manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Emerson
  6. •
  7. Control Unit
  8. •
  9. Emerson 8323G0 Series Installation and operating instructions

Emerson 8323G0 Series Installation and operating instructions

This manual suits for next models

7

Other Emerson Control Unit manuals

Emerson KTM Series User manual

Emerson

Emerson KTM Series User manual

Emerson KTM RICHARDS FIGURE R384 User manual

Emerson

Emerson KTM RICHARDS FIGURE R384 User manual

Emerson FISHER CV500 User manual

Emerson

Emerson FISHER CV500 User manual

Emerson Fisher D3 User manual

Emerson

Emerson Fisher D3 User manual

Emerson TARTARINI BM5A User manual

Emerson

Emerson TARTARINI BM5A User manual

Emerson Keystone 990 Technical Document

Emerson

Emerson Keystone 990 Technical Document

Emerson Fisher VS100 Series User manual

Emerson

Emerson Fisher VS100 Series User manual

Emerson KEYSTONE DUBEX User manual

Emerson

Emerson KEYSTONE DUBEX User manual

Emerson VS-FL Series User manual

Emerson

Emerson VS-FL Series User manual

Emerson Bettis XTE3000 User manual

Emerson

Emerson Bettis XTE3000 User manual

Emerson Fisher HP User manual

Emerson

Emerson Fisher HP User manual

Emerson NEOTECHA SNB Series User manual

Emerson

Emerson NEOTECHA SNB Series User manual

Emerson KEYSTONE FIGURE PCS17 Operation and maintenance manual

Emerson

Emerson KEYSTONE FIGURE PCS17 Operation and maintenance manual

Emerson EX4 User manual

Emerson

Emerson EX4 User manual

Emerson Sempell PSRV VS99 User manual

Emerson

Emerson Sempell PSRV VS99 User manual

Emerson Anderson Greenwood 93 Series User manual

Emerson

Emerson Anderson Greenwood 93 Series User manual

Emerson AVENTICS User guide

Emerson

Emerson AVENTICS User guide

Emerson K-BALL F110 Quick guide

Emerson

Emerson K-BALL F110 Quick guide

Emerson Fisher D3 User manual

Emerson

Emerson Fisher D3 User manual

Emerson SI-PROFIBUS User manual

Emerson

Emerson SI-PROFIBUS User manual

Emerson Fisher NPS 8 CHP User manual

Emerson

Emerson Fisher NPS 8 CHP User manual

Emerson CSI 6500 User manual

Emerson

Emerson CSI 6500 User manual

Emerson SAPAG User manual

Emerson

Emerson SAPAG User manual

Emerson TESCOM 64-2600 Series User manual

Emerson

Emerson TESCOM 64-2600 Series User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

IM-IND-553130-RevAA
Installation & Maintenance Instructions
3–WAY REDUNDANT DUAL SOLENOID–OPERATED PILOT VALVES
NORMALLY CLOSED AND NORMALLY OPEN OPERATION
BRASS AND/OR STAINLESS STEEL CONSTRUCTION
1/4” NPT – INSTRUMENT AIR SERVICE
SERIES
8323G0XX
8323G3XX
Page 1 of 4 E316582 - 08/2021 All Rights Reserved. IM-IND-553130-RevAA
No. 57, Kundrathur Main Rd., Gerugambakkam, Chennai - 6000128, India www.emerson.com
NOTICE: See separate solenoid installation and
maintenance instructions for information on: Wiring,
Solenoid Temperature, Causes of Improper Operation or
Solenoid Replacement.
DESCRIPTION
Series 8323G0XX, and 8323G3XX are 3-way redundant dual
solenoid-operated pilot valves designed for instrument air
service. Valves are normally closed or normally open depending
upon requirements.
Series 8323G0XX valves are supplied with a general purpose or
a explosionproof/watertight solenoid enclosures.
Series 8323G3XX valves are provided with low power general
purpose solenoid enclosures.
Operation Identification Chart
(Operation vs Catalog Number)
Operation Catalog Number / Construction
Normally Closed
(See Note)
8323G051 / Brass
8323G052 / Stainless Steel
8232G351 / Brass
8323G352 / Stainless Steel
Normally Open
(See Note)
8323G053 / Stainless Steel
8323G353 / Stainless Steel
NOTE: Normally closed pilot valves are used on ASCO no-
voltage release manual reset valves; normally open pilot valves
are used on trip shut-off manual-reset valves.
OPERATION
Normally Closed (Pressure at Port 3)
Both Solenoids De-energized: Flow is from Port 1 to Pilot
Exhaust.
Either or Both Solenoids Energized: Flow is from Port 3 to
Port 1.
Normally Open (Pressure at Solenoid Pilot)
Both Solenoids De-energized: Flow is from Pilot Press to Port
1.
Either or Both Solenoids Energized: Flow is from Port 1 to
Port 3.
INSTALLATION
Check nameplate for correct catalog number, pressure, voltage,
frequency, and service. Never apply incompatible fluids or
exceed pressure rating of the valve. Installation and valve
maintenance to be performed by qualified personnel.
Future Service Considerations
Provision should be made for performing seat leakage, external
leakage, and operational tests on the valve with a non-hazardous,
non-combustible fluid after disassembly and reassembly.
Temperature Limitations
For valve fluid and ambient temperature ranges, refer to chart
below. Check catalog number on nameplate.
Catalog Number Fluid & Ambient Temperature Range
8323G051
8323G052
8323G053
AC Service
32 °F (0 °C) to 125 °F (52 °C)
DC Service
32 °F (0 °C) to 104 °F (40 °C)
8323G351
8323G352
8323G353
-40 °F (-40 °C) to 140 °F (60 °C)
Positioning
Valve may be mounted in any position.
Mounting
Refer to Figure l, for valve body mounting dimensions.
Page 2 of 4 All Rights Reserved. IM-IND-553130-RevAA
No. 57, Kundrathur Main Rd., Gerugambakkam, Chennai - 6000128, India www.emerson.com
Figure 1. Valve Body Mounting Dimensions.
Piping
Debrisentering1/8"or1/4"NPTconnection
at top of solenoid may cause valve to malfunction. Use a
mu󰀪er to vent to atmosphere or connect to main exhaust
system if the air or inert gas cannot be exhausted directly
to the atmosphere.
Connect piping or tubing to valve according to markings on
valve body. Refer to flow diagrams in OPERATION section.
To avoid damage or accidental
disengagement of cartridge assembly from valve body,
hold cartridge assembly securely by wrenching ats when
installing or removing mu󰀪er or piping at top of solenoid.
Apply pipe compound sparingly to male pipe threads only. If
applied to valve threads, the compound may enter the valve
and cause operational difficulty. Avoid pipe strain by properly
supporting and aligning piping. When tightening the pipe, do
not use valve or solenoid as a lever. Locate wrenches applied to
valve body or piping as close as possible to connection point.
These solenoid valves are intended for
use on clean dry air or inert gas, ltered to 50 micrometres
or better. The dew point of the media should be at least 10
°C (18 °F) below the minimum temperature to which any
portion of the clean air/inert gas system could be exposed
to prevent freezing. If lubricated air is used, the lubricants
must be compatible with Buna N elastomers. Diester
oils may cause operational problems. Instrument air in
compliance with ANSI/I SA Standard S7.3-1975 (R1981)
exceeds the above requirements and is, therefore, an
acceptable media for these valves.
MAINTENANCE
To prevent the possibility of death,
serious injury or property damage, turn· o󰀨 electrical
power, depressurize valve, and vent uid to a safe area
before servicing the valve .
NOTE: It is not necessary to remove the valve from the pipeline
for repairs. However, piping or tubing must be removed from
pilot exhaust on top of the solenoid if present. See Piping section.
Cleaning
All solenoid valves should be cleaned periodically. The time
between cleanings will vary depending on the medium and
service conditions. In general, if the voltage to the coil is
correct, sluggish valve operation, excessive noise or leakage
will indicate that cleaning is required. In the extreme case, faulty
valve operation will occur and the valve may fail to shift. Clean
filter when cleaning the valve.
Preventive Maintenance
• Keep the medium flowing through the valve as free from
dirt and foreign material as possible.
• Periodic exercise of the valve should be considered
if ambient or fluid conditions are such that corrosion,
elastomer degradation, fluid contamination build up or
other conditions that could impede solenoid valve shifting
CAUTION
CAUTION
CAUTION
WARNING
are possible. In many cases, solenoid valves are periodically
exercised during normal system use or as part of routine
maintenance or surveillance activities and no additional
exercise is necessary. The actual frequency of exercise
necessary will depend on specific operating conditions.
A successful operating history is the best indication of a
proper interval between exercise cycles.
• Depending on the medium and service conditions, periodic
inspection of internal valve parts for damage or excessive
wear is recommended. Thoroughly clean all parts. If parts
are worn or damaged, install a complete ASCO Rebuild Kit.
Causes of Improper Operation
• Incorrect Pressure: Check valve pressure. Pressure to
valve must be within range specified on nameplate.
• Excessive Leakage: Disassemble valve and clean all
parts. If parts are worn or damaged, install a complete
ASCO Rebuild Kit.
Valve Disassembly
1. Disassemble valve in an orderly fashion using exploded
view for identification and placement of parts.
2. Disconnect tubing from valve body and top of solenoid
"A". Then remove tube fitting on adapter with tube fitting
from solenoid "A".
3. Where applicable; remove piping from cartridge assembly
at the top of solenoid ''B". Hold cartridge assembly securely
by wrenching flats, when removing piping.
Notice: Internal parts on solenoid "A" and "B" sides are identical.
4. Remove solenoid, see separate instructions.
5. For low power or intrinsically safe constructions, unscrew
cartridge assembly from valve body. Then remove cartridge
gasket from valve body and orifice gasket from recess in
base of cartridge assembly.
6. For standard construction, unscrew solenoid base sub-
assembly and remove plugnut gasket, solenoid base gasket
and core assembly with core spring and core guide.
7. All parts are now accessible for cleaning or replacement.
If parts are worn or damaged, install a complete
ASCO Rebuild Kit.
Valve Reassembly
1. Lubricate all gaskets with DOW CORNING®200 Fluid
lubricant or an equivalent high-grade silicone fluid lubricant.
2. Proceed as follows:
• For standard construction
A. Install plugnut gasket on solenoid base sub-assembly
and solenoid base gasket in valve body.
B. Install core assembly with core spring and core
guide into solenoid base sub-assembly.
C. Hand thread solenoid base sub-assembly into valve
body. Torque solenoid base sub-assembly to 175 ±
25 in-lbs [19,8 ± 2,8 Nm].
• For Low Power/ or Intrinsically Safe Construction
A. Position cartridge gasket in valve body.
B. Install orifice gasket in recess in base of
cartridge assembly.
C. Hand thread cartridge assembly with orifice gasket
into valve body. Then torque cartridge assembly to
175 ± 25 in-lbs [19,8 ± 2,8 Nm].
3. Install solenoids A and B, see separate instructions.
4. As required, make up tubing and piping to valve body and
top of solenoids A and B.
5. Make electrical connection to solenoid A and B.
To prevent the possibility of death,
serious injury or property damage, check valve for proper
operation before returning to service. Also perform internal
seat and external leakage tests with a non-hazardous, non-
combustible uid.
6. Restore line pressure and electrical power supply to valve.
7. After maintenance is completed, operate the valve a few
times to be sure of proper operation.
WARNING
Page 3 of 4 All Rights Reserved. IM-IND-553130-RevAA
No. 57, Kundrathur Main Rd., Gerugambakkam, Chennai - 6000128, India www.emerson.com
ORDERING I~FORMATION
FOR ASCO REBUILD KITS
Parts marked with an asterisk(*) in the exploded view are
supplied in Rebuild Kits. When Ordering Rebuild Kits for
ASCO valves, order the Rebuild Kit number stamped on the
valve nameplate. If the number of the kit is not visible, order by
indicating the number of kits required, and the Catalog Number
and Serial Number of the valve(s) for which they are intended.
Part Name Torques Values
In-Lbs
Torque Value
Nm
Cartridge Assembly
or Solenoid Base
Sub-Assembly
175 ± 25 19,8 ± 2,8
Torque Chart
Figure 2. Redundant Pilot Operator Assembly - Series 8323G051 and 8323G052
Figure 3. Redundant Pilot Operator Assembly - Series 8323G053
Figure 4. Redundant Pilot Operator Assembly - Series 8323G351 and 8323G352
Page 4 of 4 All Rights Reserved. IM-IND-553130-RevAA
No. 57, Kundrathur Main Rd., Gerugambakkam, Chennai - 6000128, India www.emerson.com
Figure 5. Redundant Pilot Operator Assembly - Series 8323G353