Page 1 97460C (Rev. SIC - 1/11)
4595_FTN LK4595_FTN
Owners Manual
Model 4595
Pedestal Barrier Free Stone Fountain
Toassureyouinstallyour4595StoneFountainmodeleasilyandcorrectly,
PLEASEREADTHESESIMPLEINSTRUCTIONSBEFORESTARTINGTHE
INSTALLATION.CHECKYOURINSTALLATIONFORCOMPLIANCEWITH
PLUMBING,ELECTRICAL,ANDOTHERAPPLICABLECODES.Afterinstallation,
leavetheseinstructionswiththeFountainforfuturereference.
IMPORTANT
ALLSERVICETOBEPERFORMEDBYANAUTHORIZEDSERVICEPERSON
IMPORTANT! INSTALLER PLEASE NOTE.
THEGROUNDINGOFELECTRICALEQUIPMENTSUCHASTELEPHONE,COMPUTERS, ETC.TOWATERLINES
ISACOMMONPROCEDURE.THISGROUNDING MAYBEINTHEBUILDING OR MAYOCCURAWAYFROMTHE
BUILDING.THISGROUNDINGCANCAUSEELECTRICALFEEDBACKINTOAFOUNTAIN,CREATINGAN
ELECTROLYSISWHICH CAUSESAMETALLICTASTEORAN INCREASEINTHE METALCONTENTOFTHE
WATER.THISCONDITIONISAVOIDABLE BYUSINGTHE PROPER MATERIALSAS INDICATED.ANYDRAIN
FITTINGSPROVIDEDBYTHEINSTALLER SHOULD BE MADE OF PLASTICTOELECTRICALLYISOLATETHE
FOUNTAIN FROMTHE BUILDINGPLUMBINGSYSTEM.
INSTALLER
General Installation Tips
1. Water supply 3/8" O.D. unplated copper tube. Waste 1-1/4" IPS. Contractor to supply waste trap and service stop valve
in accordance with local code.
2.Connectinglines to bemade of unplated copperand should be thoroughlyflushed to remove allforeign matter before
being connected to fountain. This fountain is manufactured in such a manner that it does not in any way cause taste,
odor, color, or sediment problems.
3.Connect fountain to supplyline with ashut-offvalve and installa 3/8" unplated copperwater line betweenthe valve and
the cooler. Remove any burrs from outside of water line. Push the tubes straight into the fittings until they reach a
positivestop, approximately3/4" (SeeFig. 6).DO NOT SOLDER TUBES INSERTED INTO THE STRAINER AS
DAMAGE TO THE O-RINGS MAY RESULT.
4. These products are designed to operate on 20 psig to 105 psig supply line pressure. If inlet pressure is above 105 psig,
a pressure regulator must be installed in the supply line.Any damage caused by reason of connecting this product to
supply line pressures lower than 20 psig or higher than 105 psig is not covered by warranty.