Document Part # 026-4413 Rev 2 Page 1 of 4
©2018 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
The Modular Refrigeration Leak Detection Sensor is
Emerson’s state-of-the-art infrared refrigerant gas
detector that can detect a wide range of gases. The
MRLDS-250 can be used on a stand-alone basis or
integrated into supervisory controls. The MRLDS-250
can be used in locations that require continuous
monitoring and to add gas detection solutions to an
existing system.
The MRLDS-250 is available in two versions:
• The broadband gas detector is used as a general
purpose gross leak detector and is factory tested and
certified to +/- 35% accuracy.
•The gas specific versions come factory certified and
calibrated with +/- 3% accuracy to the target refrigerant
when there is a need for more accurate detection.
For complete part number and installation information, see
the full MRLDS-250 manual (P/N 026-1315).
MRLDS-250 Installation
Mounting the MRLDS-250
1. To open the housing as received, use a flat blade
screwdriver and depress the top latch. While pushing
the latch, grasp the back edge of the housing near the
latch and pull the back away.
2. Position the base to the pre-determined mounting
location.
3. For Wall Mount, attach the MRLDS-250 base to the
mounting surface using two #6 screws (provided)
through two of the seven mounting holes
(see Figure 2). For Junction Box Mount, attach the
MRLDS-250 base to the junction box through the two
junction box holes.
Figure 1 - MRLDS-250 Components
Figure 2 - Front and Back of the MRLDS-250 Base
Quick Setup Guide
MRLDS-250
Document Part # 026-4413 Rev 2 Page 2 of 4
©2018 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
Wiring and Configuration
Either 24VAC or 24VDC may be used to power the
MRLDS-250. Connect wiring to the appropriate terminal
locations. Use two wires, between 14 and 22 AWG.
Refer to Figure 3 for AC wiring (left) or DC wiring (right):
WARNING: The MRLDS-250 must be powered by:
• A suitable UL 60950/CSA certified power supply
that is isolated from line voltage by double
insulation.
• An appropriately rated UL listed/CA Class 2
Transformer; a 10VA Transformer is
recommended.
• For multiple devices cascaded, a 50VA Class 2
Transformer is recommended.
The MRLDS-250 provides an analog output signal that is
proportional to the level of gas detected. Connect two
18 to 20 AWG wires to terminal block positions 5and 6
(see Figure 5A), noting ground and signal polarity.
Make relay connections (NO, NC, or both) using 18 to 20
AWG wires to terminal block positions 10, 11, and 12
(see Figure 5B), noting normally open, normally closed,
and common connectors.
NOTE: For MODBUS network communications wiring,
use only 18-24 AWG shielded twisted pair wire with 120
ohm characteristic impedance.
Figure 3 - Supply and Power Wiring Options
Figure 4 - Power Wiring of a Device Network
Figure 5A - Analog Output Wiring
Figure 5B - Sample Relay Output Wiring
Figure 6 - MODBUS Network Communication Wiring
Document Part # 026-4413 Rev 2 Page 3 of 4
©2018 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
NOTE: Be sure to enable the termination resister on the
device at each end of the network (see Figure 7):
Set Up Analog Output Type and Scaling
1. For Analog Output, look for P.-03 on the parameter list
then press the Enter button.
2. Set the desired output by pressing Up or Down
to select the type designated as follows:
• 00 Selects 0-5V
• 01 Selects 1-5V (Default)
• 02 Selects 0-10V
• 03 Selects 2-10V
• 04 Selects 4-20mA
3. Press the Enter button to save.
4. For Scaling, look for P.-16 on the parameter list then
press the Enter button.
5. This will allow you to select the full scale PPM value that
represents the maximum analog output (for example:
1000PPM = 5V when 1-5V output range was selected
for P.-03). Use Up or Down to adjust the value
and set it to 1000PPM.
6. Press the Enter button to save the setting.
MRLDS-250 Modbus Setup
Setting Up Modbus Address and Baud Rate
1. Press and hold the information button for five
seconds to activate the parameter list.
2. For the Address, look for P.-10 on the parameter list
then press the Enter button.
3. Set the desired address by pressing Up or Down
and press the Enter button to save.
4. For the Baud Rate, look for the P.-13 parameter then
press the Enter button.
5. Select 00 for 9600 Baud or 01 for 19200 Baud. Press
the Enter button to save.
How to Add an MRLDS-250 to the E2 Controller
1. MRLDS-250 is only native on E2 Enhanced Controllers
with firmware version 4.08F03; otherwise you need to
add a description file and license key.
2. Contact Customer Service to obtain a license key:
a. Phone Number: 770-425-2724 Option 4
b. Email: Solutions.CustomerService@Emerson.com
3. Add the description file using UltraSite.
4. Reboot the controller after the upload.
5. Load the license key on the E2 by logging in and then
press , ,.
6. Press F1 for ADD FEATURE and enter the License Key.
7. Add the MRLDS-250 by pressing , ,,to
access Connected I/O Boards and Controllers.
8. Press F2 twice to select C4: Third Party tab.
9. Scroll down to MGS250 and enter the quantity of
MRLDS-250 devices up to the maximum indicated.
10. Press the button to save.
11. Press , ,,for Network Summary or
+.
12. Scroll down to the MGS250 and press F4 for
COMMISSION.
13. Select the address the MRLDS-250 is set to and press
to confirm.
14. The MRLDS-250 should be Online on the E2 Network
Summary (press +).
How to Configure Alarm Setup on the E2
Controller
1. Press , and then select MGS250.
2. Press F5 for SETUP and F2 to select C2: Set Points.
3. Set the parameters depending on the System
Requirement and press the button to save.
Figure 7 - Termination Resister Setting
This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
Join Emerson Retail Solutions Technical Support on Facebook. http://on.fb.me/WUQRnt
For Technical Support call 770-425-2724 or email SolutionsTechSup@Emerson.com
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described
herein or their use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products
at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains
solely with the purchaser and end-user.
Document Part # 026-4413 Rev 2 Page 4 of 4
MRLDS to MultiFlex I/O
How to Set a MultiFlex Input Point
1. An input point on a MultiFlex board consists of two terminals. One of these terminals labeled as SIG reads the signal from
the sensor, while the other, labeled 0v is where the sensor ground wire is connected:
2. The Analog Output Signal (+) should go to (SIG) terminal of the MultiFlex board and the Ground (GND) should go to (0v)
terminal of the board.
3. The DIP switch setting of the MultiFlex board terminal for the MRLDS-250 should be in the OFF position
(see Figure 9) because it supplies its own voltage signal to the point:
How to Set the Input Type on the E2 Controller
1. Press , ,to go to the Input Status Screen.
2. Select the input point where the MRLDS-250 is connected, and press F1 for SETUP. Press for Analog.
3. Highlight Sensor Type and press F4 for LOOK UP. Select Linear and press to confirm.
4. Navigate down to Eng Units and press F4 for LOOK UP. Select PPM 33 and press to confirm.
5. Set the Low End Point and HighEnd Point equivalent to the range set on P-.03 for Analog Output.
6. Set the Low End EU and the High End EU equivalent to PPM Scaling set on P.-16.
7. For the Low End Limit, set it to -10% of Low End EU and for the HighEnd Limit, set it to +10% of
High End EU.
8. Press the button to save.
Figure 8 - MultiFlex Input Point
Figure 9 - MultiFlex Input Dip Switches

Other manuals for MRLDS-250

3

Other Emerson Security Sensor manuals

Emerson Net Safety JB Series User manual

Emerson

Emerson Net Safety JB Series User manual

Emerson Rosemount 975 Series User manual

Emerson

Emerson Rosemount 975 Series User manual

Emerson Rosemount 2160 User manual

Emerson

Emerson Rosemount 2160 User manual

Emerson Rosemount 2140 User manual

Emerson

Emerson Rosemount 2140 User manual

Emerson Rosemount 975 Use and care manual

Emerson

Emerson Rosemount 975 Use and care manual

Emerson White-Rodgers 902 User manual

Emerson

Emerson White-Rodgers 902 User manual

Emerson Rosemount 2160 User manual

Emerson

Emerson Rosemount 2160 User manual

Emerson REED Series User manual

Emerson

Emerson REED Series User manual

Emerson Net Safety Millennium User manual

Emerson

Emerson Net Safety Millennium User manual

Emerson Machinery Health AMS EZ 1000 User manual

Emerson

Emerson Machinery Health AMS EZ 1000 User manual

Emerson Machinery Health PR 9268 Series User manual

Emerson

Emerson Machinery Health PR 9268 Series User manual

Emerson Rosemount CT4215 User manual

Emerson

Emerson Rosemount CT4215 User manual

Emerson Rosemount 975 Series User manual

Emerson

Emerson Rosemount 975 Series User manual

Emerson Rosemount 226 User manual

Emerson

Emerson Rosemount 226 User manual

Emerson Mobrey Manual

Emerson

Emerson Mobrey Manual

Emerson CHD200G User manual

Emerson

Emerson CHD200G User manual

Emerson Rosemount 2160 User manual

Emerson

Emerson Rosemount 2160 User manual

Emerson Rosemount 2140 User manual

Emerson

Emerson Rosemount 2140 User manual

Emerson Rosemount 3900 User manual

Emerson

Emerson Rosemount 3900 User manual

Emerson Rosemount 975HR User manual

Emerson

Emerson Rosemount 975HR User manual

Emerson Machinery Health AMS EZ 1000 User manual

Emerson

Emerson Machinery Health AMS EZ 1000 User manual

Emerson Rosemount 2160 User manual

Emerson

Emerson Rosemount 2160 User manual

Emerson Rosemount 975 Series User manual

Emerson

Emerson Rosemount 975 Series User manual

Emerson GW-810-3760 User manual

Emerson

Emerson GW-810-3760 User manual

Popular Security Sensor manuals by other brands

Sensor Switch WSX Series instructions

Sensor Switch

Sensor Switch WSX Series instructions

Fly Sky FS-iBC01 manual

Fly Sky

Fly Sky FS-iBC01 manual

C.P. Electronics VITMR-MWS6-PRM Product guide

C.P. Electronics

C.P. Electronics VITMR-MWS6-PRM Product guide

Paradox PMD85 installation manual

Paradox

Paradox PMD85 installation manual

Abus Security-Center FU5130 installation guide

Abus

Abus Security-Center FU5130 installation guide

C.P. Electronics MWS1A-C-PRM-LV Product guide

C.P. Electronics

C.P. Electronics MWS1A-C-PRM-LV Product guide

DELTA PLUS ASCORD AN060 instructions

DELTA PLUS

DELTA PLUS ASCORD AN060 instructions

C & K Systems FG-1025Z installation instructions

C & K Systems

C & K Systems FG-1025Z installation instructions

C.P. Electronics MWS6-DD installation guide

C.P. Electronics

C.P. Electronics MWS6-DD installation guide

C.P. Electronics MWS3A-AT-DD installation guide

C.P. Electronics

C.P. Electronics MWS3A-AT-DD installation guide

HIK VISION DS-PD2-P25-W quick start guide

HIK VISION

HIK VISION DS-PD2-P25-W quick start guide

Elk Products ELK-319HRR Installation guidelines

Elk Products

Elk Products ELK-319HRR Installation guidelines

Vega VEGAPULS C 11 operating instructions

Vega

Vega VEGAPULS C 11 operating instructions

DigiSpec VMD-1001 Operation manual

DigiSpec

DigiSpec VMD-1001 Operation manual

GASSONIC Observer-i instruction manual

GASSONIC

GASSONIC Observer-i instruction manual

Honeywell NFPA 1951 User's information guide

Honeywell

Honeywell NFPA 1951 User's information guide

SICK WEU26-3 operating instructions

SICK

SICK WEU26-3 operating instructions

DELTA DORE TYXAL DOS installation guide

DELTA DORE

DELTA DORE TYXAL DOS installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.