ELREHA TAR 1700-2 User manual

Brief Description
• Suitable as :
Multistage Controller or
Differential Controller with
limitation contacts
• Operating Modes:
4-Stage Controller,
Double 2-Stage Controller,
3-Stage-Controller + Alarm,
Differential Controller
• Analog Output 0-10VDC for P/PI-
control or Remote Displays
• Alarm Limits / Alarm Relay
• Different Sensor Types
• Setpoint shift by Real Time Clock
• Minimum Idle Time
• RS-485-Interface
ELEKTRONISCHE REGELUNGEN GMBH
Can be used for
• Cooling, Heating and HVAC
Applications
Operating Elements
Parameters (setpoints, times, etc.)
All selectable parameters hold a parameter number (e.g. P04), you will find a
listing on the next page.
Calling up and editing
Press key 'P' ...................parameter number appears
Use '/' .......................select desired parameter (hold key for autoscroll)
Press "P" again...............parameter value appears
Use keys '/'................adjust parameter value (hold key for autoscroll)
Press 'P' again ................value is stored, back to parameter no.
Unlock Keys / Access code
To prevent un-authorized persons from editing parameter values, there is a
lockingfunctionwhichallowsonlythemostimportantparameterstobechanged
at any time. All other parameters must be unlocked as follows:
- enter access code before programming at parameter P41 or
- directly at the parameter to be changed. If a code no. is necessary the
display shows "C00". Set the matching code no. by the "/"-keys (70 or
88, see parameter listing) and confirm by "P".
If no key is hit for about four minutes, the access code is cancelled and the
editing function is locked automatically.
After entering of the code '70' the control functions will be disabled.
They will be restartet if the code will be changed manually (e.g. to 88
for other parameters) or will be resetted automatically after 4 minutes
without any press on a button.
Start-up behavior
Directly after start-up the display shows "700" (controller type), after that a
display test passes.
How to find out the controller type
- Press key "P" for > 2 sec. = Display shows controller type (700)
- Key "" additionally = Software version is displayed
Manual controller "wake-up"
If the controller is switched off via interface (e.g. from a PC), the display shows
"oFF". By holding key "" for > 3 sec. the controller unit engage.
Reset parameters to factory settings
Switch OFF supply voltage, press and hold "P"-key, switch supply voltage
ON again. Code request "C" appears. Enter "88", confirm by "P". One by
one software version, date and "def" appear. With this, all values are reset to
factory settings.
Please note Safety Instructions !
When replacing older types please note
changed functions and connectors!
Please read these instructions carefully before applying power. Your attention is drawn to
the fact that the warranty is subject to the application of power sources that are within the
limits specified in this manual. This documentation was compiled with utmost care, however,
we cannot guarantee for its correctnesss in every respect. Technical details can be changed
without notice, especially the software. Please note that the described functions are only
valid for units containing the software with the version-number shown on page 1. Units with
an other software number can work a little bit different. You will find this software number
on the label of the unit too.
ELREHA GmbH
D-68766 Hockenheim, Germany,
Schwetzinger Str. 103
Technical Data (see parameter listing for more information)
Supply Voltage...........................................................................see above
Output Relays................................................................... 4x potential free
Contact Rating...................................... 8A resistive, 3A cos phi 0,4, 250V AC
TAR 1700-2 (UL)..............................resistive: 120/240V AC, 8A, 30 k cycles
motor: 125/250V AC, ¼ HP, 30 k cycles
Ambient Temperature TAR 1700-2....................................-10..+65°C (14..149°F)
Ambient Temperature TAR 3700-2/5700-2. .................... -10..+55°C (14..131°F)
Storage Temperature...................................................... -30..+70°C (-22..158°F)
Relative Humidity.......................................max. 85% r.H., not condensing
Temperatur Sensor Inputs .......................... 2x TF 201 or TF 501 (Pt1000)
Display................LED, 7-segment, red, character height 13mm (.51 inch)
Resolution / Accuracy............................................0,1°C / 0,2°F / typ. ±1K
Control-/Display Range with Temperature Sensor Types
with TF 201 .................................................. -40...+80°C / -40...176°F
with TF 5xx (depending on type) up to..-100...+300°C / -148...572°F
Data storage parameters ..................................................................$20 years
Relay indicators......................................................................... 3 mm, red
Analog Output..........................................................0-10V DC, max. 3 mA
Analog Output Resolution......................... 8 bit within the set benchmarks
Interface............................................................................E-Link (RS-485)
Electrical connection.............................. screw terminals 2,5mm² (.1 inch)
Housing / Protection / Digital Input
TAR 1700-2.........................77 x 35 mm front frame, IP 54 from front
Digital input for external, potential free contact
TAR 3700-2..................................................... for rail mounting, IP 30
Digital input for mains voltage, 50-60Hz, max. 3mA
TAR 5700-2.........................96 x 48 mm front frame, IP 54 from front
Digital input for mains voltage, 50-60Hz, max. 3mA
Accessories (please order separately)
- Temperature sensor TF 201 (up to 80°C max.) or
- Temperature sensor TF 501 (PT1000, up to 300°C, dep. on type)
For type TAR 1700-2:
- Matching transformer, please contact us.
ELREHATAR
21 3
P
4
Blinking: Min.Idle Time of the stage runs
Stage 1
ON/OFF
Stage 2
ON/OFF
Stage 3
ON/OFF
Stage 4
ON/OFF resp. alarm
Increase
Values
Decrease
Values
Minus
Blinking: 2nd setpoint active
Programming
Key
Blinking:
Data transfer on bus
Automatic display
segment test after
power up !!
Technical Manual 5311032-04/14e
from Software Vers. 2.0.1
Multistage Temperature Controller
Series:
TAR 1700-2
TAR 3700-2
TAR 5700-2
TAR 1700-2
Panel mounting
12-24V AC, 50/60 Hz
18-33V DC, 5,5 VA max.
TAR 5700-2
Panel mounting
230V AC, 50/60 Hz
5,5 VA max.
TAR 3700-2
Rail mounting
230V AC, 50/60 Hz
5,5 VA max.
Blinking = Alarm
ELREHA
TAR
1 2 3
P
4
New Display
Stage 2
ON/OFF
Stage 3
ON/OFF
Stage 1
ON/OFF
Stage 4
ON/OFF

page 2 Technical Manual TAR x700-2
P19=1
P19=2
P19=3
P19=4
Parameter-# Parameter Function Range Factory Settings
P01 .... x. x .x .x....- ....... Actual Value of Sensor 1...................................................Display only! .....................................................-
P02 ............x .x....- ....... Actual Value of Sensor 2...................................................Display only! .....................................................-
P03 ................x....- ....... Differential Value Sensor 1/Sensor 2 ................................Display only! .....................................................-
P04 .... x. x .x .x....- ....... Control Setpoint 1 (absolute value) or ..............................Limited by P16/P17 .........................................0°C
Differential Setpoint (depends on Operating Mode)
P05 .... x. x .x .x....- ....... Control Setpoint 2 (absolute/relative, dep. on P08) .........." / resp. ± 100 ...................................................0°C
P06 .... x. x .x .x....- ....... Control Setpoint 3 (absolute/relative, dep. on P08) .........." / resp. ± 100 ...................................................0°C
P07 .... -.. x . x .- ....- ....... Control Setpoint 4 (absolute/relative, dep. on P08) .........." / resp. ± 100 ...................................................0°C
P08 .... x . x . x .- ....- ....... Mode of Control Setpoints 2-4 ..........................................1= absolute value .............................................1
2= relative to P04 (switching distance)
P09 .... x . x . x .x....88..... Setpoint-Offset (for day/night mode).................................-100...+100°C ...................................................0
Amount all setpoints will be shifted after OK 1 (-148...+212°F)
resp. the internal clock has been activated.
P10 .... x. x .x .x....88..... Switching characteristic of relay K1 ..................................1=RE, 2=FR, 3=HT...........................................1
P11 .... x . x .x .x....88..... Switching characteristic of relay K2 ..................................1=RE, 2=FR (not TAR 1700), 3 = HT ...............1
P12 .... x. x .x .x....88..... Switching characteristic of relay K3 ..................................1=RE, 2=FR (not TAR 1700), 3 = HT ...............1
P13 .... -.. x . x .- ....88..... Switching characteristic of relay K4 ..................................1=RE, 2=FR, 3=HT...........................................1
P14 .... x. x .x .x....88..... Setpoint-shift (day/night mode) ON time...........................0...235, oFF ......................................................oFF
P15 .... x. x .x .x....88..... Setpoint-shift (day/night mode) OFF time .........................0...235, oFF ......................................................oFF
P16 .... x. x .x .x....88..... Maximum setpoint value adjustable by P04......................P17...+300°C....................................................+50°C
P17 .... x. x .x .x....88..... Minimum setpoint value adjustable by P04.......................-110°C...P16 ....................................................-50
P18 .... x. x .x .x....88..... Hysteresis of Control Setpoints 1 - 4 ................................0,2...20 .............................................................2.0
P19 .... x . x . x . x....70..... Operating Mode ................................................................1 = 3 Stages + Alarm........................................1
2 = 4 Stages
3 = Double 3-Stages
4 = Differential control
P20 .... x . x . x .x....88..... Minimium Idle Time (all relays) .........................................0...59 min..........................................................0
P21 .... x. x .x .x....-- ...... Remaining time of alarm delay .........................................Display only !
P22 .... x. x .x .x....-- ...... Remaining time OK-input delay ........................................Display only !
P23 .... x. x .x .x....88..... Calibration of Sensor 1 .....................................................-10,0...+10,0 ....................................................0
P24 .... x. x .x .x....88..... Calibration of Sensor 2, switch oFF ..................................-10,0...+10,0, oFF.............................................0
P25 .... x. x .x .x....70* ... Sensor Type and Kind of Degrees ....................................1 = TF 201 (°C) ................................................1
2 = TF 201 (°F)
3 = Pt1000 (°C).
4 = Pt1000 (°F)
P26 .... x. x .x .x....88..... Alarm delay .......................................................................1...99 min..........................................................5
P27 .... x. x .x .x....88..... Upper alarm limit (relative, in relation to the ..................0...100 ..............................................................100
current, possibly shifted Control Setpoint 1)
P28 .... x. x .x .x....88..... Lower alarm limit (absolute value) ....................................-100...+300°C ...................................................-100
P29 .... x. x .x .x....88..... Control input (Optocoupler Input) DI/OK 1........................oFF ...................................................................oFF
1 = day/night mode
2 = external alarm
3 = controller OFF
P30 .... x. x .x .x....88..... Delay time for DI/OK 1 ......................................................0...99 min..........................................................2
P31 .... x. x .x .x....88..... Analog output: 10V output voltage at................................-100...+300°C ...................................................50
P32 .... x. x .x .x....88..... Analog output: 0V output voltage at..................................-100°C...P31.....................................................-50
P33 .... x. x .x .x....88..... Analog output: Integral time (I-part) ..................................oFF ...................................................................oFF
1 = appr. 0,25 min
2 = appr. 0,5 min
3 = appr. 1 min
4 = appr. 2 min
5 = appr. 4 min
P34 .... x. x .x .x....88..... Analog output: Mode.........................................................oFF ...................................................................oFF
1= proportional
2= inversely proport.
3= proportional, relative to the current setpoint
4= inversely proport., relative to the
current setpoint
P35 .... x. x .x .x....- ....... Real time clock: Hours .....................................................0...23
P36 .... x. x .x .x....- ....... Real time clock: Minutes ..................................................0...59
P37 .... x. x .x .x....- ....... Real time clock: Seconds.................................................Display only !
P38 .... x. x .x .x....88..... Data transmission speed (Baudrate) ................................1 = 1200, 2 = 2400, 3 = 4800, 4 = 9600 ...........4
5 = 19200, 6 = 28800, 7 = 57600
P39 .... x. x .x .x....88..... Adress of the controller in a network.................................1...78 ................................................................78
P40 .... x. x . x .x....- ....... Current error + error listing................................................multiple errors present: scroll by up/down keys
P41 .... x . x . x . x....- ....... Access Code.....................................................................0...99 ................................................................0
Code
x = Functions available in this mode,
without "x" = parameters invisible
Failure Display / Failure handling
Sensor short circuit or broken
If one of the sensors is broken, disconnected or hot-wired, or the value
is located outside of the specified range, the display shows "- - -" at first.
After 1 minute the display flashes and shows an error code. The alarm
relay will be activated at the same time.
Error Codes
E00 ...........................................ok
E01 ................. sensor F1 broken
E02 ........... sensor F1 short circuit
E03 ... sensor F1 overtemperature
E04 ....sensor F1 low temperature
E05 .................. sensor F2 broken
E06 ........... sensor F2 short circuit
E07 ... sensor F2 overtemperature
E08 .....sensor F2 low temperature
E09 ........ failure at the digital input
Failure of Sensor 1
If this sensor fails, all relays will drop out.
Display shows "oFF" if:
1. ...controller unit is switched OFF via
digital input OK1 or via network.
2. ...you select P02 or P24 and the
evaporator sensor is switched off.

Technical Manual TAR x700-2 page 3
Functional Description
Signal Input
The controller unit is able to work with the tempe-
rature sensor types TF 201 and TF 501 (Pt1000).
This must be preset by parameter P25.
Ranges:
P25 = 1 (TF 201).......-50...+100°C
P25 = 3 (TF 501/Pt1000).......-100...+300°C
Please note the specific temperature restric-
tions of the different sensor types (e.g.
-40...+80°C with standard-TF-types) and ask
for matching products if necessary.
Actual Value- and Status Display
Temperaturevaluescanbedisplayedin°Cor°F.This
will be preset together with the sensor type.
P01 shows the measured value of sensor 1.
If other parameters are selected, 4 minutes after
the last keypress the display switches back to P01
automatically. In operating mode 3+4, P02 shows
the measured value of sensor 2. In operating mode
'Differential control', P03 shows additionally the
differential value between sensor 1 and 2.
Display Correction
The Actual Value Display P01 can be calibrated by
P23, P02 can be calibrated by P24.
Operating Modes
The TAR controller knows 4 different operating
modes, which can be preset by P19:
P19 = 1: 3 Stages + Alarm.
In this mode
you realize a 3-
stage controller,
relay K4 works
as a closed cir-
cuit alarm relay,
sensor input 2 is
disabled.
The value of
sensor 1 will be
compared with
P04, P05 and
P06, the relays K1, K2 or K3 switch depending on
the deviation. P04 is always an absolute value, the
following setpoints can be either relative values or
absolute values (preset by P08).
Relative values = Stage switches in a specific
distance to the leading setpoint P04. If P04 will be
changed, the relative setpoints will be changed the
same amount.
P19 = 2 : 4-stage controller
Sensor input
2 is disabled
in this mode.
The value of
sensor 1 will be
compared with
P04, P05, P06
and P07, the
relays K1, K2,
K3 or K4 switch
depending on
the deviation.
Controlsetpoint1(P04)isalwaysanabsolutevalue,
the following setpoints can be either relative values
or absolute values (preset by P08).
P19 = 3 : Double 2-Stage Controller
Sensor 1 af-
fects on the
control set-
points P04/
P05 (= relays
K1/K2=control
circuit 1).
P04 is the lea-
dingsetpointof
control circuit
1, control set-
point 2 (P05)
can be either absolute or relative (P08). Sensor 2
affects on the control setpoints P06/P07 (= relays
K3-K4 = control circuit 2). P06 is the leading setpoint
of control circuit 2, P07 can be either absolute or
relative (P08).
P19 = 4 Differential Controller
Thecalculateddif-
ferential amount
from "sensor 1
minus sensor 2"
will be compared
with P04.
Relay K1 swit-
ches, if the pre-
set value P04 +
hysteresis P18
is reached. The
relay switches off
again, if the dif-
ferential amount
decreases and reaches P04. The stages 2 (relay
K2, P05, assigned to sensor 1) and 3 (relay K3,
P06, assigned to sensor 2), can work independly
as single stage controllers.
Relay K4 works as a closed circuit alarm relay.
Switching Hysteresis
With P18 you set a switching hysteresis, which
affects to all setpoints. The position of this hyste-
resis (above/below the setpoint) depends on the
selected switching characteristics (P10-P13) of
the single relays.
Setpoint Limits
To prevent that the final user adjusts the setpoints
to an inadmissible value, the setpoint range can be
limited by P16 and P17.
Real time clock
The integrated real time clock allows to change the
setpoints at specific times. The timer has a power
backup for about 10 days in case of power failure.
The time of the day and the date can be set with
parameters P35...P36.
Because the display has only three digits, the time
value comes in the following format:
Day-/Night Mode / Setpoint Offset
Initiation by real-time clock
With P14/P15 you can set a period of time within
all setpoints will be shifted by the amount of P09.
If not necessary, you can disable P14/P15 (display
shows "oFF").
Initiation by Digital Input
Digital Input OK 1 can also be programmed to
activate this offset (P29=1). An active 2nd setpoint
is indicated by a flashing decimal point.
Temperature Alarm
If the tempe-
rature value
measured with
sensor 1 ex-
ceeds the ran-
ge set by P27
and P28, the
alarm relay will
be activated
after the delay
timerP26isrun
down.
Parameter P21 shows the remaining time up to
an alarm.
P28 (lower limit) is an absolute value, P27 is always
a relative value in a distance to the actual setpoint
1 (P04 + potential shift).
3rd Position=
minutes x 10
1st and 2nd
Position=hours
Relay Switching Characteristic
The Switching Characteristic of the relay K1-K4 is
defined by the parameters P10...P13. The following
characteristics are possible:
1= Refrigeration (RF)
Used for standard applications (e.g.
temperatures above 0°C). The load would be
switched by the N/O-contact.
Actual value = setpoint + hysteresis: Relay on
2 = Freezing (FR)
The load would be switched by the N/C-
contact, this enables that the load will be
switched on permanently in case of mains
loss or controller defect.
Actual value = setpoint + hysteresis: Relay off
3 = Heating (HT)
Usable for heating applications. Load
would be switched off in case of mains
fail or controller defect.
Actual value = setpoint -hysteresis: Relay on
Minimum Idle-Time
If a load is switched off by a relay, this relay cannot
be switched on again before the time set with P20
is over. P20 affects all relay stages.
The indicator LED's of the single stages flashes
while this idle time runs.
The Minimum Idle-Time affects immediately after
power-on of the controller.
Digital Input
Digital input DI1 is normally connected to mains
voltage. If this voltage is interrupted, the function set
with P29 will be initiated after a time delay (P30).
P30 is adjustable within 0...99 minutes, but at '0' the
minimum delay is appr. 4 seconds.
P29=oFF Digital input DI/OK 1 is de-activated
P29=1 Control Setpoint 2 (night-setpoint) is
active. The setpoints increase/
decrease by the amount of P09.
P29=2 An external alarm is detected after
P30 is run down. LED 4 and the alarm
relay are activated after P26 has been
run down.
P29=3 Controller unit oFF. All control
functions will be disabled, the display
shows "oFF". This allows to switch off
the unit without an alarm message in
a network. Relays 1-3 are deactivated,
the alarm relay remains in a neutral
position.
Analogue output behaviour:
• Delivers 0V with op-mode
proportional (P34=1 or 3).
• Delivers 10V with op-mode
anti-proportional (P34 = 2 or 4)
P22 shows the remaining delay time of the digital
input.
Using the TAR 1700-2 this function must
bestartedbyopeninganexternal,potential
free contact connected to terminals 11/12.
Never connect mains voltage to these
terminals, danger of destruction! This
contact must be suitable for 5VDC/1mA.
K4K3
P06
K2
P05
sens2
sens1
K1
P04
K4K3
P07P06
K2
P05
sens2
P04
K1
sens1
K2
P05
K4K3
P06 P07
sens2
control circ uit 1 control circ uit 2
sens1
K1
P04
K4K3
P06
K2
P05
sens2
K1
P04
Diff.
sens1
alarm after P26 is run down
alarm after P26 is run down
temperature profile
Upper AT
P27
(relative)
Lower AT
P28
(absolute)

page 4 Technical Manual TAR x700-2
TAR 1700-2 - Dimensions and Connection
Connection Example (simplified)
Voltage Output / Analog Output
The TAR contains an analogue 0-10V DC-signal
output. Because the output is scalable, it can be
used either to forward the actual value of sensor 1
(P01) or as a proportional /PI-controller output. In
differential control mode the voltage output depends
on the determined differential amount.
P31......actualtemperature(resp.differentialamount)
the output voltage delivers 10V.
P32......actual temperature (resp. differential
amount) the output voltage amounts 0V.
P33......integral part (I-part) of the output signal in 5
steps from appr. 0,25 to 4 minutes or oFF.
Analog Output Modes
P34 fixes the Analog Output Mode.
P34 = oFFOutput is de-activated.
P34 = 1 Output works proportional, that means
rising temperature
-> rising output voltage.
P31/P32 are absolute values.
P34 = 2 Output works anti-proportional, that
means rising temperature
-> falling output voltage.
P31/P32 are absolute values.
P34 = 3 Like P34=1 but the values set by
P31/P32 work relative to the current
setpoint 1 (P04 + offset).
Example:
P31 = 10°C, P32 = -10°C, P34 = 3,
P04 = 15°C, no current shift
Output Voltages:
10V at P04 + P31 = 25°C
0V at P04 - P32 = 5°C
P34 = 4 Like P34=2, but the values set by P31/
P32 work relative to the
current setpoint 1 (P04 + offset).
Example:
P31 = 10°C, P32 = -10°C, P34 = 4,
P04 = 15°C, no current shift
Output Voltages:
0V at P04 + P31 = 25°C
10V at P04 - P32 = 5°C
Example: Actual value Image
You need a remote display or similar, which shows
-50°C with 0V DC input voltage and +50°C with 10V
DC input voltage:
P32 = "-50", P31 = "+10", P34 must be "1".
Example: Proportional Controller
You want to drive e.g. a motor valve with 0-10V
DC input depending on a temperature. This valve
should be half open at 15°C. If the temperature falls,
the valves should open, if the temperature passes
10°C it must be full open. If the temperature rises,
the valve should be closed, with 20°C and above it
should remain closed.
P32 ="10.0", P31 ="20.0", P34 ="2"
Slow-down time / I-part
P33 (slow-down time) fixes the effect of the I-part
to the control process in 5 steps. The I-part amount
of the controlling variable is identical with the P-part
and will be added. The full size of the I-part will effect
after P33 is run down.
Effects of the Slow-down time
When P34 = 1
Act.Val. = Setpoint: Output 5V ± I-Part
Act.Val. > Setpoint: Output shifts with I-part
to 10V
Act.Val. < Setpoint: Output shifts with I-part
to 0V
When P34=2
Act.Val. = Setpoint: Output 5V ± I-Part
Act.Val. > Setpoint: Output shifts with I-part
to 0V
Act.Val. < Setpoint: Output shifts with I-part
to 10V
When P34 = 3
P31/P32 define a proportional band around the
active setpoint. The output voltage is 10V at P04
+ P31 and 0V at P04-P32.
Act.Val. = Setpoint: Output 5V ± I-Part
Act.Val. > Setpoint: Output shifts with I-Part
to 10V
Act.Val. < Setpoint: Output shifts with I-Part
to 0V
When P34 = 4
P31/P32 define a proportional band around the
active setpoint. The output voltage is 0V at P04
+ P31 and 10V at P04-P32.
Act.Val. = Setpoint: Output 5V ± I-Part
Act.Val. > Setpoint: Output shifts with I-Part
to 0V
Act.Val. < Setpoint: Output shifts with I-Part
to 10V
After an excursive change of the actual value the P-
part is calculated from the max. output voltage and
the proportional band:
Ux = (10V / (|P36 - P37| [K])) * delta Theta [K]
Example: • 10V Uout at +10°C, 0V Uout at -10°C
• aimed setpoint 0°C = 5V Uout
• current actual value 0°C
Actual value increases by 2K ->
• Uout rises to 6V immediately
• Uaus rises farther, after P38 is run
down, 7V will be reached.
dimensions in: mm (inches)
ELREHATAR
76 (3.0)
1 2 3
35 (1.38)
P
4
28 (1.1)
75 (2 .9 5)
R ück ans ic ht m it B efe stigu ngs ra hm e n
741 2 3 5 6
19202122 1 82324
37 (1.46)
8 9 1 110 12
1617 15 1 4 13
T A R 1 70 0-2
K 3
K 2
1
N
PE
2 3
K 1
4 65
24
L
21
22
23 1 9
20
0..10V
1 2 -2 4 V AC
1 8 -3 3 V D C
5 0 -6 0 H z
m a x . 5 , 5V A
12
K 4
97 8 10 1 1
O K 1
13
16
DO
NDO
1718 1 5 14
23 0/2 4V ,
5 VA
probe 1
probe 2
rear view with mounting frame
70 (2.76)
11
12
8
10
9
7
6
K3
3
5
4
K2
1
2
12
(.47)
19 0..10V
Temp./Differenzregler
Temp./Difference Control
12-24VAC
18-33VDC
50/60Hz
max. 5,5VA
14
13
DI1
ND O
DO
15
16
K4
17
18
ELREHA
24
F1
20
21
F2
22
23
K1
56 (2.2 ) 3 (.12)

Technical Manual TAR x700-2 page 5
Dimensions / Connection TAR 3700-2
Temperature probe connection
Dimensions / Connection TAR 5700-2
35(1.38)
59 (2. 32)
26 (1. 02)
39 (1. 54)
Panel housing dep. on DIN 43700/IEC 61554
Cut-out: 92 x 45 mm (b x h)
Tolerances max: +0,8 (b), +0,6 (h)
45 (1.77)
49 (1.93)
1
31
12131415
23
2425
4567891011
2627282930
1
1617181920212223
mains Relay K1 Relay K2 Relay K4
(Alarm)
probe F2
probe F1
Relay K3
RS
48 5
NDO
1 32 4 65 87
N
TA R 3700 -2
N
LL L
O K 1
A C
2423
DO
0-10V OUT
D C
2625 2 7
1613119 10 12 1514 17 18 19
3528 29 3 0 3 1 32 3 3 34 36 37 3 8
DI 1
RS
485
24V AC
NDO
DO
RS
485
DO
NDO
Important: use double-pole
switches only if all controllers are
supplied by the same transformer
Electrical Cabinet
Important: Never connect
the secondary coil of the
transformer to PE!
Danger of destruction!
Attention
Networking of TAR controllers
All controllers can be networked to a host (PC or
SMZ) via their built-in RS-485-interface.
• Because all units are connected parallel on the
datacable,eachunithasitsownnetworkaddress
(P39) to ensure a specific communication.
!! Never use address 64 !!
• The data transmission speed is fixed by P38, the
default value is 9600 Baud.
• Wiring must be made by standard data cable.
• Shieldings must be connected to the nearest
grounding terminal.
• The unshielded part of the data cable must be as
short as possible.
Ifnetworkedcontrollers(1700-2typesonly)aresup-
pliedbyonetransformeronlyandthesinglepositions
must be switched off, use double-pole switches
only. If not, the unit will be supplied partially over
the shielding of the data connection and continues
operation, depending on the secondary voltage of
the transformer. Please note: If a unit is not supplied,
the PC-software notifies a unit breakdown !
A better way is not to switch-off the supply voltage
but to disable the unit by Digital Input.
Electrical Cabinet
PE
Dimensions in mm,
(in brackets = inches)
Note
Protective Earth
Earth
46 (1.81)
63 (2.48)
91 (3.58)
1 2 3 4 5 76 108 9 1 211 13 1 4 1 5 1 6 17 1 8
2 4
P
19
1 3
27232 220 2 1 25 2624 292 8 3130 3 2 3433
105 (4 .13 )
35 3 6 37 38
TA R
E L R EH A
TAR ELREHA
ELREHA
TAR
76 (3.0)
1 2 3
35 (1.38)
P
4
2/ 4/
E LR E H A
1/ 3/
P
TAR
TAR ELREHA
ELREHA
TAR
76 (3.0)
1 2 3
35 (1.38)
P
4
119 (4.69)
0..10V DC
unger.
DI 1
92 (3.62)
22
7
26
24 25
23 30
29
15
13 14
12
811
10
9
K 4
K 3
K 2
DO
GND
NDO
PE LN
230VAC
50/60Hz
max.5VA
56
34
2
1
17 20 21
18
K 1
F2
16
F1
97 (3.81)
Made in Germany
ELREHA
8
119 (4.69 )
0..10V DC
DI 1
92 (3.62)
22
7
29 30
25
23 24 26
13 15
14
89
K 4
K 2
DO
GND
NDO
3456
2
LN
PE
1
17
230V AC
50/60Hz
max.5VA
21
K 1
20
18 19
4..20mA
unger.
F2
16
F1
97 (3.81)
Made in Germany
ELREHA
8
29 30 31
16 17 18 19 20 21 24 25 2622 23
19
(0.75)

page 6 Technical Manual TAR x700-2
CONNECTION INFORMATION & SAFETY INSTRUCTIONS
The guarantee will lapse in case of damage caused by failure
to comply with these operating instructions! We shall not be
liable for any consequent loss! We do not accept liability for
personal injury or damage to property caused by inadequate
handling or non-observance of the safety instructions!
The guarantee will lapse in such cases.
This manual contains additional safety instructions in the
functional description. Please note them!
If you notice any damage, the product may not be connected
to mains voltage! Danger of Life!
A riskless operation is impossible if:
• The device has visible damages or doesn't work
• After a long-time storage under unfavourable conditions
• The device is strongly draggled or wet
• After inadequate shipping conditions
• Never use this product in equipment or systems that are
intended to be used under such circumstances that may
affect human life. For applications requiring extremely
high reliability, please contact the manufacturer first.
• The product may only be used for the applications
described on page 1.
• Electrical installation and putting into service must be
done from qualified personnel.
• During installation and wiring never work when the
electricity is not cut-off ! Danger of electric shock!
• Never operate unit without housing.
Danger of electric shock!
• All ‘PE’ terminals must be connected to ground.
Danger of electric shock! Additionally, the internal noise
filter will not work, faulty indicated values may occur.
• Please note the safety instructions and standards of your
place of installation!
• Before installation: Check the limits of the controller and
the application (see tech. data). Check amongst others:
- Make sure that all wiring has been made in accordance
with the wiring diagram in this manual.
- Supply voltage (is printed on the type label).
- Environmental limits for temperature/humidity.
- Maximum admitted current rate for the relays. Compare
it with the peak start-up currents of the controlled loads
(motors, heaters,etc.).
Outside these limits malfunction or damages may occur.
• Sensor/probe cables must be shielded. Don’t install them
in parallel to high-current cables. Shielding must be
connected to PE at the end close to the controller.
If not, inductive interferences may occur.
• Please note for elongation: The wire gauge is not critical,
but should have 0,5mm² as a minimum.
• Mounting the controller close to power relays is
unfavourable. Strong electro-magnetic interference,
malfunction may occur!
• Take care that the wiring of interface lines meets the
necessary requirements.
• All used temperature sensors must be identical. Never
use different types at the same time. This will not work.
• TF-type sensors are not designed for being immersed in
fluids permanently. In such a case, always use dip-fittings.
With extreme temperature variations, the sensor may be
damaged.
Cleaning
Theuseofadry,lint-freeclothandhouseholdagentsissufficient
to clean the product.
Never use acids or acidic fluids! Risk of damage!
Installation / Start-up
Read Safety Instructions !
If the TAR unit is switched ON, the display shows
the actual value of sensor 1. At first you have to set
the basic parameters:
• Enter Access Code '70' at P41
• Operating mode (P19)
• Type of used sensor (P25)
• Enter Access Code '88' at P40
• Switching characteristic of the relays
(P10-P13)
• Task of control input DI1 (OK1) (P29)
• If the unit is networked:
Address in network (P39) and Baudrate (P38)
• Function of the Analogue Output (P31 - P34)
This was the basic configuration, now you can enter
the specific setpoints, times, etc.
Installation hint:
If the measured values 'jump' check the
following: Is the shielding of the sensor
wire connected to PE near the controller
unit? Is the PE terminal of the controller
unit connected to PE? If the sensor wire
is shielded correctly but the value on the
display continues 'jumping', please try
to solve the problem by removing the
shield from PE and connecting it to a
ground terminal of the TAR.
Display Adjust
To calibrate the two actual value displays, use para-
meters P23 resp. P24 to correct the value.
original set up: 9.3.18, tkd/jr checked: 12.3.2018, ek/ha approved: 12.3.2018, mv/mh transl.(): corr:
For the devices TAR 1700-2, TAR 3700-2 and TAR 5700-2 we state the following:
When operated in accordance with the technical manual, the criteria have been met that are outlined in the EMC Directive 2014/30/EC and the Low Voltage
Directive 2014/35/EC. This declaration is valid for those products covered by the technical manual which itself is part of the declaration.
Following standards were consulted for the conformity testing to meet the requirements of EMC and Low Voltage Guidelines:
EN 55011:2016, EN 61010-1:2010, EN 61326-1:2013 CE marking of year: 2017
This statement is made for the manufacturer / importer by:
ELREHA Elektronische Regelungen GmbH Werner Roemer, Technical Director
D-68766 Hockenheim
www.elreha.de Hockenheim ......12.6.2017.................................................................
(Name / Address) City Date Signature
EC Declaration of Conformity
This manual suits for next models
2
Table of contents
Other ELREHA Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Hugo Müller
Hugo Müller TS 3.10 KNX Series instruction manual

LAE electronic
LAE electronic TMR15 Instructions for use

AFRISO
AFRISO CosiTherm FT operating instructions

UIS
UIS STH-230 installation guide

Automationdirect.com
Automationdirect.com SOLO SL4896 Series Quick start guid

BST
BST E806TW quick start guide