EC2-311_65081_EN_R08.doc Replacement for Rev.:06 3 / 4 PCN: 864 911 20.03.2008 
 
 
EC2-311 Display Case and Coldroom Controller 
Operating Instructions GB 
List Of Parameters 
 
/ DISPLAY PARAMETERS Min Max Unit Def. Custom
/1 Value to show 0 9 - 0 
 0 = Thermostat control temperature with Temp. alignment °C 
1 = Air-in temperature °C 
2 = Air-out temperature °C 
3 = Alarm temperature °C 
4 = Defrost termination temperature °C 
5 = Coil-in temperature °C 
6 = Coil-out temperature °C 
7 = Calculated superheat °K 
8 = Valve opening in % 
9 = Displays defrost status 
 
/2 Alarm suppression 0= off, 1 = on 0 1 - 0 
/5 Temperature Unit 0 = °C, 1 = °F 0 1 - 0 
/6 Decimal point 0 = yes, 1 = no 0 1 - 0 
/7 Display during defrost 0 2 - 0 
 0 = dF (= defrost mode); 1 = dF + defrost termination temp. 
 2 = dF + control temperature 
 
/C Temperature alignment for /1=0 - 20 20 K 0.0 
A ALARM-PARAMETERS 
A0 Mean factor alarm temperature 0 100 % 100 
A1 Low temp alarm delay 0 180 min 5 
A2 High temp alarm delay 0 180 min 5 
A3 Alarm delay after defrost 0 180 min 10 
AH High temp alarm limit AL 70 °C / K 40 
AL Low temp alarm limit -55 AH °C / K -50 
At Alarm limit type 0 1 - 0 
 0=absolute temperatures °C; 1= relative temperatures K to setpoint 
r THERMOSTAT-PARAMETERS 
r1 Min setpoint -50 r2 °C - 50 
r2 Setpoint max r1 + 60 °C 40 
r3 Day/night control 0 = off, 1 = on 0 1 - 1 
r4 Thermostat mode 0 4 - 1 
 0 = off, no thermostat function, continues cooling air in sensor 
monitoring off, no temp. alarms generated 
1 = cooling, deadband control 
cut in = set-point + difference 
cut out = set-point 
2 = cooling, modulating thermostat 
cut in = set-point 
cut out = set-point – difference /2 
3 = heating, deadband control 
cut in = set-point – difference 
cut out = set-point 
4 = on, external control using nvi Valve via SNMP. Air in and air 
out sensor monitoring off. Temp. alarms will be generated 
 
r6 Setpoint night r1 r2 °C 4.0 
r7 Differential night 0.1 20.0 K 2.0 
r8 Mean factor, day operation 0 100 % 100 
r9 Mean factor, night operation 0 100 % 50 
rd Differential day 0.1 20.0 K 2.0 
St Setpoint day r1 r2 °C 2.0 
d DEFROST PARAMETERS 
d0 Defrost mode 0 2 - 1 
 0 = natural defrost, defrost heater not activated 
pulsed defrost not possible 
1 = forced defrost, defrost heater activated, pulsed 
defrost possible 
2 = forced defrost, defrost heater activated, pulsed defrost possible, 
defrost termination using nviStartUp via SNMP 
 
d1 Termination by: 0 3 - 0 
 0 = termination by temperature, 
termination by time will generate an alarm 
1 = termination by time, 
termination by temperature will generate an alarm 
2 = first, what ever comes first time or temperature, no alarm 
3 = last, by time and temperature, no alarm 
 
d2 Defrost termination sensor 0 1 - 1 
 0 = Dedicated defrost sensor must be installed 
1 = Air-out sensor used for defrost termination 
 
 
 Min Max Unit Def. Custom
d3 Pulsed defrost 0 1 - 0 
 0 = off, no pulsed defrost, heaters switched off at defrost termin-
ation temperature dt or max. time dP whatever is selected 
1 = on, pulsed defrost, dd and dH in use, heaters are switched off at 
dH and switched on again at dH – dd 
 
d4 Defrost at startup 0 = no, 1 = yes 0 1 - 0 
d5 Delay power up defrost 0 180 min 0 
d6 Pump down delay 0 180 sec 0 
 Compressor will run during pump down delay while valve is closed 
d7 Drain delay 0 15 min 2 
d8 Injection delay 0 180 sec 0 
 Valve is open during injection delay while compressor is not running 
d9 Demand defrost mode 
0 = off, 1 = on, 
2 = on together with timed defrost 
0 2 - 0 
dd Pulsed defrost differential 1 20 K 2 
dH Pulsed defrost setpoint -40 dt °C 5 
dt Defrost termination temperature -40 90 °C 8 
dP Max defrost duration 0 180 min 30 
dI Defrost interval 0 192 h 8 
du Start up delay after synch 0 180 min 30 
F FAN-PARAMETERS 
F1 Fan startup by: 0 = on 0 4 - 0 
 1 = delayed by time Fd, error on temperature 
2 = by temperature Ft, error on time 
3 = first, whatever comes first time or temperature, no alarm 
4= last, time and temperature must come, no alarm 
 
F2 During no cooling 0 3 - 0 
 0 = on; 1 = off; 2 = delayed by F4; 3 = off, when door open 
F3 During defrost 0 = on, 1 = off 0 1 - 0 
F4 Stop delay time 0 30 min 0 
F5 During cleaning 0 = off, 1 = on 0 1 - 0 
Fd Fan delay after defrost 0 30 min 0 
Ft On temp after defrost -40 40 °C 0 
C COMPRESSOR-PARAMETERS 
C0 Delay first start after power up 0 15 min 0 
C1 Cycle time 0 15 min 0 
C2 Min stop time it 0 15 min 0 
C3 Min run time 0 15 min 0 
u SUPERHEAT PARAMETERS 
u0 Refrigerant 0 = R22, 1 = R134a, 0 7 - 3 
 2 = R507; 3 = R404A; 4 = R407C; 5 = R410A; 6 = R124; 7 = R744 
u1 Correction glide / dp 
Glide = positive values 
Pressure drop = negative values 
-20.0 20.0 K 0.0 
u2 MOP control 
0 = MOP off, 1 = MOP on 
0 1 - 0 
u3 MOP temperature -40 40 °C 0 
u4 Superheat mode 0 = off 
1 = fixed superheat 
2 = adaptive superheat 
0 2 - 1 
u5 Superheat init setpoint u6 u7 K 6 
u6 Superheat setpoint min 3 u7 K 3 
u7 Superheat setpoint max u6 20 K 15 
uu Start opening 25 75 % 30 
H OTHER PARAMETERS 
H2 Display access 0 4 - 3 
 0 = all disabled (Caution, access to controller only via LON 
network possible) 
1 = Keyboard enabled 
2 = IR remote control enabled 
3 = Keyboard and IR remote control; Temporary data display and 
manual defrost enabled. 
4 = Keyboard and IR remote control; Temporary data display 
disabled. Control setpoint with SEL key and manual defrost 
enabled. 
 
H3 IR access code 0 199 - 0 
H5 Password 0 199 - 12