SIL Safety Manual
SM-025-GVO Rev. 0
 
November 2017
9
Section 5: Service Condition Limitations 
Service Condition Limitations
Section 5: Service Condition Limitations 
 (limitation of use)
The designer of an SIF must check that the product is rated for use within the expected 
application limits. The operating conditions limits strongly depend on the actuator type and 
on its construction materials.
Operating pressure values are dened for each actuator.
Temperature limits are the following:
• Standard ambient temperature range: -30°C to +100°C
• Extended ambient temperature range: -60°C to +200°C (special versions)
Supply medium: instrument air, nitrogen or sweet gas (sour gas special version is available).
If GVO-CLP-SR/FS actuator is intended to be used outside the application limits or with 
incompatible materials, the reliability data provided in the present document are invalid.
• The actual environmental conditions are included on the actuator nameplate
• The chose values are valid for the lifetime specied in Section 6.
• Manual override
Normally, the GVO-CLP-SR/FS actuators can  be tted with  one of the  following types of 
manual overrides:
• MHW Manual Hand-wheel mounted on the end ange of the pneumatic cylinder
• MHP Manual Hydraulic override including an additional hydraulic cylinder with 
manual pump and distributor
With reference GVO-CLP-SR/FS actuator, the mechanical manual override can be done with 
three conguration depending of the actuator size:
The use of a manual override is not recommended in a SIL classied application, as it results 
in a bypass of the safety function.
In case the manual override is used, the following requirements must be fulllled, or the 
Functional Safety Certication will become invalid:
1. The users authorized to operate on the actuator shall be skilled personnel;
2. The maximum duration of bypass shall be dened (responsibility of the nal user).
3. If necessary, compensatory measures to allow the safe operation of the process 
shall be dened (responsibility of the nal user).
4. Before selecting remote operating mode control of actuator, the manual override 
must be disengaged according to IOM Manual. The position selected 
(remote/automatic control or local / manual control) can be achieved with a 
specic technical solution that does not allow to reach an intermediate position 
lever’s and avoids unintentional activation. 
5. The engagement of the manual override shall be signalled, at least locally, 
according to IOM Manual. As optional request from nal user, to determine if the 
manual override is engaged, an electrical signal using contact switching can be 
provided to communicate the status to the control room.