EC3-932_65149_EN_R02.doc Replacement for R01 3 / 4 PCN: 865 874 22.09.2009
EC3-932 Rack and Condenser Controller and ECD-000 Display Unit
Operating Instructions GB
List Of Parameters
/ DISPLAY PARAMETERS Min Max Unit Def. Custom
/1 Value to show 0 4 - 0
0 = Compressors and fans states (controller 1 and controller 2)
1 = Suction pressure (bar)
2 = Saturation temperature (°C) calculated from suction pressure
3 = Condensing pressure (bar)
4 = Saturation temperature (°C) calculated from discharge pressure
5 = Digital Scroll capacity (%); 6 = Variable fan speed capacity %
Controller C1 (Rack Controller)
P SET-POINT PARAMETERS (C1)
P0 Suction pressure set point -1 50 bar 3.0
P1 Suction band 0 50 bar 2.0
P3 Fast recovery from low pressure -9.9 50 bar -9.9
P4 Suction shift (0=disabled, 1=enabled) 0 1 - 0
P5 Suction shift max 0 3.0 bar 3.0
P8 High discharge pressure recovery -9.9 50 bar 50.0
P9 Discharge recovery step 0 5.0 bar 1.0
t TIME PARAMETERS (C1)
t0 Integration time 30 99 10 sec* 60
t1 Time delay before adding capacity 0 99 10 sec* 6
t2 Time delay before removing capacity 0 99 10 sec* 0.2
t3 Compressor min on time 0 99 10 sec* 6
t4 Compressor min off time 0 99 10 sec* 6
t5 Maximum compressor switching
(0=number of switching unrestricted)
0 199 1/hr 0
A ALARM-PARAMETERS (C1)
A0 Alarm delay LP 0 99 10 sec* 0
A1 Alarm delay HP 0 99 10 sec* 0
A2 Suction alarm min. limit -1.0 50 bar 1.0
A3 Suction alarm max. limit -1.0 50 bar 6.0
A4 Alarm delay suction min. limit 0 99 10 sec* 0
A5 Alarm delay suction max. limit 0 99 10 sec* 0
A6 Maximum discharge temperature 50 150 °C 130
A7 Maximum discharge temperaturedelay 0 99 10 sec* 3
A8 Alarm delay serial alarm comp. 0 99 10 sec* 0
A9 Compressor service interval 0 99 10,000hr** 0
u STEP ENABLE PARAMETERS (C1)
u0 Compressor service interval reset 0 5 - 0
0 = do nothing
1 = reset operating time compr. 1
2 = reset operating time compr. 2
3 = reset operating time compr. 3
4 = reset operating time compr. 4
5 = reset op. time all compressors
u1 Compressor 1: 0=disable, 1=enable 0 1 flag 1
u2 Compressor 2 enable ( - " - ) 0 1 flag 1
u3 Compressor 3 enable ( - " - ) 0 1 flag 1
u4 Compressor 4 enable ( - " - ) 0 1 flag 1
c APPLICATION PARAMETERS (C1)
c1 Number of compressors 1 4 - 4
c3 Compr. control mode (0 = P mode, 0 3 - 2
1 = PI mode, 2 = dead band mode 3 = binary mode)
c4 Compressor 1 control mode 0 2 - 2
0 = in standard control loop 1 = act as base load compressor
2 = act as modulating capacity; function defined by parameter F5
c5 Compressor rotation 0 1 flag 1
0 = FILO logic (First In, Last Out) 1 = FIFO logic (First In, First Out)
c6 Sensor fail 0 4 - 0
(number of compressors in case of sensor failure)
h0 Discharge pressure sensor
0 = not available; 1 = available
0 1 flag 1
r SENSOR PARAMETERS (C1)
r0 Suction sensor 0% -1.0 50 bar -0.8
r1 Suction sensor 100% -1.0 50 bar 7
r2 Suction sensor offset -1.0 1.0 bar 0.0
r3 Refrigerant 0 7 - 3
0 = R 22
1 = R 134a
2 = R 507
3 = R 404A
4 = R 407C
5 = R 410A
6 = R 124
7 = R 744
* Resolution = 10 sec, on the local display. Example a value 2 means 20 sec.
** Resolution = 10,000 hrs. on the local display. Example a value 2 means 2.000 hours.
F MODULATING PARAMETERS (C1)
Min Max Unit Def. Custom
F2 Minimum output value (F5 = 0 or 1) 10 100 % 10
F3 Maximum output value (F5 = 0 or 1) 10 100 % 100
F3 PWM rate if F5 = 2 (Digital Scroll) 10 20 sec 10
F5 Analogue output mode for Comp. 1
0 or 1 = 0 … 10V; 2 = PWM (digital)
0 2 - 2
Controller C2 (Condenser Controller)
P SET-POINT PARAMETERS (C2)
P0 Condensing pressure set point -1 50 bar 14.0
P1 Cond. pressure band 0 50 bar 4.0
P2 Condensing pressure set point 2 -1 50 bar 14.0
P3 Condensing recovery min -9.9 50.0 bar -9.9
P4 Condensing shift (0 = off, 1 = on) 0 1 - 0
P5 Condensing shift max 0.0 3.0 bar 3.0
P6 Condensing shift temp min -50 50 °C 30°C
P7 Condensing shift temp max -50 50 °C 15°C
P8 Condensing recovery max -9.9 50 bar 50
t TIME PARAMETERS (C2)
t0 Integration time 30 99 10 sec* 60
t1 Time delay before adding capacity 0 99 10 sec* 3
t2 Time delay before removing capacity 0 99 10 sec* 3
A ALARM-PARAMETERS (C2)
A1 Alarm delay HP 0 99 10 sec* 0
A2 Condensing alarm limit min -1.0 50 bar 10
A3 Condensing alarm limit max -1.0 50 bar 27
A4 Alarm delay condensing limit min 0 99 10 sec* 0
A5 Alarm delay condensing limit max 0 99 10 sec* 0
A8 Alarm delay serial alarm fan 0 99 10 sec* 0
A9 Service interval 0 99
1,000 hr** 0
u STEP ENABLE PARAMETERS (C2)
u0 Fan service interval reset 0 4 - 0
0 = do nothing
1 = reset operating time fan 1
2 = reset operating time fan 2
3 = reset operating time fan 3
4 = reset op. time all fans
u1 Fan 1 enable (0=disable, 1=enable) 0 1 flag 1
u2 Fan 2 enable (0=disable, 1=enable) 0 1 flag 1
u3 Fan 3 enable (0=disable, 1=enable) 0 1 flag 1
c APPLICATION PARAMETERS (C2)
c1 Number of fans 1 3 - 3
c3 Control mode (0 = P mode,
1 = PI mode, 2 = dead band mode)
0 2 - 2
c4 First fan control mode 0 2 - 0
0 = in standard control loop,
1 = act as base load fan,
2 = act as modulating capacity (0…10V
for inverter command or TRIAC output)
c5 Fan rotation 0 1 flag 0
0 = FILO logic (First In, Last Out) 1 = FIFO logic (First In, First Out)
c6 Sensor fail (nr. of fans in case of sens fail) 0 3 - 0
r SENSOR PARAMETERS (C2)
r0 Condensing sensor 0% -1.0 50 bar 0.0
r1 Condensing sensor 100% -1.0 50 bar 30
r2 Condensing sensor offset -1.0 1.0 bar 0.0
F MODULATING PARAMETERS (C2)
F2 Fan 1 min speed (if controlled) 0 100 % 0
F3 Fan 1 max speed (if controlled) 0 100 % 100
F4 Fan 1 at min: (0=off; 1 =min speed) 0 1 flag 0
F7 Output mode for modulating fan 1: 0 1 flag 0
0 = 0 – 10V analogue output; 1 = Phase cutting with Triac
H OTHER PARAMETERS
H2 ECD Display access 0 3 - 3
0 = all disabled (Caution, access
to controller only via TCP/IP
network possible)
1 = Keyboard enabled
2 = IR remote control enabled
3 = Keyboard and IR remote
control enabled
H3 IR access code 0 199 - 0
H5 Password 0 199 - 12