
Reference Manual
MHM-97408.5
April 2010
CSI 9420
2-10
The CSI 9420 obviously provides the ability to get data much more frequently.
WirelessHART, in fact, requires that any device on the wireless network must
publish at least once per hour. For this reason, the minimum (least frequent)
publish rate for which the CSI 9420 can be configured is once per hour.
Publishing less frequently than this violates the network requirements.
It is, however, perfectly acceptable to publish stale data without violating the
network policy. Waking up to publish previously acquired data provides a
significant power savings over making a completely new measurement.
Power save publish is an integer field, ranging from 0 to 23, indicating the
number of “power-save” publishes between actual acquisitions. A value of
zero indicates that an acquisition occurs with each publish (i.e. Power save
publish is disabled). A value of 1 specifies one publish without an actual
acquisition (i.e. if the publish occurs every hour, then an acquisition will occur
every two hours). The maximum value of 23, with a publish rate of 1 hour,
indicates that a new acquisition occurs only once every 24 hours, with the
previously acquired data being published once an hour in between.
If the application does not require more frequent data acquisition, significant
power savings can be gained by using Power save publish. Each publish
without an acquisition saves about 50% of the power that would have
otherwise been consumed by the acquisition.
Trending Parameters Parameters can be trended either in a plant historian, in AMS Machinery
Manager, or in both locations simultaneously. The method for configuring this
functionality is contained in the associated software and the details of all the
possibilities are beyond the scope of this manual. This manual indicates
some of the general capabilities and version requirements.
Values can be trended in essentially any host that accepts Modbus or OPC
inputs. Configuration of OPC tags and Modbus registers for wireless devices
is done in the 1420 Smart Wireless Gateway web interface. Refer to the 1420
User Manual for additional information. The settings in the 1420 and the host
must be consistent and it is necessary to enter the information (e.g. Modbus
register definitions) in both locations.
DeltaV 10.3 or later integrates the 1420 Smart Wireless Gateway as a native
I/O device on the control network. In this case the wireless devices can be
managed as native HART devices and the variables trended accordingly.
This type of installation also allows richer alerting and diagnostics because
the full HART capabilities are available.
Ovation 3.3 or later also integrates the 1420 Smart Wireless Gateway with all
the associated benefits of HART.
AMS Machinery Manager 5.4 or later, while not a full HART host, implements
sufficient HART functionality to read configuration and alert information as
well as the dynamic parameters from the CSI 9420 (note this is for the
Wireless HART 2.4 GHz version only – the 900 MHz version is only supported
via Modbus). This allows Machinery Manager, among other things, to
“auto-discover” all of the devices on the wireless mesh as well as the specific
sensor configurations, units settings, and variable mappings for the CSI 9420
devices.
Also, with AMS Machinery Manager 5.4 or later, and CSI 9420 revision 3 or
later devices (that are licensed for waveform/spectra), it is possible to trend
Energy Band parameters. Refer to the discussion on bulk data retrieval and
storage below for additional information.