Ekinex EK-BF1-TP-D1 Instructions for use

Application manual
KNX/DALI gateways
EK-BF1-TP-D1/D2
and DCA App

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 2
Contents
1Revision history.......................................................................................................................... 4
2Using the application program.................................................................................................... 5
3General Product information ...................................................................................................... 5
3.1 DALI Bus system properties.................................................................................................. 5
3.2 EK-BF1-TP-D1/D2 product overview..................................................................................... 6
3.3 EK-BF1-TP-D1/D2 product features...................................................................................... 6
3.4 Improvements to the previous firmware 0.2.x ....................................................................... 8
3.4.1 Single ECG control ........................................................................................................ 8
3.4.2 ECG operating modes (normal, permanent, night and panic mode)............................. 8
3.4.3 Counting the operating hours of the individual ECGs.................................................... 8
3.4.4 Export and import of scenes.......................................................................................... 8
3.4.5 Editing and exporting/importing description texts.......................................................... 8
3.4.6 Manual override in schedules........................................................................................ 9
4Installation and Concept of Commissioning............................................................................. 10
4.1 Overview.............................................................................................................................. 10
4.2 ETS-App (DCA)................................................................................................................... 11
4.3 Parameter Configuration ..................................................................................................... 13
5Devices for colour control (DT-8) ............................................................................................. 14
5.1 DALI device type 8 features ................................................................................................ 14
5.2 Colour display via XY coordinates....................................................................................... 14
5.3 Colour display via colour temperature................................................................................. 15
5.4 Colour display via 3 or 4 colour channels (RGBWAF) ........................................................ 15
6Manual mode............................................................................................................................ 16
6.1 1 Channel Device (EK-BF1-TP-D1)..................................................................................... 16
6.2 2 Channels Device (EK-BF1-TP-D2)................................................................................... 18
7Operating modes...................................................................................................................... 21
7.1 Normal mode....................................................................................................................... 21
7.2 Permanent mode................................................................................................................. 21
7.3 Staircase mode.................................................................................................................... 21
7.4 Night mode .......................................................................................................................... 21
7.5 Panic mode (exceptional case) ........................................................................................... 22
7.6 Operating mode hierarchy................................................................................................... 22
8Analysis and service functions ................................................................................................. 23
8.1 Recording operating hours .................................................................................................. 23
8.2 Individual fault recognition at ECG level.............................................................................. 23
8.3 Fault analysis at group level................................................................................................ 23
8.4 Fault analysis at device level............................................................................................... 24
9ETS communication objects..................................................................................................... 25
9.1 General objects.................................................................................................................... 25
9.2 Objects for the time control module..................................................................................... 30
9.3 Objects for Energy Saving................................................................................................... 30
9.4 Group objects ...................................................................................................................... 31

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 3
9.4.1 Objects for colour control............................................................................................. 35
9.4.1.1 Colour temperature 35
9.4.1.2 RGB (DPT 232.600) 36
9.4.1.3 RGB (separate objects) 37
9.4.1.4 HSV 38
9.4.1.5 RGBW (DPT 251.600) 39
9.4.1.6 RGBW (separate objects) 40
9.4.1.7 HSVW (separate objects) 41
9.4.1.8 XY (DPT 242.600) 42
9.4.1.9 XY (separate objects) 43
9.5 ECG objects......................................................................................................................... 44
9.5.1 ECG objects behaviour................................................................................................ 44
9.5.2 ECG objects analysis and service ............................................................................... 45
9.6 Objects for scene control..................................................................................................... 45
10 ETS parameters ....................................................................................................................... 47
10.1 General................................................................................................................................ 47
10.1.1 Parameter page: Analysis and service ........................................................................ 47
10.1.2 Parameter page: Special functions.............................................................................. 50
10.2 Group................................................................................................................................... 52
10.2.1 General ........................................................................................................................ 52
10.2.2 Behaviour..................................................................................................................... 56
10.2.3 Analysis and service.................................................................................................... 60
10.2.4 Colour control............................................................................................................... 61
10.3 ECG..................................................................................................................................... 66
10.3.1 ECG 1 (2.. 64).............................................................................................................. 66
10.3.1.1 Behaviour 71
11 DALI Channel Selection ........................................................................................................... 75
12 DALI commissioning................................................................................................................. 75
12.1 ECG info and errors............................................................................................................. 80
12.2 ECG and group detail info ................................................................................................... 82
12.2.1 ECG info in the right-hand side tree ............................................................................ 83
12.2.2 ECG info in the ECG table........................................................................................... 83
12.2.3 Group info in the group tree......................................................................................... 83
12.3 Operating DALI devices....................................................................................................... 84
12.4 Post Installation ................................................................................................................... 86
12.5 ECG Easy Replacement...................................................................................................... 87
12.6 Data Restore of DALI configuration..................................................................................... 87
13 Scenes...................................................................................................................................... 88
13.1 Configuration ....................................................................................................................... 88
13.2 Colour entries ...................................................................................................................... 90
13.3 Programming scenes........................................................................................................... 91
13.4 Testing a scene event ......................................................................................................... 91

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 4
13.5 Testing the whole scene...................................................................................................... 91
13.6 Export/Import/Delete............................................................................................................ 92
14 Time Control............................................................................................................................. 93
14.1 Configuration ....................................................................................................................... 93
14.2 Action types......................................................................................................................... 95
14.3 Disabling/Enabling............................................................................................................... 98
14.4 Manual Override.................................................................................................................. 99
14.5 Timer.................................................................................................................................... 99
14.6 Export/Import..................................................................................................................... 100
15 Extras...................................................................................................................................... 101
15.1 Menu: Edit Descriptions..................................................................................................... 101
16 DCA OSS ............................................................................................................................... 103
17 Markings................................................................................................................................. 104
18 Maintenance........................................................................................................................... 104
19 Disposal.................................................................................................................................. 104
20 General warnings ................................................................................................................... 104
21 Other information.................................................................................................................... 105
1 Revision history
Revision
Changes
Date
Written by
Verified by
1.0
First issue
06/05/2023
G. Schiochet
C. Baldini
1.1
Added instructions in case the ETS App installation fails
(par. 4.2).
06/10/2023
G. Schiochet
C. Baldini

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 5
2 Using the application program
The application description is valid for firmware version 0.3.0 and higher.
Product family: Lighting
Product type: Gateway
Manufacturer: Ekinex S.p.A.
1 Channel Device:
Name: EK-BF1-TP-D1_V1.0.0
Order no.: EK-BF1-TP-D1 DALI2 1CH
Number of objects: 1279
Number of group addresses: 1279
Number of associations: 1279
2 Channels Device:
Name: EK-BF1-TP-D2_V1.0.0
Order no.: EK-BF1-TP-D2 DALI2 2CH
Number of objects: 2316
Number of group addresses: 2316
Number of associations: 2316
3 General Product information
3.1 DALI Bus system properties
The cross-functional DALI-Bus (DALI = Digital Addressable Lighting Interface) is a system used to
control electronic ballasts (ECGs) in lighting technology. The specifications of the DALI
communications interface are set in the international norm EN62386.
The DALI Bus enables the receipt of switch and dim commands. In addition, the DALI can be used
for status information about light values or the notification of a fault such as a light or ECG failure.
Via the connected control device / gateway (Master), up to 64 individual DALI ECGs (Slaves) can
be connected in a DALI segment. When the DALI is commissioned, the ECGs receive an
automatically generated 3 Byte long address. Based on the long address a short address between
0 and 63 is assigned during the further commissioning process. As the address assignment is
automatic, the device order is random. The individual ECGs/lights therefore need to be identified
during the further commissioning process (see below).

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 6
The addressing of individual ECGs in the system is either based upon the short address (individual
addressing) or upon a DALI group address (group addressing). For this purpose, any number of
ECGs within a segment can be assigned to up to 16 groups. The group addressing in the DALI
system guarantees that switch and dim processes of different lights within a system are performed
simultaneously without time delays.
In addition to short and group addresses, the light values of individual DALI ECGs can also be
merged into scenes and addressed via scene addresses.
For a detailed description of the DALI system, please see the DALI handbook at
https://www.digitalilluminationinterface.org
3.2 EK-BF1-TP-D1/D2 product overview
The EK-BF1-TP-D1/D2 is delivered in 2 product variants:
Feature
Description
Order No.
1 Channel
EK-BF1-TP-D1
EK-BF1-TP-D1 DALI2 1CH
2 Channels
EK-BF1-TP-D2
EK-BF1-TP-D2 DALI2 2CH
The application of the second DALI channel is an identical copy of the first channel.
All functions, objects and parameters are available twice.
Both DALI segments are commissioned separately.
Therefore, both DALI segments are configured independently of each other.
The following documentation describes the configuration and commissioning of one DALI channel
as an example.
3.3 EK-BF1-TP-D1/D2 product features
The Ekinex KNX/DALI gateway EK-BF1-TP-D1/D2 is a device used to control ECGs with a DALI
interface via the KNX installation bus. The device transforms switch and dim commands from the
connected KNX system into DALI telegrams and status information from the DALI bus into KNX
telegrams.
The EK-BF1-TP-D1/D2 is a Single Master Application Controller (in accordance with EN 62386-
103). This means the device must only be used in DALI segments with connected ECGs and not
with other DALI control devices within the segment (no multi-master function). Power supply for the
up to 64, resp. 128 connected ECGs comes directly from the EK-BF1-TP-D1/D2. An additional
DALI power supply is not required and not permitted. . Supported are ECGs according to EN

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 7
62386-102 ed1 (DALI1) as well as devices according to EN 62386-102 ed2 (DALI2). The device is
DALI-2 certified and listed in the corresponding database of DiiA.
The device comes in a 4 units wide DIN Rail casing so it can be directly integrated into the mains
distribution box.
In addition to the pure gateway function, the EK-BF1-TP-D1/D2 offers numerous additional
features:
Addressing of 16, resp. 32 DALI groups or 64, resp. 128 Single ECGs
Flexible DALI commissioning concept in the ETS5
Coloured light control with the help of device type 8 ECGs (DT-8)
Coloured light control depending on ECG sub-type:
oColour temperature (DT-8 Sub-Type Tc)
oXY colour (DT-8 Sub-Type XY)
oRGB (DT-8 Sub-Type RGBWAF)
oHSV (DT-8 Sub-Type RGBWAF)
oRGBW (DT-8 Sub-Type RGBWAF)
The DT-8 sub-type PrimaryN is not supported.
Support of time scheduling programmes to control groups and ECGs according to values
and/or colour
Different operating modes such as permanent mode, night-time mode or staircase mode
Integrated operating hours counter for each group and ECG with an alarm for when the
maximum life-span has been reached
Individual fault recognition with objects for each light/ECG

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 8
Complex fault analysis at group/device level with number of faults and fault rate calculation
Fault threshold monitoring with individually configurable threshold values
Scene module for extensive scene programming and possibility of dimming scenes,
“Quick exchange function“ for easy replacement of individual faulty ECGs,
Manual control of group and broadcast telegrams via control buttons on the device,
Indication of a fault status via LEDs on the device.
The special interface for the configuration of DALI segments is designed as a DCA (Device Control
App) for the ETS5.
Please remember to install the corresponding ETS App in addition to the product database
KNXprod. The ETS App is available for download on the Ekinex website or from KNX website.
3.4 Improvements to the previous firmware 0.2.x
Firmware 0.3.0 also introduces a new ETS application and a new DCA.
3.4.1 Single ECG control
Special attention is now given to the possibility of single ECG control.
Single ECGs can be addressed in scenes, in schedules or via KNX communication objects.
3.4.2 ECG operating modes (normal, permanent, night and panic mode)
The individual ECGs can be used in different operating modes, just like the groups.
3.4.3 Counting the operating hours of the individual ECGs
This function counts the switch-on times of groups and/or ECGs. The counter reading can be used
as threshold value for an alarm notification, for example when the service life has been reached.
3.4.4 Export and import of scenes
In order to be able to use configured scenes easily in other projects, the possibility of importing and
exporting has been implemented.
3.4.5 Editing and exporting/importing description texts
All description texts of the groups or the single ECGs can be edited now additionally centrally.
There, the texts can also be easily imported or exported from other file formats.

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 9
3.4.6 Manual override in schedules
An automatic schedule can be manually overridden for certain requirements. More information can
be found in chapter 14.4 Manual Override.

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 10
4 Installation and Concept of Commissioning
The Commissioning is separated in following steps:
4.1 Overview
After the wiring of the DALI segment according to the operating and installation instructions
document, software start-up can begin.
To do this, the product database is loaded and the corresponding ETS App installed in the ETS5,
see Chapter: 4.2 ETS-App (DCA).

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 11
4.2 ETS-App (DCA)
The application for the EK-BF1-TP-D1/D2 is based on the standard interface for the configuration
of communication objects and parameters as well as a special interface for configuring the DALI
bus system. This special interface is designed as a DCA (Device Control App) for the ETS5. All
required program data are automatically created when the App is imported.
The ETS App can be downloaded from KNX website, following the instructions at
https://support.knx.org/hc/en-us/articles/115001353070-Installing-ETS5-Apps
Therefore click on Button “App“ in the footer of ETS5 and then the “plus“ sign in order to add an
ETS App to your ETS5 system:
A file box will become visible to select the ETS App for the EK-BF1-TP-D1/D2:
The App is displayed in the list of all ETS5 Apps:
When the product is selected an additional DCA tab is shown:
Then the ETS must be started again.
Note: if during the installation the following error is displayed

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 13
4.3 Parameter Configuration
The parameters and the corresponding group addresses can then be configured as with any other
KNX product. With the help of the parameters, various operating modes can also be configured,
which are described in more detail in the chapter: 6 Manual mode.
The DALI specific configuration is performed in the DCA tab. First, the assigment of the ECGs to
the desired groups should be carried out.
This work can be carried out offline without connection to the KNX, or without connection to the
EK-BF1-TP-D1/D2. The actual DALI commissioning is only possible online, that means a
connection to the device is necessary. In this step, all connected ECGs are searched and found
and can then be assigned to the preconfigured configuration.
After this assignment has been carried out, this special DALI configuration must be loaded into the
device. The "Download" key is available in the DCA tab, see Chapter: 12 DALI commissioning.
In the last step, the parameters and the links to the group addresses should be loaded into the
device using normal ETS download. The device is now ready for operation.

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 14
5 Devices for colour control (DT-8)
The EK-BF1-TP-D1/D2 also supports ECGs for colour control (device type 8 according to EN
62386-209). Such devices allow for multi-channel colour control (RGB) and thereby enable the
mixing of a light colour or the setting of a colour temperature via DALI.
5.1 DALI device type 8 features
ECGs for colour control (DT-8) are offered by a range of manufacturers. Usually these devices
allow for the direct control of LED modules with multi-colour LEDs. The most common ones are
modules with LEDs in the three colours red, green, blue (RGB), as well as modules with two
different white tones (Tunable White). Occasionally LED modules with a further integrated white
channel (RGBW) are offered on the market. Whilst it is, of course, possible to control the different
colour channels individually, each via a separate DALI control device for LEDs (Device Type-6),
this solution has the disadvantage, that each of these devices is assigned a separate DALI short
address. This means that two (tunable white), three (RGB) or even four short addresses are
required to control a module. With a maximum number of 64 available short addresses per DALI
segment, the number of lights that can be used is greatly reduced. With a DT-8 device, however,
only one short address is required for all colour channels and the maximum possible range of 64
lights can be controlled. The DALI standard EN 62386-209 defines different colour control methods
for DT-8 devices. Normally, a certain device supports only one of these possible methods.
Therefore please pay attention to the specifications of the respective manufacturer.
5.2 Colour display via XY coordinates
The display of a colour via two nominated coordinates in a so-called colour space is a common
method. By means of the XY coordinates any point in this space is accessible and as a result any
colour can be defined. The diagram used in the DALI standard is the colour space chromaticity
diagram according to the 1931 CIE standard. (Cambridge University Press) which is shown in the
following graphic.
Figure 1: Colour space chromaticity diagram according to CIE 1931 (Source: Wikipedia)

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 15
In devices that support the XY coordinates method, the colour is set via two values between 0.0
and 1.0. However, because of the physical properties of an LED, even in an RGB LED module not
every colour is practically possible. In practice, it iscommon toset the valuewhich is closest. Please
pay attention to the instructions of the ECG or light manufacturer. Usually the XY values, which are
supported by the lamp, are specified here. Values outside of the specified range can generate non-
reproducible colours.
5.3 Colour display via colour temperature
A subset of all possible colours in the colour space are the different white tones. The white tones
are found on one line across the whole colour space.
Figure 2: White tone on Black-Body-Line (Source: Wikipedia)
The points on this so-called black-body-line (BBL) are usually defined via a colour temperature in
Kelvin. This makes it possible to exactly determine the white tone of a light between warm and cool
with just one value. The colour temperature principle is therefore perfect for the control of white
light fixtures (tunable white). DT-8 operating devices set the required colour temperature on an LED
module by mixing cool and warm white LEDs. Of course, as before this is only possible within
certain physical limits. With today’s LED modules colour temperatures between 2000 and 8000
Kelvin are common.
5.4 Colour display via 3 or 4 colour channels (RGBWAF)
Principally, a colour is created by mixing different individual colours (different white tones, RGB or
RGBW). A colour can therefore also be displayed based on the mixing ratio of different single
colours, e.g. 50% red, 0% green, 60% blue. The colour definition in this case is not exact but
depends greatly on the specific, physical attributes of the LEDs used to create the colour (wave
length, intensity). Nonetheless, the indication of the primary colour percentages within a system is
useful for the relative description of a colour. In some DT-8 ballasts, the colour is set by stating 3
(RGB) or 4 values (RGBW) between 0 and 100%. Accoring to DALI standard EN 62386-209, up to
six colours (RGBWAF) can theoretically be drawn upon.

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 16
6 Manual mode
6.1 1 Channel Device (EK-BF1-TP-D1)
The EK-BF1-TP-D1 has 9 operating buttons and LEDs on the front side, which offer numerous
possibilities for manual control and broadcast and analysis functions.
The buttons and LEDs are accessible without having to remove the cover. During KNX bus
operation and in the absence of any errors, all 9 LEDs are switched off. If the gateway detects an
error (e.g. a faulty lamp or KNXfailure), only the LED on the Man. button lights up inred and flashes
quickly. During programming (e.g. during installation) all LEDs light up in red and flash slowly.
Activate the manual mode with a long keypress on the button in the bottom right-hand corner.
The manual mode ends automatically 60 seconds after the last time the button has been activated.
If manual mode is active, shortly press the same button again to toggle between the different
manual mode levels. The RGB LED on the Man. button shows which level you are currently on.
The individual levels have the following meaning:

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 17
Manual mode level 1
LED on Man. button lights up permanently in green
Use buttons 1/9 to 8/16 to switch DALI groups 1 to 8. The light value of the group changes from
100% (On) to 0% (Off) each time the button is pressed. The switch status of each group is shown
via the LEDs on the buttons 1/9 to 8/16.
Manual mode level 2
LED on Man. button flashes green
Use buttons 1/9 to 8/16 to switch DALI groups 9 to 16. The light value of the group changes from
100% (On) to 0% (Off) each time the button is pressed. The switch status of each group is shown
via the LEDs on the buttons 1/9 to 8/16.
Manual mode level 3
LED on Man. button lights up permanently in red
Briefly press button 1/9 to trigger a broadcast command. Whether the command that is sent first is
an on or off command depends on the status of group 1. Each further keypress toggles all lights
via broadcast. The LED on button 1/9 shows the switch status. All lights react to a broadcast
command even if group assignment has not yet taken place.
A long keypress on button 5/13 triggers a quick exchange command. This function makes it
possible to replace a faulty ECG even without the ETS (see chapter ECG quick exchange).
A long keypress on button 6/14 activates the converter inhibit mode. If the power supply for the
connected emergency lights is turned off within 15 minutes after activating the converter inhibit
mode, the lights are turned off instead of changing into emergency mode. This operating mode
may be necessary during the commissioning and installation process to prevent constant
emergency lighting and battery discharge.
If the gateway detects a fault, the LEDs on buttons 2/10 to 4/12 and 7/15 to 8/16 show the exact
type of fault. The LED is constantly lit up in red. The faults are as follows:
LED Button 2/10 Converter fault
LED Button 3/11 ECG fault
LED Button 4/12 Lamp fault
LED Button 7/15 DALI short-circuit
LED Button 8/16 KNX fault

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 18
6.2 2 Channels Device (EK-BF1-TP-D2)
The EK-BF1-TP-D2 has 9 operating buttons and LEDs on the front side, which offer numerous
possibilities for manual control and broadcast and analysis functions.
The buttons and LEDs are accessible without having to remove the cover. During KNX bus
operation and in the absence of any errors, all 9 LEDs are switched off. If the gateway detects an
error (e.g. a faulty lamp or KNXfailure), only the LED on the Man. button lights up inred and flashes
quickly. During programming (e.g. during installation) all LEDs light up in red and flash slowly.
Activate the manual mode with a long keypress on the button in the bottom right-hand corner.
The manual mode ends automatically 60 seconds after the last time the button has been activated.
If manual mode is active, shortly press the same button again to toggle between the different
manual mode levels. The RGB LED on the Man. button shows which level you are currently on.
The individual levels have the following meaning:

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 19
Manual mode level 1 (channel 1)
LED on Man. button lights up permanently in green
Use buttons 1/9 to 8/16 to switch DALI groups 1 to 8. The light value of the group changes from
100% (On) to 0% (Off) each time the button is pressed. The switch status of each group is shown
via the LEDs on the buttons 1/9 to 8/16.
Manual mode level 2 (channel 1)
LED on Man. button flashes green
Use buttons 1/9 to 8/16 to switch DALI groups 9 to 16. The light value of the group changes from
100% (On) to 0% (Off) each time the button is pressed. The switch status of each group is shown
via the LEDs on the buttons 1/9 to 8/16.
Manual mode level 3 (channel 1)
LED on Man. button flashes red/green
Briefly press button 1/9 to trigger a broadcast command. Whether the command that is sent first is
an on or off command depends on the status of group 1. Each further keypress toggles all lights
via broadcast. The LED on button 1/9 shows the switch status. All lights react to a broadcast
command even if group assignment has not yet taken place.
A long keypress on button 5/13 triggers a quick exchange command. This function makes it
possible to replace a faulty ECG even without the ETS (see chapter ECG quick exchange).
A long keypress on button 6/14 activates the converter inhibit mode. If the power supply for the
connected emergency lights is turned off within 15 minutes after activating the converter inhibit
mode, the lights are turned off instead of changing into emergency mode. This operating mode
may be necessary during the commissioning and installation process to prevent constant
emergency lighting and battery discharge.
If the gateway detects a fault, the LEDs on buttons 2/10 to 4/12 and 7/15 to 8/16 show the exact
type of fault. The LED is constantly lit up in red. The faults are as follows:
LED Button 2/10 Converter fault
LED Button 3/11 ECG fault
LED Button 4/12 Lamp fault
LED Button 7/15 DALI short-circuit
LED Button 8/16 KNX fault
Manual mode level 4 (channel 2)
LED on Man. button lights up permanently in blue
Use buttons 1/9 to 8/16 to switch DALI groups 1 to 8. The light value of the group changes from
100% (On) to 0% (Off) each time the button is pressed. The switch status of each group is shown
via the LEDs on the buttons 1/9 to 8/16.

Application Manual
KNX/DALI gateways EK-BF1-TP-D1/D2 and DCA App
Rev. 1.1 –06/10/2023 MAEKBF1TPD1D2_EN
© Ekinex S.p.A. –All rights reserved Pag. 20
Manual mode level 5 (channel 2)
LED on Man. button flashes blue
Use buttons 1/9 to 8/16 to switch DALI groups 9 to 16. The light value of the group changes from
100% (On) to 0% (Off) each time the button is pressed. The switch status of each group is shown
via the LEDs on the buttons 1/9 to 8/16.
Manual mode level 6 (channel 2)
LED on Man. button flashes red/blue
Briefly press button 1/9 to trigger a broadcast command. Whether the command that is sent first is
an on or off command depends on the status of group 1. Each further keypress toggles all lights
via broadcast. The LED on button 1/9 shows the switch status. All lights react to a broadcast
command even if group assignment has not yet taken place.
A long keypress on button 5/13 triggers a quick exchange command. This function makes it
possible to replace a faulty ECG even without the ETS (see chapter ECG quick exchange).
A long keypress on button 6/14 activates the converter inhibit mode. If the power supply for the
connected emergency lights is turned off within 15 minutes after activating the converter inhibit
mode, the lights are turned off instead of changing into emergency mode. This operating mode
may be necessary during the commissioning and installation process to prevent constant
emergency lighting and battery discharge.
If the gateway detects a fault, the LEDs on buttons 2/10 to 4/12 and 7/15 to 8/16 show the exact
type of fault. The LED is constantly lit up in red. The faults are as follows:
LED Button 2/10 Converter fault
LED Button 3/11 ECG fault
LED Button 4/12 Lamp fault
LED Button 7/15 DALI short-circuit
LED Button 8/16 KNX fault
This manual suits for next models
1