Installation 
Only qualied personnel should install or 
service a regulator. Regulators should 
be installed, operated, and maintained 
in accordance with international and 
applicable codes and regulations, and 
Fisher instructions. 
If the regulator vents uid or a leak 
develops in the system, it indicates that 
service is required. Failure to take the 
regulator out of service immediately may 
create a hazardous condition. 
Personal injury, equipment damage, or 
leakage due to escaping uid or bursting of 
pressure-containing parts may result if this 
regulator is overpressured or is installed 
where service conditions could exceed the 
limits given in the Specications section, 
or where conditions exceed any ratings of 
the adjacent piping or piping connections. 
To avoid such injury or damage, provide 
pressure-relieving or pressure-limiting 
devices (as required by the appropriate 
code, regulation, or standard) to prevent 
service conditions from exceeding limits. 
Additionally, physical damage to the 
regulator could result in personal injury 
and property damage due to escaping 
uid. To avoid such injury and damage, 
install the regulator in a safe location. 
Clean out all pipelines before installation of the regulator 
and check to be sure the regulator has not been damaged 
or has collected foreign material during shipping. Use 
suitable line gaskets and approved piping and bolting 
practices. Install the regulator in any position desired. 
However, to ensure self-draining (from outlet to inlet) the 
regulator should be installed with the spring case in the 
upright vertical position.  The arrow on the body indicates 
ow direction.
Note 
It is important that the regulator be 
installed so that the vent hole in the 
spring case is unobstructed at all times. 
Overpressure Protection 
The recommended pressure limitations are stamped 
on the regulator nameplate. Some type of overpressure 
protection is needed if the actual inlet pressure 
exceeds the maximum operating outlet pressure rating. 
Overpressure protection should also be provided if the 
regulator inlet pressure is greater than the safe working 
pressure of the downstream equipment. 
Regulator operation below the maximum pressure 
limitations does not preclude the possibility of damage 
from external sources or debris in the line. The 
regulator should be inspected for damage after any 
overpressure condition. 
Startup
The regulator is factory set at approximately the 
midpoint of the spring range or the pressure requested, 
so an initial adjustment may be required to give the 
desired results. Make sure the CIP/SIP Pin (key 30, 
Figure 1) is not installed in the spring case. With 
proper installation completed and relief valves properly 
adjusted, slowly open the upstream and downstream 
shutoff valves.
The CIP/SIP pin must be removed before 
regulator is placed in operation. The 
pin will inhibit the proper operation and 
function of the regulator and result in 
overpressure of the downstream system.
Adjustment 
To change the outlet pressure, remove the closing cap 
or loosen the locknut and turn the adjusting screw or 
handwheel clockwise to increase outlet pressure or 
counterclockwise to decrease pressure. Monitor the outlet 
pressure with a test gauge during the adjustment. Replace 
the closing cap or tighten the locknut to maintain the 
desired setting.
Pressure Loaded Construction
The spring case can be pressure loaded to adjust outlet 
pressure. An optional tapped spring case, guide ring seal 
and sealing washer on the adjusting screw must be used 
for these applications. The loading pressure is connected 
to the 1/4-inch NPT connection in the spring case 
allowing registration on the spring side of the diaphragm. 
Adjusting loading pressure will proportionally change the 
outlet pressure setting of the regulator. A small amount of 
mechanical spring load, in addition to the pressure load, is 
recommended. Regulator set pressure achieved from the 
combination of spring load and pressure load should not 
exceed the outlet pressure ranges listed on page 1.
Taking Out of Service (Shutdown) 
To avoid personal injury resulting from 
sudden release of pressure, isolate 
the regulator from all pressure before 
attempting disassembly. Relieve all spring 
compression and isolate regulator from the 
pressurized system prior to removing the 
clamp (key 15, Figure 1).