Elsner KNX S1R-UP Guide

Item numbers 70511 (KNX S1R-UP), 70512 (KNX S1R-BA2-UP), 70513 (KNX S1R-BA4-UP)
EN
KNX S1R-UP
KNX S1R-BA2-UP
KNX S1R-BA4-UP
Multifunctional Actuators
Installation and Adjustment


1 Contents
Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany
Actuators KNX S1R-UP • from software version 4.00, ETS programme version 4.0
Status: 27.05.2020 • Subject to technical changes. Errors excepted.
1. Description ........................................................................................... 3
1.0.1. Scope of delivery .......................................................................................... 4
1.1. Technical specification ............................................................................................. 4
2. Installation and start-up ....................................................................... 5
2.1. Installation notes ...................................................................................................... 5
2.2. Safety notice for automatic functions .................................................................... 5
2.3. Installation ................................................................................................................ 6
2.4. Connection ................................................................................................................ 7
2.4.1. Connection examples ................................................................................... 7
2.5. Instructions for assembly and operational start-up. ............................................. 9
3. Addressing of the device at the bus .................................................... 9
4. Disposal ............................................................................................... 9
5. Transfer protocol ............................................................................... 10
5.1. List of all communication objects ......................................................................... 10
6. Parameter setting .............................................................................. 21
6.1. General settings ..................................................................................................... 21
6.2. Output ..................................................................................................................... 21
6.2.1. Channel settings – drives ........................................................................... 22
6.2.1.1. Control (drives) ............................................................................ 24
6.2.1.2. Manual ........................................................................................... 31
6.2.1.3. Automation - external .................................................................. 32
6.2.1.4. Automatic - internal for shading (drives) .................................... 32
6.2.1.5. Automatic for windows (drives) .................................................. 37
6.2.1.6. Scenes (drives) .............................................................................. 41
6.2.1.7. Button inputs (drives) ................................................................... 41
6.2.2. Output channel with drive .......................................................................... 47
6.2.3. Connection option for zero position sensors ........................................... 49
6.2.4. Output channel with switch function ........................................................ 51
6.2.5. Channel settings – switch functions .......................................................... 52
6.2.5.1. Connection (switch functions) ..................................................... 52
6.2.5.2. On/Off switch delays, time switching (switch functions) .......... 53
6.2.5.3. Blocking function (switch functions) ........................................... 54
6.2.5.4. Button input (switch functions) ................................................... 54
6.3. Temperature threshold values .............................................................................. 55
6.3.1. Temperature threshold value 1, 2, 3, 4 ..................................................... 55

2 Clarification of signs
This manual is amended periodically and will be brought into line with new software
releases. The change status (software version and date) can be found in the contents footer.
If you have a device with a later software version, please check
www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to-
date version of the manual is available.
Clarification of signs used in this manual
Installation, inspection, commissioning and troubleshooting of the device
must only be carried out by a competent electrician.
Safety advice.
Safety advice for working on electrical connections, components,
etc.
DANGER! ... indicates an immediately hazardous situation which will lead to
death or severe injuries if it is not avoided.
WARNING! ... indicates a potentially hazardous situation which may lead to
death or severe injuries if it is not avoided.
CAUTION! ... indicates a potentially hazardous situation which may lead to
trivial or minor injuries if it is not avoided.
ATTENTION! ... indicates a situation which may lead to damage to property if it is
not avoided.
ETS In the ETS tables, the parameter default settings are marked by
underlining.

3 Description
Actuators KNX S1R-UP • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
1. Description
Actuators KNX S1R-UP with integrated façade control have a multifunctional output
which can connect to either a drive with Up/Down control (blinds, awnings, shutters,
windows) or two switchable devices (On/Off for light and ventilation). Because the out-
put is designed to be free of potential, other systems can also be controlled, e.g. via the
manual switch input on a motor control unit.
Automation can be specified externally or internally. Internally, there are numerous op-
tions available for blocking, locking (e.g. master-slave) and priority definitions (e.g.
manual-automatic). Scenes can be saved and called up via the bus (scene control with
16 scenes per drive).
The KNX S1R-B4-UP and KNX S1R-BA2-UP models are equipped with inputs which
are used as bus inputs (buttons, alarms, etc.) or for T-NTC temperature sensors. The
KNX S1R-UP model does not have any analogue/digital inputs.
Functions:
•Free of potential multifunctional output for a 230 V drive (shading,
windows) or connection of two switchable devices (light, fan)
• Relays switch with low wear near the zero-voltage transition
•Inputs for binary contact or temperature sensor (not on KNX S1R-UP)
•Automatic runtime measurement of the drives for positioning (incl. fault
reporting object)
•Position feedback (movement position, also slat position for shutters)
•Position storage (movement position) via 1-bit object (storage and call-up
e.g. via buttons)
• Parameters for taking drive and mechanics downtimes into account
• Control via internal or external automation functions
•Integratedshade control with slat adjustment for shutters based on the
position of the sun
•Scene control for movement position with 16 scenes per drive (also slat
position for shutters)
• Mutual locking of two drives using zero position sensors prevents collisions
e.g. of shade and window (master–slave)
•Blocking objects and alarm reports have different priorities, so safety
functions always take precedence (e.g. wind block)
• Manual or automatic priority setting via time or communication object
•4 temperature switching outputs in the application program with
adjustable threshold values (presetting the parameters or communication
object)
•Brief time limit (movement command blocked) and 2 movement limits
Configuration is made using the KNX software ETS 5. The product file can be down-
loaded from the ETS online catalogue and the Elsner Elektronik website on www.els-
ner-elektronik.de in the “Service” menu.

4 Description
Actuators KNX S1R-UP • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
1.0.1. Scope of delivery
•Actuator
1.1. Technical specification
The product is compliant with the provisions of EU guidelines.
Housing Plastic
Colour White
Assembly Flush-mounted (in connector socket Ø 60 mm, 60 mm
deep)
Protection category IP 20
Dimensions approx. 50 x 50 x 54 (W × H × D, mm)
Weight approx. 100 g
Ambient temperature Operation -20…+45°C, storage -30…+85°C
Ambient humidity 5...80% RH, non-condensing
Operating voltage KNX bus voltage
Current at the bus 10 mA
Output 1 × output, free of potential
with 2 connections for drive up/down or 2 devices
(power supply, PE/N/1/2).
Secured by a microfuse T4.0 A.
Can withstand a total of max. 4 A (resistive load),
switch-on current totally max. 4 A at 20ms.
Maximum load Each terminal contact may be loaded with a maximum
of 10 A.
Minimum current for runt-
ime measurement
AC effektive 200 mA
Inputs KNX S1R-UP: no inputs
KNX S1R-BA2-UP: 2× analogue/digital.
KNX S1R-BA4-UP: 4× analogue/digital.
max. output length 10 m
Setting range for the T-NTC
temperature sensor on the
input
-30°C...+80°C
Data output KNX +/- bus connector terminal
BCU type Integrated microcontroller
PEI type 0
Group addresses max. 1024
Assignments max. 1024
Communication objects KNX S1R-UP: 147
KNX S1R-BA2-UP: 174
KNX S1R-BA4-UP: 200

5 Installation and start-up
Actuators KNX S1R-UP • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
2. Installation and start-up
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
DANGER!
Risk to life from live voltage (mains voltage)!
There are unprotected live components within the device.
• VDE regulations and national regulations are to be followed.
• Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
• Do not use the device if it is damaged.
• Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is no
longer guaranteed.
The device is only to be used for the intended purpose described in this manual. Any
improper modification or failure to follow the operating instructions voids any and all
warranty and guarantee claims.
After unpacking the device, check it immediately for possible mechanical damage. If it
has been damaged in transport, inform the supplier immediately.
The device may only be used as a fixed-site installation; that means only when assem-
bled and after conclusion of all installation and operational start-up tasks and only in
the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2.2. Safety notice for automatic functions
WARNING!
Risk of injury from automatically moving components!
Parts of the system can be started by the automatic controls
and be a danger to persons.
• No persons may remain in the travelling range of parts
driven by an electric motor.
• Adhere to the relevant building regulations.
• Ensure that the return path/access to the building is not blocked
if spending time outside the building (danger of being locked out).
• Correctly decommission the system for maintenance and
cleaning work.

6 Installation and start-up
Actuators KNX S1R-UP • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
If there is a power outage, the system does not work. Therefore, shadings should be
moved to a save position if there are anticipated weather conditions, for example, if
this has not already been done by the automatic function (product protection).
If the power supply is removed, the connected drive switches off. When the power is
restored, the consumer remains switched off until a new movement command is re-
ceived by the actuator.
2.3. Installation
Fig. 1: Bus side
1 Analogue/digital inputs connector
(not for KNX S1R-UP)
2 Label field
3 KNX terminal +/-
4 Programming LED and programming
button (countersunk)
Analogue/digital inputs connector assignment:
KNX S1R-UP: Not assigned!
KNX S1R-B2A-UP: 1: GND | 2: IN1 | 3: GND | 4: IN2
KNX S1R-BA4-UP: 1: GND | 2: IN1 | 3: GND | 4: IN2 | 5: GND | 6: IN3 | 7: GND | 8: IN4
All GND connectors are internally bridged.
1
2
3
4
Fig. 2: Output side
1 Connector for drive/consumers
(free of potential)
1

7 Installation and start-up
Actuators KNX S1R-UP • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
2.4. Connection
The Actuators KNX S1R-UP are installed in a flush-mounted socket. The connection
is made using a KNX connector on the KNX data bus. In addition, a power supply for
the connected drive or consumer is necessary (output free of potential).
Follow the guidelines and standards for SELV electric circuits
while installing and cable laying of the KNX connection and
inputs!
ATTENTION!
Relays may be switched on when starting the device for the first
time!
The bistable relays used in this product may switch on in case of shock,
e. g. during transportation.
• First apply the bus voltage, as this will switch off the relays. Then
switch on the voltage supply of the drive.
The physical address is assigned by the KNX software. There is a button with a control
LED for this on the actuator.
2.4.1. Connection examples
230V drive at the output:
Mains
(230V)
Two 230V consumers at the output:
Mains
(230V)
Each terminal contact may be loaded with a maximum of 10 A.

8 Installation and start-up
Actuators KNX S1R-UP • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
Control of an external motor control unit via the output:
Inputs:
Note: The Actuators KNX S1R-UP can
also be used with direct-current voltage
(12 V DC, 24 V DC) due to their potential-
free output. The „L“ connector is used as
„Com“ in this case. The automatic runtime
measurement is not possible with direct-
currant voltage!
Motor
control unit
Manual switch input
Example KNX S1R-B4-UP with
binary contact on input 1
and T-NTC temperature sensor on input 4.
Connection of the temperature sensor is in-
dependent of the polarity.

9 Addressing of the device at the bus
Actuators KNX S1R-UP • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
2.5. Instructions for assembly and operational
start-up.
Never expose actuators to water (e.g. rain) or dust. This can damage the electronics.
You must not
exceed a relative air humidity of 80%. Avoid condensation.
After the auxiliary voltage has been applied, the device will enter an initialisation phase
lasting a few seconds. During this phase no information can be received or sent via the
bus.
For KNX devices with safety functions (e.g. wind or rain blocks), it is important to set
up periodical monitoring of the safety objects. The optimal ratio is 1:3 (example: if the
weather station sends a value every 5 minutes, the actuator must be configured for a
monitoring period of 15 minutes).
3. Addressing of the device at the bus
The device is supplied with the bus address 15.15.255. You can program another ad-
dress into the ETS by overwriting the 15.15.255 address or by teaching via the pro-
gramming button.
4. Disposal
After use, the device must be disposed of or recycled in accordance with the legal reg-
ulations. Do not dispose of it with the household waste!

10 Transfer protocol
Actuators KNX S1R • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
5. Transfer protocol
5.1. List of all communication objects
Abbreviations:
R Read
WWrite
C Communication
T Transfer
No Text Function Flags Data Point Type Size
1 Software version Readable R-C- [217.1]
DPT_Version
2 Bytes
100 Channel A status automatic
or manual
Output R-CT [1]
1.xxx
1 Bit
101 Channel A manual long
term
Input RWC- [1.8]
DPT_UpDown
1 Bit
102 Channel A manual short
term
Input RWC- [1.8]
DPT_UpDown
1 Bit
103 Channel A manual
movement position
Input RWC- [5.1]
DPT_Scaling
1 Byte
104 Channel A manual slat
position
Input RWC- [5.1]
DPT_Scaling
1 Byte
105 Channel A automatic long
term
Input RWC- [1.8]
DPT_UpDown
1 Bit
106 Channel A automatic short
term
Input RWC- [1.8]
DPT_UpDown
1 Bit
107 Channel A automatic
movement position
Input RWC- [5.1]
DPT_Scaling
1 Byte
108 Channel A automatic slat
position
Input RWC- [5.1]
DPT_Scaling
1 Byte
109 Channel A switch from
manual to automatic
Input RWC- [1]
1.xxx
1 Bit
110 Channel A automatic
blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
111 Channel A current
movement position
Output R-CT [5.1]
DPT_Scaling
1 Byte
112 Channel A current slat
position
Output R-CT [5.1]
DPT_Scaling
1 Byte
113 Channel A status object Output R-CT [1]
1.xxx
1 Bit
114 Channel A - Approach
position memory manually
Input RWC- [1.1]
DPT_Switch
1 Bit
115 Channel A - Learn object 0
position memory manually
Input RWC- [1.1]
DPT_Switch
1 Bit

11 Transfer protocol
Actuators KNX S1R • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
116 Channel A - Learn object 1
position memory manually
Input RWC- [1.1]
DPT_Switch
1 Bit
119 Channel A - Approach
position memory
automatically
Input RWC- [1.1]
DPT_Switch
1 Bit
120 Channel A - Learn object 0
position memory
automatically
Input RWC- [1.1]
DPT_Switch
1 Bit
121 Channel A - Learn object 1
position memory
automatically
Input RWC- [1.1]
DPT_Switch
1 Bit
124 Channel A call saving
scenes
Input RWC- [18.1]
DPT_SceneControl
1 Byte
125 Channel A outdoor
temperature
Blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
126 Channel A outdoor
temperature blocking
measurement value
Input RWC- [9.1]
DPT_Value_Temp
2 Bytes
127 Channel A outdoor
temperature blocking status
Output R-CT [1.1]
DPT_Switch
1 Bit
128 Channel A twilight object Input RWC- [1.1]
DPT_Switch
1 Bit
129 Channel A twilight
measurement value
Input RWC- [9.4]
DPT_Value_Lux
2 Bytes
130 Channel A twilight status Output R-CT [1.1]
DPT_Switch
1 Bit
131 Channel A time control Input RWC- [1.1]
DPT_Switch
1 Bit
132 Channel A inside
temperature release object
Input RWC- [1.1]
DPT_Switch
1 Bit
133 Channel A inside
temperature release
measurement value
Input RWC- [9.1]
DPT_Value_Temp
2 Bytes
134 Channel A inside
temperature release target
value
Input RWC- [9.1]
DPT_Value_Temp
2 Bytes
135 Channel A inside
temperature release status
Output R-CT [1.1]
DPT_Switch
1 Bit
136 Channel A shading object Input RWC- [1.1]
DPT_Switch
1 Bit
137 Channel A shading
brightness
Measurement value 1
Input RWC- [9.4]
DPT_Value_Lux
2 Bytes
No Text Function Flags Data Point Type Size

12 Transfer protocol
Actuators KNX S1R • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
138 Channel A shading
brightness
Measurement value 2
Input RWC- [9.4]
DPT_Value_Lux
2 Bytes
139 Channel A shading
brightness
Measurement value 3
Input RWC- [9.4]
DPT_Value_Lux
2 Bytes
140 Channel A shading
threshold value
Input /
output
RWCT [9.4]
DPT_Value_Lux
2 Bytes
141 Channel A shading
threshold value 1 = + | 0 = -
Input RWC- [1]
1.xxx
1 Bit
142 Channel A shading
threshold value +
Input RWC- [1]
1.xxx
1 Bit
143 Channel A shading
threshold value -
Input RWC- [1]
1.xxx
1 Bit
144 Channel A shading status Output R-CT [1.1]
DPT_Switch
1 Bit
145 Channel A shading position
Teaching object
Input RWC- [1]
1.xxx
1 Bit
146 Channel A azimuth Input RWC- [9]
9.xxx
2 Bytes
147 Channel A elevation Input RWC- [9]
9.xxx
2 Bytes
148 Channel A cold air supply
blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
149 Channel A cold air supply
outside temperature
measurement value
Input RWC- [9.1]
DPT_Value_Temp
2 Bytes
150 Channel A cold supply air
blocking status
Output R-CT [1.1]
DPT_Switch
1 Bit
151 Channel A forced
ventilation
Input RWC- [1.1]
DPT_Switch
1 Bit
152 Channel A warm air supply
blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
153 Channel A warm air supply
inside temperature
measurement value
Input RWC- [9.1]
DPT_Value_Temp
2 Bytes
154 Channel A warm air supply
outside temperature
measurement value
Input RWC- [9.1]
DPT_Value_Temp
2 Bytes
155 Channel A warm air supply
blocking target value
Input RWC- [9.1]
DPT_Value_Temp
2 Bytes
156 Channel A warm air supply
blocking status
Output R-CT [1.1]
DPT_Switch
1 Bit
157 Channel A inside
temperature opening object
Input RWC- [1.1]
DPT_Switch
1 Bit
No Text Function Flags Data Point Type Size

13 Transfer protocol
Actuators KNX S1R • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
158 Channel A inside
temperature opening
measurement value
Input RWC- [9.1]
DPT_Value_Temp
2 Bytes
159 Channel A inside
temperature opening target
value
Input RWC- [9.1]
DPT_Value_Temp
2 Bytes
160 Channel A inside
temperature opening
threshold value
Input /
output
RWCT [9.1]
DPT_Value_Temp
2 Bytes
161 Channel A inside
temperature opening
threshold value 1 = +
Input RWC- [1]
1.xxx
1 Bit
162 Channel A inside
temperature opening
threshold value +
Input RWC- [1]
1.xxx
1 Bit
163 Channel A inside
temperature opening
threshold value -
Input RWC- [1]
1.xxx
1 Bit
164 Channel A inside
temperature opening status
Output R-CT [1.1]
DPT_Switch
1 Bit
165 Channel A inside humidity
opening object
Input RWC- [1.1]
DPT_Switch
1 Bit
166 Channel A inside humidity
opening
Measurement value
Input RWC- [9.7]
DPT_Value_Humidity
2 Bytes
167 Channel A inside humidity
opening status
Output R-CT [1.1]
DPT_Switch
1 Bit
170 Channel A zero position
reached
Input RWC- [1.1]
DPT_Switch
1 Bit
171 Channel A zero position
sensor malfunctioning
Output R-CT [1.1]
DPT_Switch
1 Bit
172 Channel A master zero
position status
Output R-CT [1.1]
DPT_Switch
1 Bit
173 Channel A master zero
position command
Output R-CT [1.1]
DPT_Switch
1 Bit
174 Channel A slave zero
position status
Input RWC- [1.1]
DPT_Switch
1 Bit
175 Channel A master zero
position status
Input RWC- [1.1]
DPT_Switch
1 Bit
176 Channel A master zero
position command
Input RWC- [1.1]
DPT_Switch
1 Bit
177 Channel A slave zero
position status
Output R-CT [1.1]
DPT_Switch
1 Bit
178 Channel A drive moving Output R-CT [1]
1.xxx
1 Bit
No Text Function Flags Data Point Type Size

14 Transfer protocol
Actuators KNX S1R • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
179 Channel A malfunction
object
Output R-CT [1]
1.xxx
1 Bit
180 Channel A block 1 blocking
object
Input RWC- [1.1]
DPT_Switch
1 Bit
181 Channel A block 1 wind
blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
182 Channel A block 1 wind
blocking
Measurement value
Input RWC- [9.5]
DPT_Value_Wsp
2 Bytes
183 Channel A block 1 wind
blocking status
Output R-CT [1.1]
DPT_Switch
1 Bit
184 Channel A block 1 rain
blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
185 Channel A block 2 blocking
object
Input RWC- [1.1]
DPT_Switch
1 Bit
186 Channel A block 2 wind
blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
187 Channel A block 2 wind
blocking object
Input RWC- [9.5]
DPT_Value_Wsp
2 Bytes
188 Channel A block 2 wind
blocking
Measurement value
Input R-CT [1.1]
DPT_Switch
1 Bit
189 Channel A block 2 wind
blocking status
Output RWC- [1.1]
DPT_Switch
1 Bit
190 Channel A block 2 rain
blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
191 Channel A block 3 blocking
object
Input RWC- [1.1]
DPT_Switch
1 Bit
192 Channel A block 3 wind
blocking object
Input RWC- [9.5]
DPT_Value_Wsp
2 Bytes
193 Channel A block 3 wind
blocking
Measurement value
Input R-CT [1.1]
DPT_Switch
1 Bit
194 Channel A block 3 wind
blocking status
Output RWC- [1.1]
DPT_Switch
1 Bit
195 Channel A block 3 rain
blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
196 Channel A block 4 blocking
object
Input RWC- [1.1]
DPT_Switch
1 Bit
197 Channel A block 4 wind
blocking object
Input RWC- [9.5]
DPT_Value_Wsp
2 Bytes
198 Channel A block 4 wind
blocking
Measurement value
Input R-CT [1.1]
DPT_Switch
1 Bit
No Text Function Flags Data Point Type Size

15 Transfer protocol
Actuators KNX S1R • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
199 Channel A block 4 wind
blocking status
Output RWC- [1.1]
DPT_Switch
1 Bit
200 Channel A block 4 rain
blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
201 Channel A block 5 blocking
object
Input RWC- [1.1]
DPT_Switch
1 Bit
202 Channel A block 5 wind
blocking
Measurement value
Input RWC- [9.5]
DPT_Value_Wsp
2 Bytes
203 Channel A block 5 wind
blocking status
Output R-CT [1.1]
DPT_Switch
1 Bit
204 Channel A block 5 rain
blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
205 Channel A - Movement
limitation 1 - blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
206 Channel A - Movement
limitation 2 - blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
207 Channel A - Short time
restriction
Input RWC- [1.1]
DPT_Switch
1 Bit
210 Channel A1 - switching Input RWC- [1.1]
DPT_Switch
1 Bit
211 Channel A1 - feedback Output R-CT [1.1]
DPT_Switch
1 Bit
212 Channel A1 - status Readable R-C- [1.1]
DPT_Switch
1 Bit
213 Channel A1 - blocking
object
Input RWC- [1.1]
DPT_Switch
1 Bit
215 Channel A1 start stair case
light function
Input -WC- [1.10]
DPT_Start
1 Bit
216 Channel A1 start stop stair
case light function
Input RWC- [1.10]
DPT_Start
1 Bit
217 Channel A1 connection Input RWC- [1.2]
DPT_Bool
1 Bit
218 Channel A1 - Call up /
saving scenes
Input RWC- [18.1]
DPT_SceneControl
1 Byte
220 Channel A2 switching Input RWC- [1.1]
DPT_Switch
1 Bit
221 Channel A2 feedback Output R-CT [1.1]
DPT_Switch
1 Bit
222 Channel A2 status Readable R-C- [1.1]
DPT_Switch
1 Bit
223 Channel A2 blocking object Input RWC- [1.1]
DPT_Switch
1 Bit
No Text Function Flags Data Point Type Size

16 Transfer protocol
Actuators KNX S1R • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
225 Channel A2 start stair case
light function
Input -WC- [1.10]
DPT_Start
1 Bit
226 Channel A2 start stop stair
case light function
Input RWC- [1.10]
DPT_Start
1 Bit
227 Channel A2 connection Input RWC- [1.2]
DPT_Bool
1 Bit
228 Channel A2 - Call up /
saving scenes
Input RWC- [18.1]
DPT_SceneControl
1 Byte
249 Channel A - local operation
blocking object
Input RWC- [1.1]
DPT_Switch
1 Bit
500 Temp. threshold value 1:
Measured value
Input -WC- [1.1]
DPT_Switch
1 Bit
501 Temp. threshold value 1:
Absolute value
Input -WC- [7]
7.xxx
2 Bytes
502 Temp. threshold value 1:
(1:+ | 0:-)
Input -WC- [7]
7.xxx
2 Bytes
503 Temp. threshold value 1:
Switching delay from 0 to 1
Input R-CT [1.1]
DPT_Switch
1 Bit
504 Temp. threshold value 1:
Switching delay from 1 to 0
Input -WC- [1.1]
DPT_Switch
1 Bit
505 Temp. threshold value 1:
Switching output
Input -SWC- [9.1]
DPT_Value_Temp
2 Bytes
506 Temp. threshold value 1:
Switching output block
Input/
Output
RWCT [9.1]
DPT_Value_Temp
2 Bytes
507 Temp. threshold value 2:
Measured value
Input -WC- [1.1]
DPT_Switch
1 Bit
508 Temp. threshold value 2:
Absolute value
Input -WC- [7]
7.xxx
2 Bytes
509 Temp. threshold value 2:
(1:+ | 0:-)
Input -WC- [7]
7.xxx
2 Bytes
510 Temp. threshold value 2:
Switching delay from 0 to 1
Output R-CT [1.1]
DPT_Switch
1 Bit
511 Temp. threshold value 2:
Switching delay from 1 to 0
Input -WC- [1.1]
DPT_Switch
1 Bit
512 Temp. threshold value 2:
Switching output
Input -WC- [9.1]
DPT_Value_Temp
2 Bytes
513 Temp. threshold value 2:
Switching output block
Input/
Output
RWCT [9.1]
DPT_Value_Temp
2 Bytes
514 Temp. threshold value 3:
Measured value
Input -WC- [1.1]
DPT_Switch
1 Bit
515 Temp. threshold value 3:
Absolute value
Input -WC- [7]
7.xxx
2 Bytes
516 Temp. threshold value 3:
(1:+ | 0:-)
Input -WC- [7]
7.xxx
2 Bytes
No Text Function Flags Data Point Type Size

17 Transfer protocol
Actuators KNX S1R • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
517 Temp. threshold value 3:
Switching delay from 0 to 1
Output R-CT [1.1]
DPT_Switch
1 Bit
518 Temp. threshold value 3:
Switching delay from 1 to 0
Input -WC- [1.1]
DPT_Switch
1 Bit
519 Temp. threshold value 3:
Switching output
Input -WC- [9.1]
DPT_Value_Temp
2 Bytes
520 Temp. threshold value 3:
Switching output block
Input/
Output
RWCT [9.1]
DPT_Value_Temp
2 Bytes
521 Temp. threshold value 4:
Measured value
Input -WC- [1.1]
DPT_Switch
1 Bit
522 Temp. threshold value 4:
Absolute value
Input -WC- [7]
7.xxx
2 Bytes
523 Temp. threshold value 4:
(1:+ | 0:-)
Input -WC- [7]
7.xxx
2 Bytes
524 Temp. threshold value 4:
Switching delay from 0 to 1
Output R-CT [1.1]
DPT_Switch
1 Bit
525 Temp. threshold value 4:
Switching delay from 1 to 0
Input -WC- [1.1]
DPT_Switch
1 Bit
526 Temp. threshold value 4:
Switching output
Output R-CT [1.1]
DPT_Switch
1 Bit
527 Temp. threshold value 4:
Switching output block
Input -WC- [1.1]
DPT_Switch
1 Bit
Input 1 and 2 only for KNX S1R-BA2-UP and KNX S1R-BA4-UP:
250 Input 1 long term Input /
output
RWCT [1.8]
DPT_UpDown
1 Bit
251 Input 1 short term Output R-CT [1.8]
DPT_UpDown
1 Bit
252 Input 1 switching Input /
output
RWCT [1.1]
DPT_Switch
1 Bit
253 Input 1 dim relative Input /
output
RWCT [3.7]
DPT_Control_Dimmin
g
4 Bit
254 Input 1 encoder 8 bit Output R-CT [5]
5.xxx
1 Byte
255 Input 1 encoder
temperature
Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
256 Input 1 encoder brightness Output R-CT [9.4]
DPT_Value_Lux
2 Bytes
257 Input 1 scene Output R-CT [18.1]
DPT_SceneControl
1 Byte
258 Input 1 blocking object Input RWC- [1.1]
DPT_Switch
1 Bit
260 Input 1 - Temperature
sensor malfunction
Output --CT [1.1]
DPT_Switch
1 Bit
No Text Function Flags Data Point Type Size

18 Transfer protocol
Actuators KNX S1R • Version: 27.05.2020 • from software version 4.00, ETS programme version 4.00 •
Technical changes and errors excepted.
261 Input 1 - Temperature
sensor total value
Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
262 Input 1 - Temperature
sensor measured value
external
Input -WC- [9.1]
DPT_Value_Temp
2 Bytes
263 Input 1 - Temperature
sensor measured value
Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
270 Input 2 long term Input /
output
RWCT [1.8]
DPT_UpDown
1 Bit
271 Input 2 short term Output R-CT [1.8]
DPT_UpDown
1 Bit
272 Input 2 switching Input /
output
RWCT [1.1]
DPT_Switch
1 Bit
273 Input 2 dim relative Input /
output
RWCT [3.7]
DPT_Control_Dimmin
g
4 Bit
274 Input 2 encoder 8 bit Output R-CT [5]
5.xxx
1 Byte
275 Input 2 encoder
temperature
Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
276 Input 2 encoder brightness Output R-CT [9.4]
DPT_Value_Lux
2 Bytes
277 Input 2 scene Output R-CT [18.1]
DPT_SceneControl
1 Byte
278 Input 2 blocking object Input RWC- [1.1]
DPT_Switch
1 Bit
280 Input 2 - Temperature
sensor malfunction
Output --CT [1.1]
DPT_Switch
1 Bit
281 Input 2 - Temperature
sensor total value
Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
282 Input 2 - Temperature
sensor measured value
external
Input -WC- [9.1]
DPT_Value_Temp
2 Bytes
283 Input 2 - Temperature
sensor measured value
Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
Input 3 and 4 only for KNX S1R-BA4-UP:
300 Input 3 - Temperature
sensor malfunction
Output --CT [1.1]
DPT_Switch
1 Bit
301 Input 3 - Temperature
sensor total value
Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
302 Input 3 - Temperature
sensor measured value
external
Input -WC- [9.1]
DPT_Value_Temp
2 Bytes
303 Input 3 - Temperature
sensor measured value
Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
No Text Function Flags Data Point Type Size
This manual suits for next models
5
Table of contents
Other Elsner Controllers manuals

Elsner
Elsner WS1000 Color User instructions

Elsner
Elsner KNX S4-B10 230 V Guide

Elsner
Elsner Cala KNX M-T CH Series Guide

Elsner
Elsner Cala KNX T 201 Sunblind Guide

Elsner
Elsner WS1000 Color Owner's manual

Elsner
Elsner Solexa II Parts list manual

Elsner
Elsner Cala KNX M-T Series Guide

Elsner
Elsner KNX eTR Sunblind User manual

Elsner
Elsner KNX eTR Sunblind Series Guide

Elsner
Elsner KNX S1E-UP 230V Guide