 hours and try again. Consider to
replace battery if backup time is short.
Red ON and beep keep alarm Potential internal failure. Restart UPS. If red LED still
light, call for assistance.
Red Blinking and 1 beep every 0.5
second
UPS lightly or heavily overload, reduce load. Reset
circuit breaker or change fuse on UPS if necessary
Red ON Faulty battery. Recharge battery. Replace battery if
fault reappears.
Any information or advice, please visit our web sit at www.eaton.com or contact EATON after-sales service.