Elmdene ACCESS-UL-PSU1 User manual

1
ACCESS-UL-PSU1/PSU2 PAK200844_01D April 2021 2021 Elmdene International Ltd
ACCESS-UL-PSU1
(UL294 Access Control G Enclosure with UL294-12V 4A FOM4 Mo ule)
ACCESS-UL-PSU2
(UL294 Access Control D Enclosure with UL294-12V 4A FOM4 Mo ule)
UL294-G Enclosure P/N: CAS996997-1
UL294-D Enclosure P/N: CAS958959-1
UL294-12V 4A FOM4 MODULE P/N: SAS138936
F
EATURES
Hi h efficiency cost effective UL294-listed power supply/char er desi ned for use in Access Control systems enclosed in
two spacious cabinet choices each fitted with locks and tamper switch. Re ulated 13.8Vdc output with battery stand-by
supplyin rated current to 4 independently PTC Fused Outputs (resettable fuses) individually confi ured for continuous or
switched output current via a fire relay switch with flexible tri er options, capable of operatin with any external control
si nal. PSU Universal mains input. Two dry (volt free) contacts are provided to si nal loss of mains and battery / output
faults.
•Continuous full rated current to load at 12V 4A
•Universal mains input volta e 100-240Vac
•Full electronic short circuit and overload protection
•Individual battery and output fuse protection
•Hi h efficiency electronics for reduced runnin costs
and operatin temperatures
•Installer safe desi n with all hi h volta e electronics
fully shrouded
•Mains transient protection circuit
•Dry contact indicatin AC mains failure (EPS).
Required to be monitored by UL listed control unit
in UL294 application.
•Dry contact for output and battery faults (GEN)
•Green Mains present LED
•Red Fault dia nostic LED
•Versatile fire relay functionality
•4-way Class 2 fused outputs with health LED’s
•Enclosure fitted with a tamper switch and lock(s)
•UL294 UL Listed for Access Control Systems
Destructive Attack – I; Endurance – IV;
Line Security – I; Stand-by Power - II
S
PECIFICATION
Input Specification
Rated Volta e 100-240Vac
Frequency 50-60Hz
Max Current 2.0Amax @ Full load
Mains Input Fuse T3.15A (20mm IEC 250Vac HBC)
Output Specification
Volta e 12.8 – 14.2V dc (13.8V dc nominal) on mains power
9.8 – 13.0V dc on battery standby
Total load current 4A maximum (4 outputs at 1.0A each)
Ripple < 150 mV pk-pk max
Module Output Fuse
FOM Fuses
F4.0A (20mm IEC Glass)
4 off 1.35A PTC Fused Outputs Class 2 (resettable)
Overload Electronic shutdown until overload or short circuit removed
(under AC mains power only)
Elmdene International Ltd
Tel: +44 (0)23 9269 6638
3 Keel Close, Interchange Park, Fax: +44 (0)23 9266 0483
Portsmouth, Hampshire, PO3 5QD, UK
Web: www.elmdene.co.uk

2
ACCESS-UL-PSU1/PSU2 PAK200844_01D April 2021 2021 Elmdene International Ltd
Stan by Battery
Battery Type 12V Valve Re ulated Lead Acid
Battery Capacity Desi ned for 8.5Ah (G-box) or 18Ah* (D-box) VRLA
Battery Char in Fuse protection F4.0A (20mm IEC Glass)
Mechanical
Pro uct Reference External Dimensions h x w x d (mm)
Battery Capacity
Weight (kg)
Battery Exclu e
ACCESS
-
UL
-
PSU1
“G” Enclosure (440 x 250 x 115) 8.5Ah 4.5
ACCESS
-
U
L
-
PSU
2
“D” Enclosure (505 x 407 x 80) 8.5Ah or 18Ah* 7.5
* Hold-up not tested by UL294
Environmental
Temperature -10 to +49°C (operatin ) 75% RH non-condensin
-20 to +80°C (stora e)
S
IGNALLING
O
UTPUTS
Type: Solid state relay contacts, volt free (dry)
EPS Fault: Open if Loss of mains for >8s
GEN Fault: Open if Battery terminal volta e < 11.5V dc (when operatin in standby with no
mains present), battery not present or Output and/or battery fuse blown
Fault Diagnostic Table:
Re LED
(Fault)
Green LED
(Mains) PSU Status
OFF ON Normal: Battery fully char ed
One short flash
every second ON Normal: Battery char in but not fully char ed
Flashin :
1second On
1 second Off
ON Fault: Output fuse or battery fuse blown, or battery missin
OFF Fault: No mains, output fuse blown
One short flash
every 3 seconds OFF Fault: No mains, battery supplyin load.
OFF OFF Fault: No mains, No output, Batteries disconnected or completely
dischar ed
L
OCAL
I
NDICATORS
MAINS LED (Green) Mains present
FAULT LED (Red) Fault present: Output or Battery fuse failed. Battery shorted, reversed, or low volta e.
OUTPUT LEDS - 4off (Red) Indicates output volta es (1 to 4) present when ON
RELAY LED (Oran e) Indicates Control Relay ener ised when ON
C
ONNECTIONS
MAINS INPUT L N LIVE and NEUTRAL
MAINS FAIL EPS FAULT Dry contact. Open at loss of mains input
GENERAL FAULT GEN FAULT Dry (Volt-free) contact. Open on fault
OUTPUTS 1,2,3,4 0/P action confi ured by Jumpers ON, OFF or RELAY TRIGGER Controlled
Note: Observe polarity
BATTERY BATT + - Connection to standby battery. Use cables provided.
Note: Observe polarity
RELAY TRIGGER TRIG + -
Confi ured by Jumpers as +VE, NC or NO
Note: Polarity must be observed for +VE connection

3
ACCESS-UL-PSU1/PSU2 PAK200844_01D April 2021 2021 Elmdene International Ltd
I
NSTALLATION
I
NSTRUCTIONS
Wirin methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities havin jurisdiction. Use a minimum spacin of 0.25” between power limited and non-power
limited wirin . This unit is only suitable for installation as permanently connected equipment. This PSU is NOT
SUITABLE for external installation. This unit must be fed from a mains power source havin a separate (approved)
disconnect device and fitted with a fuse or other over-current protection device rated at 15A maximum.
Ensure that the disconnect device used has appropriate earth fault protection to the applicable standard.
EQUIPMENT MUST BE EARTHED. Before installation or servicin , ensure that external disconnect device is OFF.
Mounting
1) Mount securely in a suitable enclosure with the correct orientation allowin minimum clearance – see Figure 1
2) Route mains and low volta e output cables via different knockouts and/or cable entry holes.
3) Use bushes and cable lands rated to UL94 HB minimum.
•
Secure all field wiring exiting enclosure with cable ties.
•
Protect field wiring exiting enclosure using knockouts with
bushes or similar.
•
Use conduit for all Class 1 and non-Class O/Ps field wiring
exiting enclosure.
•
Minimum s acing of 0.25” (6.4mm) between ower limited and
non- ower limited wiring.
•
Out ut wiring rated
for maximum load current.
Minimum of 0.4” (10cm) clearance
each side
15A Circuit Break
er
Mains in ut cable rating:
15A 300Vac minimum
Figure 1
Ty ical
Installation
12V 8.5A
12V 18Ahr*
* Hold-u not tested by UL294
“G” Enclosure “D” Enclosure
12V 8.5Ahr

4
ACCESS-UL-PSU1/PSU2 PAK200844_01D April 2021 2021 Elmdene International Ltd
Mains Power Up
4) Attach correctly rated mains cable (minimum 2.5mm
2
[15A], 300/500Vac). Fasten with cable ties.
5) Apply mains power. Check for 13.8Vdc on load outputs and Green Mains LED is ON.
6) Disconnect mains power.
Loa Output
7) Attach correctly rated load cable and fasten usin cable ties. Note polarity.
8) Apply mains power.
Check Green Mains LED is ON.
NOTE: Red Fault LED may flash to indicate no battery has been connected, this is normal.
Verify load is operatin correctly.
9) Disconnect mains power.
Signalling
10) Connect EPS and GEN fault outputs to appropriate inputs of Access Control or Indicatin Equipment.
Wirin to “EPS” and "GEN" should be less than 98.5ft (30m) in len th from controller.
Stan by Battery
11) Attach supplied battery cables to terminal block before connectin the battery.
NOTE: ensure correct polarity of battery connections: +ve use Re lead, -ve use Black lead.
Fire Relay Configuration
12) See “OUTPUT FIRE RELAY OPERATION” - Typical Application below.
Tamper
13) Connect tamper switch to appropriate inputs of control and indicatin equipment.
14) Close the lid and fasten with screw supplied.
15) With the unit mounted on the wall check that the rear tamper is not in a position that will affect its operation,
for example over a mortar course, recess or raised area on the wall.
Check that the tamper switch is:
•CLOSED when the lid/cover is closed, and the retainin screws are fitted.
•OPEN when the retainin screws are removed, and the lid/cover is open.
Use the fine adjustment screw if necessary, to ali n indicator with set point.
16) Close the lid/cover and fasten. Re-check tamper circuit is closed at the control panel.
O
PERATING
I
NSTRUCTIONS
In the event of loss of AC mains, a battery fault or a GEN fault, the correspondin Fault si nal contacts will open (see
Fault dia nostic table for LED indicator status).
If the output of the PSU fails, the cause of the failure should be investi ated e. . short circuit load, connection of a
deeply dischar ed battery. The fault should be rectified before restorin power to the PSU. If any of the fuses require
replacin , ensure the correct fuse ratin and type is used.
O
UTPUT
F
IRE
R
ELAY
O
PERATION
The power module Fire Relay functionality ives the installer the choice of continuous or switch external control of the
PTC fused Class 2 outputs, by the means of either a Volt Free contact (N/O or N/C) or a low volta e si nal
(12Vdc/24Vdc), as shown in the block dia ram below:
13.8V dc
5
A
PSU
Tri er I/P
s
(Contact or Volta e)
4 x
individ
ually controlled O/P’s
13.8V dc
(Switche
d On/Off
-
Tri er controlled)

5
ACCESS-UL-PSU1/PSU2 PAK200844_01D April 2021 2021 Elmdene International Ltd
Typical Application:
Power must be removed from certain parts of the system in the event of a Fire Alarm activation, i.e. door lock power
removed whilst Auxiliary Control Unit (ACU) equipment remains powered.
F
IRE
FOM
C
ONNECTIONS
&
J
UMPERS
TRIG: + Tri er I/P from control device (+VE or Contact)
- Tri er I/P from control device (0V or Contact)
Note: Wirin to “TRIG” should be less than 98.5ft (30m) in len th from controller
Note: Fail safe mo e shall be employe in UL294 applications
In case of fail secure configuration, panic har ware shoul be employe to allow exit from secure location.
Contact local authorities having juris iction.
The device has 3 modes of tri er (TRIG) operation set by the on-board jumpers:
Contact Mode (NO) - Jumper across: 2 & 3
FAIL SAFE
Contact Mode (NC) - Jumpers across: 1 & 2 and 3 & 4
FAIL SECURE
Volta e Mode - Jumper across 3 & 4
FAIL SAFE
Each output (O/P) can then be set usin the jumpers next to the relevant fuse:
Output (O/P) a
lways ON (+V)
Output (O/P) Isolated on TRIGGER (Relay)
Note: Removing the jumper completely, will disable the output (no output).
able 1 below defines the output state for the Normal Closed and “Normal Open Contact Modes with rigger
( RIG) selection.
* Note: Tri er Input terminals (TRIG) + and - are polarity conscious when used in Volta e Mode only.
** In Volta e Mode the “+V Applied” can be used with volta es between 10.0V to 28.4V.
Typical Fire Relay Fail-Safe Setup for a Fire Panel Alarm:
In this example the power to the access control lock is FAIL-SAFE when the Fire Panel alarms, or O/P power is
removed.
•
O/P 3 & 4 confi ured to be “Relay(switched O/P)”.
•
Contact Mode Normal Closed - “Tri er Select” TRIG : confi ured as N0 (2 &3 Linked)
•
O/P 2 confi ured as always ON (+V linked)
•
O/P1 confi ured as always OFF (No link)
able 1 Trigger
Select Jumper(s) Trigger
+ & - Output Orange
LED
Contact Mo e
Normal Close NO 2 & 3 Open No output OFF
Closed 12V dc ON
Contact Mo e
Normal Open NC 1 & 2
3 & 4
Open 12V dc ON
Closed No output OFF
Voltage Mo e +VE* 3 & 4 +V Applied** 12V dc ON
Removed No output OFF

6
ACCESS-UL-PSU1/PSU2 PAK200844_01D April 2021 2021 Elmdene International Ltd
Note: Listed panic hardware may be required for fail secure confi uration. Consult local authority havin jurisdiction.
M
AINTENANCE
This unit is intended for use by Service Personnel only and must be disconnect Power Prior to Service.
There are NO USER SERVICEABLE parts inside. There is no re ular maintenance required of the PSU other than periodic
testin , and replacement of the standby battery. Reference should be made to the battery manufacturer's
documentation to determine typical/expected battery life with a view to periodic replacement of the battery.
C
OMPLIANCE
This power supply unit meets the essential requirements of the followin European Directives:
CPR: 305/2011/EU
Low Volta e 2014/35/EU
EMC 2014/30/EU
WEEE 2012/19/EU
RoHs2 2011/65/EU
D
ISPOSAL OF
P
RODUCT AT
E
ND OF
L
IFE
This product falls within the scope of EU Directives 2012/19/EU Waste Electrical and Electronic Equipment (WEEE) and
2013/56/EU (Battery). At the end of life, the product must be separated from the domestic waste stream and disposed
via an appropriate approved WEEE disposal route in accordance with all national and local re ulations.
Before disposal of the product, any batteries must be removed, and disposed separately via an appropriate approved
battery disposal route in accordance with all national and local re ulations. Packa e used batteries safely for onward
transport to your supplier, collection point or disposal facility.
Caution: Risk of fire or explosion
if bare battery wires are allowed to touch.
1
NC
NO
+VE
TRIG
+
-
1
O/P 3 &
4
Access Control Locks
FAIL SAFE when Fire
Panel Alarms or O/P
Power is removed + 4
–
Battery
Connection
BATT
FUSE
O/P FUSE
+ 3
-
-
+
2
-
+V (Unswitched O/P)
JUMPERS
Relay (switched O/P)
LED A
AC MAINS resent when ON (GREEN)
LED B FAULT WHEN ON (RED)
LED C RELAY ON (ORANGE)
LED D O/P 1-4 ON (RED)
+ 1
-D
B
A
C
3
D
D
D
O/P 2
Always ON
O/P 1
Always OFF
FIRE PANEL
FAULT
ALARM
12V
24V
+
-
+
–
BATT
-
NO
+VE
NC
+ -
12V Battery

7
ACCESS-UL-PSU1/PSU2 PAK200844_01D April 2021 2021 Elmdene International Ltd
See Specification for battery type information. The battery is marked with the crossed out wheelie bin symbol, which
may include letterin to indicate cadmium (Cd), lead (Pb), or mercury (H ). For more information see:
www.recyclethis.info
he packaging supplied with this product may be recycled. Please dispose of packaging accordingly.
This manual suits for next models
7
Table of contents
Popular IP Access Controllers manuals by other brands

ACT Technology
ACT Technology ACT1000 - ACCESS CONTROL UNIT - INSTALLERS installation instructions

RBH Access Technologies
RBH Access Technologies Integra 32 UNC100 manual

nvent
nvent SPECTRACOOL instruction manual

Soyal
Soyal AR-327-E manual

Digiplex
Digiplex Paradox ACM12 Installation instructions and instructions for use

Visionis
Visionis VIS-3002 user manual

Roger
Roger MCT86M-IO-HR-CH operating manual

Altronix
Altronix Trove T2SSK7F8 installation guide

Schlage
Schlage Panel Interface Module RS485 Installation & operating instructions

GeoVision
GeoVision GV-CS1320 quick start guide

Prosonic
Prosonic PRO-698 instruction manual

VisiConsult
VisiConsult VC Security 101775 manual