Section 3: Designing a Safety Function using the Rosemount 2130
March 2015
Designing a Safety Function using the Rosemount 2130
Table 3-1. 2130 Failure Rates
Note
The FMEDA report is available from the Safety quick link at www.rosemount.com. Select Product
List, then Level tab, and finally select 2130. In the right-hand panel, there are SIL documents
including the FMEDA report (and this safety manual).
3.6 Connection of the 2130 to the SIS logic solver
The Rosemount 2130 level switch should be connected to the safety-rated logic solver which is
actively performing the safety function as well as automatic diagnostics (if any) designed to
diagnose potentially dangerous failures within the level switch. In some cases, it may also be
connected directly to the final element.
The Rosemount 2130 reference manual gives full installation details for the level switch. The logic
solver trip levels must be compatible with (higher than) the sensor alarm levels given in the
specifications section of this manual.
Note
For all product information and documentation downloads, see the on-line
Rosemount 2130 web page at www.rosemount.com.
3.7 General requirements
The system and function response time shall be less than the process safety time
The 2130 level switch will change to its defined safe state in less than this time with relation
to the specific hazard scenario.
All SIS components, including the 2130 level switch must be operational before process
start-up
The user shall verify that the 2130 level switch is suitable for use in safety applications by
confirming the level switch nameplate and model number are properly marked
Output Type and
Model Option Code Mode SD(1)
(1) FIT is the abbreviation for Failure In Time. One FIT is 1x10-9 failure per hour.
SU DD DU SFF %
NAMUR NDRY=On 0.0 FIT 195.5 FIT 151.2 FIT 17.5 FIT 95.20
NAMUR NWET=On 0.0 FIT 78.3 FIT 259.1 FIT 26.1 FIT 92.80
PNP/PLC PDRY=On 0.0 FIT 422.8 FIT 171.9 FIT 50.8 FIT 92.10
PNP/PLC PWET=On 0.0 FIT 307.6 FIT 283.8 FIT 53.5 FIT 91.70
Direct Load Switching LDRY=On 0.0 FIT 364.8 FIT 170.6 FIT 45.0 FIT 92.20
Direct Load Switching LWET=On 0.0 FIT 246.9 FIT 278.4 FIT 54.8 FIT 90.60
Relay DDRY=On 0.0 FIT 266.1 FIT 142.9 FIT 104.6 FIT 79.60
Relay DWET=On 0.0 FIT 146.6 FIT 240.9 FIT 116.9 FIT 76.80
8/16 mA MDRY=On 0.0 FIT 350.7 FIT 172.4 FIT 28.5 FIT 94.80
8/16 mA MWET=On 0.0 FIT 238.6 FIT 283.4 FIT 29.6 FIT 94.60