Emerson MRLDS-250 User manual

Document Part # 026-4413 Rev 2 Page 1 of 4
©2018 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
The Modular Refrigeration Leak Detection Sensor is
Emerson’s state-of-the-art infrared refrigerant gas
detector that can detect a wide range of gases. The
MRLDS-250 can be used on a stand-alone basis or
integrated into supervisory controls. The MRLDS-250
can be used in locations that require continuous
monitoring and to add gas detection solutions to an
existing system.
The MRLDS-250 is available in two versions:
• The broadband gas detector is used as a general
purpose gross leak detector and is factory tested and
certified to +/- 35% accuracy.
•The gas specific versions come factory certified and
calibrated with +/- 3% accuracy to the target refrigerant
when there is a need for more accurate detection.
For complete part number and installation information, see
the full MRLDS-250 manual (P/N 026-1315).
MRLDS-250 Installation
Mounting the MRLDS-250
1. To open the housing as received, use a flat blade
screwdriver and depress the top latch. While pushing
the latch, grasp the back edge of the housing near the
latch and pull the back away.
2. Position the base to the pre-determined mounting
location.
3. For Wall Mount, attach the MRLDS-250 base to the
mounting surface using two #6 screws (provided)
through two of the seven mounting holes
(see Figure 2). For Junction Box Mount, attach the
MRLDS-250 base to the junction box through the two
junction box holes.
Figure 1 - MRLDS-250 Components
Figure 2 - Front and Back of the MRLDS-250 Base
Quick Setup Guide
MRLDS-250
Document Part # 026-4413 Rev 2 Page 2 of 4
©2018 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
Wiring and Configuration
Either 24VAC or 24VDC may be used to power the
MRLDS-250. Connect wiring to the appropriate terminal
locations. Use two wires, between 14 and 22 AWG.
Refer to Figure 3 for AC wiring (left) or DC wiring (right):
WARNING: The MRLDS-250 must be powered by:
• A suitable UL 60950/CSA certified power supply
that is isolated from line voltage by double
insulation.
• An appropriately rated UL listed/CA Class 2
Transformer; a 10VA Transformer is
recommended.
• For multiple devices cascaded, a 50VA Class 2
Transformer is recommended.
The MRLDS-250 provides an analog output signal that is
proportional to the level of gas detected. Connect two
18 to 20 AWG wires to terminal block positions 5and 6
(see Figure 5A), noting ground and signal polarity.
Make relay connections (NO, NC, or both) using 18 to 20
AWG wires to terminal block positions 10, 11, and 12
(see Figure 5B), noting normally open, normally closed,
and common connectors.
NOTE: For MODBUS network communications wiring,
use only 18-24 AWG shielded twisted pair wire with 120
ohm characteristic impedance.
Figure 3 - Supply and Power Wiring Options
Figure 4 - Power Wiring of a Device Network
Figure 5A - Analog Output Wiring
Figure 5B - Sample Relay Output Wiring
Figure 6 - MODBUS Network Communication Wiring
Document Part # 026-4413 Rev 2 Page 3 of 4
©2018 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
NOTE: Be sure to enable the termination resister on the
device at each end of the network (see Figure 7):
Set Up Analog Output Type and Scaling
1. For Analog Output, look for P.-03 on the parameter list
then press the Enter button.
2. Set the desired output by pressing Up or Down
to select the type designated as follows:
• 00 Selects 0-5V
• 01 Selects 1-5V (Default)
• 02 Selects 0-10V
• 03 Selects 2-10V
• 04 Selects 4-20mA
3. Press the Enter button to save.
4. For Scaling, look for P.-16 on the parameter list then
press the Enter button.
5. This will allow you to select the full scale PPM value that
represents the maximum analog output (for example:
1000PPM = 5V when 1-5V output range was selected
for P.-03). Use Up or Down to adjust the value
and set it to 1000PPM.
6. Press the Enter button to save the setting.
MRLDS-250 Modbus Setup
Setting Up Modbus Address and Baud Rate
1. Press and hold the information button for five
seconds to activate the parameter list.
2. For the Address, look for P.-10 on the parameter list
then press the Enter button.
3. Set the desired address by pressing Up or Down
and press the Enter button to save.
4. For the Baud Rate, look for the P.-13 parameter then
press the Enter button.
5. Select 00 for 9600 Baud or 01 for 19200 Baud. Press
the Enter button to save.
How to Add an MRLDS-250 to the E2 Controller
1. MRLDS-250 is only native on E2 Enhanced Controllers
with firmware version 4.08F03; otherwise you need to
add a description file and license key.
2. Contact Customer Service to obtain a license key:
a. Phone Number: 770-425-2724 Option 4
b. Email: Solutions.CustomerService@Emerson.com
3. Add the description file using UltraSite.
4. Reboot the controller after the upload.
5. Load the license key on the E2 by logging in and then
press , ,.
6. Press F1 for ADD FEATURE and enter the License Key.
7. Add the MRLDS-250 by pressing , ,,to
access Connected I/O Boards and Controllers.
8. Press F2 twice to select C4: Third Party tab.
9. Scroll down to MGS250 and enter the quantity of
MRLDS-250 devices up to the maximum indicated.
10. Press the button to save.
11. Press , ,,for Network Summary or
+.
12. Scroll down to the MGS250 and press F4 for
COMMISSION.
13. Select the address the MRLDS-250 is set to and press
to confirm.
14. The MRLDS-250 should be Online on the E2 Network
Summary (press +).
How to Configure Alarm Setup on the E2
Controller
1. Press , and then select MGS250.
2. Press F5 for SETUP and F2 to select C2: Set Points.
3. Set the parameters depending on the System
Requirement and press the button to save.
Figure 7 - Termination Resister Setting
This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
Join Emerson Retail Solutions Technical Support on Facebook. http://on.fb.me/WUQRnt
For Technical Support call 770-425-2724 or email SolutionsTechSup@Emerson.com
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described
herein or their use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products
at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains
solely with the purchaser and end-user.
Document Part # 026-4413 Rev 2 Page 4 of 4
MRLDS to MultiFlex I/O
How to Set a MultiFlex Input Point
1. An input point on a MultiFlex board consists of two terminals. One of these terminals labeled as SIG reads the signal from
the sensor, while the other, labeled 0v is where the sensor ground wire is connected:
2. The Analog Output Signal (+) should go to (SIG) terminal of the MultiFlex board and the Ground (GND) should go to (0v)
terminal of the board.
3. The DIP switch setting of the MultiFlex board terminal for the MRLDS-250 should be in the OFF position
(see Figure 9) because it supplies its own voltage signal to the point:
How to Set the Input Type on the E2 Controller
1. Press , ,to go to the Input Status Screen.
2. Select the input point where the MRLDS-250 is connected, and press F1 for SETUP. Press for Analog.
3. Highlight Sensor Type and press F4 for LOOK UP. Select Linear and press to confirm.
4. Navigate down to Eng Units and press F4 for LOOK UP. Select PPM 33 and press to confirm.
5. Set the Low End Point and HighEnd Point equivalent to the range set on P-.03 for Analog Output.
6. Set the Low End EU and the High End EU equivalent to PPM Scaling set on P.-16.
7. For the Low End Limit, set it to -10% of Low End EU and for the HighEnd Limit, set it to +10% of
High End EU.
8. Press the button to save.
Figure 8 - MultiFlex Input Point
Figure 9 - MultiFlex Input Dip Switches

Other manuals for MRLDS-250

3

Other Emerson Security Sensor manuals

Emerson Rosemount 2140 User manual

Emerson

Emerson Rosemount 2140 User manual

Emerson Rosemount 975 Series User manual

Emerson

Emerson Rosemount 975 Series User manual

Emerson Net Safety Millennium User manual

Emerson

Emerson Net Safety Millennium User manual

Emerson Net Safety JB Series User manual

Emerson

Emerson Net Safety JB Series User manual

Emerson Rosemount 396P User manual

Emerson

Emerson Rosemount 396P User manual

Emerson Machinery Health AMS EZ 1000 User manual

Emerson

Emerson Machinery Health AMS EZ 1000 User manual

Emerson Rosemount 2160 User manual

Emerson

Emerson Rosemount 2160 User manual

Emerson Rosemount 389 User manual

Emerson

Emerson Rosemount 389 User manual

Emerson Rosemount 975HR User manual

Emerson

Emerson Rosemount 975HR User manual

Emerson GDU-Incus User manual

Emerson

Emerson GDU-Incus User manual

Emerson Rosemount 2140 User manual

Emerson

Emerson Rosemount 2140 User manual

Emerson White-Rodgers 902 User manual

Emerson

Emerson White-Rodgers 902 User manual

Emerson ROSEMOUNT 242 User manual

Emerson

Emerson ROSEMOUNT 242 User manual

Emerson REED Series User manual

Emerson

Emerson REED Series User manual

Emerson Rosemount 2160 User manual

Emerson

Emerson Rosemount 2160 User manual

Emerson Rosemount 975 Use and care manual

Emerson

Emerson Rosemount 975 Use and care manual

Emerson F145RF-1600 User manual

Emerson

Emerson F145RF-1600 User manual

Emerson Rosemount 226 User manual

Emerson

Emerson Rosemount 226 User manual

Emerson Rosemount 2160 User manual

Emerson

Emerson Rosemount 2160 User manual

Emerson Dixell GDS41M Wiring diagram

Emerson

Emerson Dixell GDS41M Wiring diagram

Emerson Machinery Health AMS EZ 1000 User manual

Emerson

Emerson Machinery Health AMS EZ 1000 User manual

Emerson Machinery Health PR 9268 Series User manual

Emerson

Emerson Machinery Health PR 9268 Series User manual

Emerson Rosemount 975 User manual

Emerson

Emerson Rosemount 975 User manual

Emerson Rosemount 975MR User manual

Emerson

Emerson Rosemount 975MR User manual

Popular Security Sensor manuals by other brands

STEINEL Professional Series instructions

STEINEL

STEINEL Professional Series instructions

IGM Vega FD 330-4-1 user manual

IGM

IGM Vega FD 330-4-1 user manual

Siemens 7MH7701-0AA00-0A operating instructions

Siemens

Siemens 7MH7701-0AA00-0A operating instructions

VOLTCRAFT LSG-10 operating instructions

VOLTCRAFT

VOLTCRAFT LSG-10 operating instructions

IMMOOS SS1 oGB operating instructions

IMMOOS

IMMOOS SS1 oGB operating instructions

Sensear SM1P manual

Sensear

Sensear SM1P manual

Extech Instruments DV40 manual

Extech Instruments

Extech Instruments DV40 manual

Ametek Ortec radEAGLET-R Series user manual

Ametek

Ametek Ortec radEAGLET-R Series user manual

REED R9300 instruction manual

REED

REED R9300 instruction manual

GEV LAB 018709 operating instructions

GEV

GEV LAB 018709 operating instructions

TiTLEY Scientific Anabat Scout user manual

TiTLEY Scientific

TiTLEY Scientific Anabat Scout user manual

Inficon HLD6000 Translation of the original operating instructions

Inficon

Inficon HLD6000 Translation of the original operating instructions

Elektrotechnik Schabus SHT 5001 operating instructions

Elektrotechnik Schabus

Elektrotechnik Schabus SHT 5001 operating instructions

CARLO GAVAZZI Guardian 2 Original user manual

CARLO GAVAZZI

CARLO GAVAZZI Guardian 2 Original user manual

3M Macurco CM-E1 User instructions

3M

3M Macurco CM-E1 User instructions

Argus Security SG200 quick start guide

Argus Security

Argus Security SG200 quick start guide

Honeywell BW Solo user manual

Honeywell

Honeywell BW Solo user manual

Pentair Goyen Mecair FFD Installation and operation manual

Pentair

Pentair Goyen Mecair FFD Installation and operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.