EMKO TRANS-AMF User manual

TRANS-AMF
AUTOMATIC MAINS FAILURE UNIT
FOR GAS/DIESEL/GASOLINE GENERATORS
WITH J1939 ECUs
User Manual
EMKO ELEKTRON K A. .
Demirta Org. San. Bolg.
Karanfil Sk. No: 6 TR
16369 Bursa / TURKEY
ÝÞ
þ
Phone
Faks
Url
E-mail
: +90 224 261 1900
: +90 224 261 1912
: www.emkoelektronik.com.tr
:emko@emkoelektronik.com.tr
exposales@emkoelektronik.com.tr
Introduction Manual. ENG TRANS-AMF 02 V28 09/15

1.Introduction.......................................................................................................................................
1.1 General Specifications..............................................................................................................
1.2 Warranty....................................................................................................................................
1.3 Maintenance .............................................................................................................................
2.Installation.........................................................................................................................................
2.1 Unit Configuration......................................................................................................................
2.2 Panel Mounting..........................................................................................................................
Figure 2.1 Front View................................................................................................................
Figure 2.2 Panel Cut-Out..........................................................................................................
2.3 Electrical Connection.................................................................................................................
3.Definition Of Front Panel And Accessing To The Parameters......................................................
3.1 Front Panel Description.............................................................................................................
3.2 Accessing To The Operator Parameters....................................................................................
3.3 Accessing To The Technician Parameters.................................................................................
3.4 Changing And Saving Parameter Values .................................................................................
4.Parameters........................................................................................................................................
4.1 Operator Parameters.................................................................................................................
4.1.1 Mains................................................................................................................................
4.1.2 Generator.........................................................................................................................
4.2 Technician Parameters..............................................................................................................
4.2.1 System.............................................................................................................................
4.2.2 Mains................................................................................................................................
4.2.3 Generator.........................................................................................................................
4.2.4 Engine..............................................................................................................................
4.2.5 Inputs...............................................................................................................................
4.2.6 Outputs.............................................................................................................................
4.2.7 Timers..............................................................................................................................
4.2.8 Expansion Modules..........................................................................................................
4.2.9 User Adjustment...............................................................................................................
5.Specifications....................................................................................................................................
6.Other Informations.............................................................................................................................
CONTENTS
Page 4
Page 7
Page 6
Page 5
Page 7
Page 5
Page 5
Page 5
Page 16
Page 79
Page 4
Page 4
Page 4
2
Page 25
Page 25
Page 25
Page 25
Page 27
Page 27
Page 32
Page 32
Page 35
Page 48
Page 64
Page 73
Page 74
Page 75
Page 5
Page 17
Page 24
Page 80

Manufacturer’s Name : EMKO ELEKTRONIK A.S.
Manufacturer’s Address : DOSAB, Karanfil Sk., No:6,
16369 Bursa, TURKEY
The manufacturer hereby declares that the product:
Product Name : Automatic Mains Failure Unit
Type Number : TRANS-AMF
Product Category : Electrical equipment for measurement, control and
laboratory use
Conforms to the following directives :
2006 / 95 / EC The Low Voltage Directive
2004 / 108 / EC The Electromagnetic Compatibility Directive
has been designed and manufactured to the following specifications:
EN 61000-6-4:2007 EMC Generic Emission Standard for Industrial Environments
EN 61000-6-2:2005 EMC Generic Immunity Standard for Industrial Environments
EN 61010-1:2001 Safety Requirements for electrical equipment for measurement, control
and laboratory use
When and Where Issued Authorized Signature
th
25 February 2011 Name : Serpil YAKIN
Bursa-TURKEY Position : Quality Manager
EU DECLARATION OF CONFORMITY
3

1.Introduction
1.1 General Specifications
4
The unit provides for automatic transfer of a load from mains to generator in the event of a
mains failure. Intended for unattended operation, it is able to detect failure of any phase of the
mains and to start and switch over to a generator if the mains voltage goes outside pre-set
limits. Both automatic and manual control is possible. A test mode is also available which
allows the generator to be run without taking the load.
The unit has Dual Working feature. In the event of a mains failure, group with high priority
starts and takes the load. If both groups has no priority, the group with less working hour will
start and take the load. To use Dual Working feature Dual Set expansion module must be
used.
The unit calculates engine RPM from Magnetic Pickup sensor input (MPU) and/or generator
voltage signal.
The unit monitors J1939 ECU messages and provides remote start/stop control via J1939
protocol (supported ECUs: Volvo EMS2, Volvo EDC4, Perkins, Scania S6, MAN MFR and
standard messages).
The unit is extensively programmable through the front panel, with password protection on two
levels. Operational parameters can also be monitored and controlled from a PC via a built-in USB
communication port.
.
The unit monitors generator operation and gives warning of any faults that are detected.
The configurable input-3 can be used as the water level sensing input.
The configurable input-7 can be used as the cabin temperature analog input.
In the event that the engine fails to start on the first attempt, the attempt will be repeated a
programmed number of times or until successful
If a fault is detected, the unit shuts down the engine and shows the failure message on the LCD
display and activates the internal sounder.
1.2 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.3 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.

5
ü
Ýçindekiler
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit , power off
the system and seperate the electrical connection of the device from the system.
Keep the power off until all of the wiring is completed so that electric shock and trouble with
the unit can be prevented.
To reduce the effect of electrical noise on device, Low voltage line (especially sensor input
cable) wiring must be separated from high current and voltage line.
If possible, use shielded cable and shield must be connected to ground only one side.
Before commissioning the device, parameters must be set in accordance with desired use.
Incomplete or incorrect configuration can cause dangerous stiuations.
Before beginning installation of this product, please read the instruction
manual and warnings below carefully.
2. Installation
Ýçindekiler
2.1 Unit Configuration
Ýçindekiler
2.2 Panel Mounting
The unit is designed for panel mounting. Fixing is by two screw fixings.
1- Insert the unit in the panel cut-out from the front.
2- Insert the fixings in the slotted at the corners of the unit and tighten the fixing screws to secure
the unit against the panel.
During the equipment is putted in hole on the metal panel while mechanical
installation some metal burrs can cause injury on hands, you must be careful.
Figure 2.1 Front View Figure 2.2 Panel Cut-Out
The unit can be programmed using the buttons and LCD display on the front panel or PC
Software.
182mm
135mm
152mm
229mm
!
!

2.3 Electrical Connection
6
TRANS-AMF three phase connections schematic
1- Connect the unit as shown in the appropriate diagram. Be sure to connect the battery
supply the right way round and battery negative should be grounded.
2- The CAN interface requires that a 120 Ohms terminator is fitted to each end of the
communications link. This termination resistor is fitted internally into the unit. So it is not
required externally. The screen is grounded at one end ONLY.
3- Screened cable must be used for connecting the Magnetic Pickup, ensuring that the
screen is grounded at one end ONLY.
4- Current transformers secondary should be grounded.
FUSE-1, FUSE-2, FUSE-5, FUSE-6 2A. T FUSE-3, FUSE-4 8A. T
FUSE-7 6A. T
FUSE-8 Max. 10 A. T
!
25
Level Sender or
Configurable Analog Input-1
Temperature Sender
Oil Sender
24 2335 21
22
BATTERY -
BATTERY +
40
42 41
5A
BATTERY +
27 26
Configurable Analog Input-2
Sender Common
18 19
17
H(+) L(-)
J1939 ECUs
34 33
BATTERY -
32 31 30 29 28
High Temperature or
Configurable Input-5
Low Oil Pressure or
Configurable Input-4
Water Level or
Configurable Input-3
Configurable Input-2
Configurable Output-5
Configurable Output-6
5A
To Engine
Earth
USB
SCR
FUSE-7
FUSE-8
*
*
IT CAN BE USED
AS A DIGITAL INPUT
BY SELECTING
FROM THE PROGRAM
PARAMETERS
* * *
3
1
Configurable Output-3
39 38 37 36
Configurable Output-4
TRANSISTOR OUTPUTS
MAX. 1 A
BATTERY +
20
-(SCR) +
MPU
2
Emergency Stop or
Configurable Input-1
Configurable Input-6
627 3
8
8A
8A
14
910 5
L1
GENERATORMAINS
L2
L3
N
M
LOAD
G
L1
L2
L3
N
El c r c l nte lock
e t iai r
Mehanica in rlkc l te oc
11 12 13 14 15 16
Mains
Contactor
Relay
Generator
Contactor
Relay
FUSE-1
FUSE-2
FUSE-3
FUSE-4
FUSE-5
FUSE-6
4
!
! !
!
Fuel Or
Configurable Output-1
Crank Or
Configurable Output-2
D+(W.L.)
Charge Alt.
Max. 300VVMax. 300VV
Cabin Temperature or
Configurable Input-7

This LED indicates that a "Shutdown" alarm was detected.
1
2
4
5
6
7
9
12
13
14
Number Comment
ü
1
2
3
4
56 7
8
9
10 11 12 13 14
15 16 17
18
19 21
20
22
24
26
28
27
29 30 31 32 33
25
23
3. Front Panel Description And Accessing To The Parameters
3.1 Front Panel Description
This LED indicates that a "Warning" alarm was detected
This LED indicates that a "Maintenance" alarm was detected
3
This LCD display is used for displaying the electrical measurements during normal operation,
and editing/inspecting programming parameters in program mode.
This LED indicates that Mains voltage and frequency is within limits and is ready to take over the
load.
This LED shows that the load is supplied from the mains.
This LED shows that the load is supplied from the generator.
8This LED indicates that Generator voltage and frequency is within limits and is ready to take over
the load.
This LED indicates that the engine has started and is running.
10
11
This LED shows that the unit is in theAUTO mode.
This LED shows that the unit is in the TEST mode.
This LED shows that the unit is in the MANUAL mode.
In the MAN, AUTO and TEST modes, this LED indicates that the engine is starting up or is
running.
This LED shows that the unit is in the STOP mode.
7

MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Wait for start
21
22
23
24
25
26
19
15
18
Number Comment
Warning and Alarm messages shortcut button.
Event Logs shortcut button.
16
17 The LAMP TEST button illuminates all LED indicators.
This button is used for showing previous parameters on the currently selected page in
normal operation. In Programming mode, it operates as an Up button (changing cursor
position) or Increment button (increase parameter value).
This button is used for showing previous page in normal operation. In Programming mode, it
operates as an Left button (changing cursor position).
20 This button is used for entering parameter edit section and saving parameter value in
programming mode.
This button is used for showing next page in normal operation. In Programming mode, it
operates as an Right button (changing cursor position).
This button is used for showing next parameters on the currently selected page in normal
operation. In Programming mode, it operates as an Down button (changing cursor position)
or Decrement button (decrease parameter value).
The Escape button is used for exit previous section in programming mode.
When this button is pressed, the unit goes into its PROGRAMMING Mode.
This button will silence the alarm horn after a failure has been detected.
This button opens or closes the mains contactor, only operative when manual mode is selected.
This button opens or closes the gen. contactor, only operative when manual mode is selected.
This button will reset the controller after a failure has been detected.
TheAUTO button is used for changing operating mode of the unit to theAUTO Mode.
The TEST button is used for changing operating mode of the unit to the TEST Mode.
The MAN button is used for changing operating mode of the unit to the MANUAL Mode.
The START button is used for starting the engine when the unit is in the Manual Mode.
The STOP button is used for changing operating mode of the unit to the STOP Mode.
The generator is stopped.
27
28
29
30
31
32
33
LCD display Description
Mains Page1
Measurement values
Engine Status or Error Messages
Current page name
128x64 Dot-matrix LCD display.
Use the Next and Previous buttons to select which Data display page (screen) is to be displayed.
When the Alarm (!) shortcut button is pressed, the Warning & Alarm display page is displayed.
When the Event log (LOG) shortcut button is pressed, the Event Log display page is displayed.
ü
8

Mains Page1:
V12: Mains voltage L1-L2
V23: Mains voltage L2-L3
V31: Mains voltage L3-L1
V1: Mains voltage L1-N
V2: Mains voltage L2-N
V3: Mains voltage L3-N
Mains Page2:
Fq: Mains frequency
Phase Seq.: Mains phase sequence
Generator Page1:
V12: Generator voltage L1-L2
V23: Generator voltage L2-L3
V31: Generator voltage L3-L1
V1: Generator voltage L1-N
V2: Generator voltage L2-N
V3: Generator voltage L3-N
Generator Page2:
I1: Load Current L1
I2: Load Current L2
I3: Load Current L3
PF1: Generator power factor L1
PF2: Generator power factor L2
PF3: Generator power factor L3
Generator Page3:
Fq: Generator frequency
Ie: Earth Current
Phase Seq.: Generator phase sequence
Generator Page4:
P1: Generator active power L1
P2: Generator active power L2
P3: Generator active power L3
9
Data display pages on the LCD display;
MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Wait for start
MAINS
Fq:50.0Hz
Phase seq.: L1 L2 L3
Wait for start
GENERATOR
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
On load
GENERATOR
I1: 26A PF1: -0.84
I2: 23A PF2: -0.80
I3: 25A PF3: -0.82
On load
GENERATOR
Fq:50.0Hz Ie: 0A
Phase seq.: L1 L2 L3
On load
GENERATOR
P1: 170kW
P2: 170kW
P3: 170kW
On load

Generator Page5:
Q1: Generator reactive power L1
Q2: Generator reactive power L2
Q3: Generator reactive power L3
Generator Page6:
S1: Generator apparent power L1
S2: Generator apparent power L2
S3: Generator apparent power L3
Generator Page7:
S
S
S
P: Generator total active power
Q: Generator total reactive power
S: Generator total apparent power
Generator Page8:
kWh: Generator active energy
KVArh: Generator reactive energy
Engine Page1:
Oil pressure: Oil pressure sender input value
Temperature: Coolant temperature sender input value
Speed: Engine speed
Engine Page2:
Conf. AI1: Configurable Analog Input-1 value
Conf. AI2: Configurable Analog Input-2 value
Battery volt: Battery supply voltage
10
GENERATOR
Q1: 40kVAr
Q2: 40kVAr
Q3: 40kVAr
On load
GENERATOR
S1: 210kVA
S2: 210kVA
S3: 210kVA
On load
GENERATOR
P: 510kW
Q: 120kVAr
S: 630kVA
On load
S
S
S
GENERATOR
kWh : 30600
kVArh: 7200
On load
ENGINE
Oil Pressure: 4.3bar
Temperature : 30ºC
Speed : 1500rpm
On load
ENGINE
Conf.AI1 : 96%
Conf.AI2 : 40ºC
Battery volt: 12.0Vdc
On load

J1939 VALUES
Coolant level: 87.6%
Load at cur.spd: 25%
Fuel temper.: 13°C
On load
J1939 VALUES
Fuel rate: 12.50L/h
Fuel tot.: 176L
Oil level: 97.2%
On load
J1939 VALUES
Engine speed: 1500rpm
Oil pressure: 4.0bar
Coolant temp: 27ºC
On load
ENGINE MAINTENANCE
Next hours : 5000
Next days : 180
Last date: 15/02/2011
On load
ENGINE
W.Hour_Min: 2_57
Cabin temp: 26ºC
On load
Engine Page3:
Gen.chg.volt: Charge generator voltage
Run times: Number of generator runs
Crank times: Number of generator starts
Engine Page4:
W.Hour_Min: Engine running time (Hour and Minute)
Cabin temp: Cabin temperature
Engine Maintenance Page:
Next hours: The remaining hour for maintenance
Next days: The remaining day for maintenance
Last date: The last maintenance date
J1939 Values Page1:
Engine speed: Engine speed via J1939
Oil pressure: Oil pressure via J1939
Coolant temp: Coolant temperature via J1939
J1939 Values Page2:
Fuel rate: Fuel rate via J1939
Fuel tot.: Fuel total used via J1939
Oil level: Oil level via J1939
J1939 Values Page3:
Coolant level: Coolant level via J1939
Load at cur.spd: Load at current speed via J1939
Fuel temper.: Fuel temperature via J1939
11
ENGINE
Gen.chg.volt: 11.8Vdc
Run times : 7
Crank times : 11
On load

DATE & TIME
15/02/2011
13:32:28
EXP. INPUT & OUTPUT
1 4 5 8
Inputs : 0000 0000
Outputs: 0000 0000
On load
INPUT & OUTPUT
1 4 5 8
Inputs : 0000 000X
Outputs: 0000 0000
On load
J1939 DM1 FAULTS1
Spn:110
Fmi:0 Oc:1
Coolant Temper.sensor
Value too high
J1939 VALUES
Int.man.temp.: 45ºC
Pedal position: 50.0%
W.Hour_Min: 2_57
On load
J1939 VALUES
Oil temper.: 82.00ºC
Act.engine torq: 75%
Boost press.: 2.8bar
On load
J1939 Values Page4:
Oil temper.: Oil temperature via J1939
Act.engine torq: Actual engine torque via J1939
Boost press.: Boost pressure via J1939
J1939 Values Page5:
Int.man.temp.: Intake manifold temperature via J1939
Pedal position: Accelerator pedal position via J1939
W.Hour_Min: Working hour and minute via J1939
J1939 DM1 (Active) Faults Page:
Spn: Suspect parameter number (e.g. SPN = 110 corresponds to
coolant temperature sensor)
Fmi: Failure mode identifier (e.g. FMI = 0 means value too high)
Oc: Occurrence count (if OC = 0, no alarm is present)
The first 10 active alarm messages (Active Diagnostic Trouble
Codes - DM1) with SPN, FMI, and OC are displayed). If more than
one active fault condition is present, all of them is displayed
sequencely by pressing Next and Previous buttons.
Input & Output Status Page: Inputs: Input status information. If an input is active, related digit
is displayed as "1" else it is displayed as "0".
1: Conf. in-1, 2: Conf. in-2, 3: Conf. in-3, 4: Conf. in-4,
5: Conf. in-5, 6: Conf. in-6, 7: Conf. in-7, 8: Not available.
Outputs: Output status information. If an output is active, related
digit is displayed as "1" else it is displayed as "0".
1: Conf. out-1, 2: Conf. out-2, 3: Conf. out-3, 4: Conf. out-4,
5: Conf. out-5, 6: Conf. out-6, 7: Generator contactor,
8: Mains contactor.
Exp. Input & Output Status Page: Inputs: Exp. input status information. If an input is active, related
digit is displayed as "1" else it is displayed as "0".
1: Exp. conf. in-1, 2: Exp. conf. in-2, 3: Exp. conf. in-3,
4: Exp. conf. in-4, 5: Exp. conf. in-5, 6: Exp. conf. in-6,
7: Exp. conf. in-7, 8: Exp. conf. in-8.
Outputs: Exp. output status information. If an output is active,
related digit is displayed as "1" else it is displayed as "0".
1: Exp. conf. out-1, 2: Exp. conf. out-2, 3: Exp. conf. out-3,
4: Exp. conf. out-4, 5: Exp. conf. out-5, 6: Exp. conf. out-6,
7: Exp. conf. out-7, 8: Exp. conf. out-8.
Date & Time Page:
Date: Day, Month, Year.
Time: Hour, minute, second.
12

Warning & Alarm Page:
1/3: The first message of current alarms.
Emergency stop!: This message indicates that an emergency
stop alarm has occurred.
Event Log Page1:
1.1: The first page of related event log
Emergency stop: This message indicates that an emergency stop
alarm has occurred. (Event history: 15/02/2011 date, 14:26:08
time).
V1: Generator voltage L1-N
I1: Load Current L1
V2: Generator voltage L2-N
I2: Load Current L2
Event Log Page2:
1.2: The second page of related event log
V3: Generator voltage L3-N
I3: Load Current L3
Fq: Generator frequency
kW: Generator total active power
Oil oressure: Oil pressure sender input value
Coolant temp: Coolant temperature sender input value
Event Log Page3:
1.3: The last page of related event log
Conf. AI1: Configurable Analog Input-1 value
Conf. AI2: Configurable Analog Input-2 value
kWh: Generator active energy
Events (from 1 to 50) can be displayed sequencely with the Next
and Previous buttons.
13
WARNING&ALARM 1/3
Emergency stop!
EVENT LOG 1.1
15/02/2011 14:26:08
Emergency stop
V1: 220V I1: 26A
V2: 220V I2: 23A
EVENT LOG 1.2
V3: 220V I3: 25A
Fq:50.0Hz kW: 510
Oil pressure: 4.3bar
Coolant temp: 30ºC
EVENT LOG 1.3
Conf.AI1 : 96%
Conf.AI2 : 40ºC
kWh: 30600
Warning & Alarm display pages on the LCD display;
Event Log display pages on the LCD display;
GenSet Page: (This page is only available at TRANS-AMF.TR device)
VLn: Generator voltage L1-N, L2-N and L3-N
Amp: Generator current L1, L2 and L3
Hz: Generator frequency
bar: Oil pressure sender input value
kW: Generator total active power
ºC: Coolant temperature sender input value
cos: Generator power factor average
%: Configurable Analog Input-1 value
rpm: Engine speed
Vdc: Battery supply voltage
GENSET
VLn 220V 220V 220V
Amp 26A 23A 25A
50.0Hz 4.3bar
630kW 30ºC
1.00cos 96%
1500rpm 12.0Vdc
On load

GENERATOR
kWh : 30600
kVArh: 7200
On load
ENGINE
Oil Pressure: 4.3bar
Temperature : 30ºC
Speed : 1500rpm
On load
ENGINE
Conf.AI1 : 96%
Conf.AI2 : 40ºC
Battery volt: 12.0Vdc
On load
MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Wait for start
MAINS
Fq:50.0Hz
Phase seq.: L1 L2 L3
Wait for start
GENERATOR
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
On load
GENERATOR
I1: 26A PF1: -0.84
I2: 23A PF2: -0.80
I3: 25A PF3: -0.82
On load
GENERATOR
P1: 170kW
P2: 170kW
P3: 170kW
On load
GENERATOR
Fq:50.0Hz Ie: 0A
Phase seq.: L1 L2 L3
On load
GENERATOR
P: 510kW
Q: 120kVAr
S: 630kVA
On load
S
S
S
GENERATOR
S1: 210kVA
S2: 210kVA
S3: 210kVA
On load
GENERATOR
Q1: 40kVAr
Q2: 40kVAr
Q3: 40kVAr
On load
ENGINE
Gen.chg.volt: 11.8Vdc
Run times : 7
Crank times : 11
On load
ENGINE
W.Hour_Min: 2_57
Cabin temp: 26ºC
On load
ENGINE MAINTENANCE
Next hours : 5000
Next days : 180
Last date: 15/02/2011
On load
J1939 VALUES
Engine speed: 1500rpm
Oil pressure: 4.0bar
Coolant temp: 27ºC
On load
J1939 VALUES
Fuel rate: 12.50L/h
Fuel tot.: 176L
Oil level: 97.2%
On load
J1939 VALUES
Coolant level: 87.6%
Load at cur.spd: 25%
Fuel temper.: 13°C
On load
J1939 DM1 FAULTS1
Spn:110
Fmi:0 Oc:1
Coolant Temper.sensor
Value too high
J1939 VALUES
Oil temper.: 82.00ºC
Act.engine torq: 75%
Boost press.: 2.8bar
On load
J1939 VALUES
Int.man.temp.: 45ºC
Pedal position: 50.0%
W.Hour_Min: 2_57
On load
INPUT & OUTPUT
1 4 5 8
Inputs : 0000 000X
Outputs: 0000 0000
On load
EXP. INPUT & OUTPUT
1 4 5 8
Inputs : 0000 000X
Outputs: 0000 0000
On load
DATE & TIME
15/02/2011
13:32:28
Example-1: Displaying all Data display pages.
14

WARNING&ALARM 1/2
Emergency stop!
WARNING&ALARM 2/2
High temp.prealarm!
MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Wait for start
Example-2: Displaying all Warning&Alarm display pages
15
Example-3: Displaying all Event Log display pages
EVENT LOG 1.1
15/02/2011 14:26:08
Emergency stop
V1: 220V I1: 26A
V2: 220V I2: 23A
EVENT LOG 1.2
V3: 220V I3: 25A
Fq:50.0Hz kW: 510
Oil pressure: 4.3bar
Coolant temp: 30ºC
EVENT LOG 1.3
Conf.AI1 : 96%
Conf.AI2 : 40ºC
kWh: 30600
MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Wait for start
LCD display language selection
MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Wait for start
ü
English Display
ü
ü
Press the Up or
Down buttons to
select the language
you wish to change.
Press the
Enter
button.
LCD DISPLAY
Language
ENGLISH
LCD DISPLAY
Language
ENGLISH
Press the Enter
button to confirm
the changed value.
Press the Escape
button to exit language
selection screen.
MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Wait for start
English Display
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Chinese Display
主电源

3.2 Accessing To The Operator Parameters
16
PROGRAM
Operator setting
Technician setting
Factory adjustment
OPERATOR SETTING
Password
0000
ü ü
OPERATOR SETTING
Mains
Generator
ü
MAINS
Volt level
Frequency level
ü
MAINS VOLT LEVEL
Under volt trip
Under volt reset
Over volt trip
Over volt reset
ü
MAINS VOLT LEVEL
Under volt trip
320 Vac
ü
MAINS
Volt level
Frequency level
ü
MAINS FREQ. LEVEL
Under freq trip
Under freq reset
Over freq trip
Over freq reset
ü ü
MAINS FREQ. LEVEL
Under freq trip
45.0 Hz
OPERATOR SETTING
Mains
Generator
ü
GENERATOR
Volt level
Frequency level
Current level
Power level
ü
GENERATOR
Volt level
Frequency level
Current level
Power level
ü
GENERATOR VOLT LEVEL
Under volt shutdown
Under volt prealarm
Under volt reset
Over volt shutdown
ü
GENERATOR VOLT LEVEL
Under volt shutdown
320 Vac
ü
GENERATOR
Volt level
Frequency level
Current level
Power level
ü
GENERATOR CUR LEVEL
Under cur. set
Under cur. prealarm
Under cur. reset
Over cur. set
GENERATOR CUR LEVEL
Over cur. prealarm
Over cur. reset
ü
ü
GENERATOR CUR LEVEL
Under cur. set
20 A
ü
ü
GENERATOR VOLT LEVEL
Over volt prealarm
Over volt reset
Shutdown delay time
ü
GENERATOR VOLT LEVEL
Over volt prealarm
340 Vac
ü
GENERATOR VOLT LEVEL
Under volt shutdown
Under volt prealarm
Under volt reset
Over volt shutdown
GENERATOR VOLT LEVEL
Over volt prealarm
Over volt reset
Shutdown delay time
GENERATOR FREQ LEVEL
Under freq shutdown
Under freq prealarm
Under freq reset
Over freq shutdown
ü
GENERATOR FREQ LEVEL
Under freq shutdown
43.0 Hz
ü
GENERATOR FREQ LEVEL
Under freq shutdown
Under freq prealarm
Under freq reset
Over freq shutdown
GENERATOR FREQ LEVEL
Over freq prealarm
Over freq reset
Shutdown delay time
ü
GENERATOR FREQ LEVEL
Over freq prealarm
55.0 Hz
ü
GENERATOR FREQ LEVEL
Over freq prealarm
Over freq reset
Shutdown delay time
GENERATOR CUR LEVEL
Over cur. prealarm
90 A
GENERATOR
Volt level
Frequency level
Current level
Power level
ü
GEN POWER LEVEL
Under power set
Under power prealarm
Under power reset
Over power set
GEN POWER LEVEL
Over power prealarm
Over power reset
Reverse power set
ü
ü
GEN POWER LEVEL
Under power set
150 kVA
ü
ü
GEN POWER LEVEL
Over power prealarm
280 kVA
GEN POWER LEVEL
Over power prealarm
Over power reset
Reverse power set
GEN POWER LEVEL
Under power set
Under power prealarm
Under power reset
Over power set
GENERATOR CUR LEVEL
Under cur. set
Under cur. prealarm
Under cur. reset
Over cur. set
GENERATOR CUR LEVEL
Over cur. prealarm
Over cur. reset
GENERATOR
Working calendar
ü
ü
ü
ü
GEN WORKING CALENDAR
Stop time on tuesday
Start time on wednes.
Stop time on wednes.
Start time on thurs.
GEN WORKING CALENDAR
Stop time on thursday
Start time on friday
Stop time on friday
Start time on satur.
GEN WORKING CALENDAR
Stop time on saturday
Start time on sunday
Stop time on sunday
ü
GEN WORKING CALENDAR
Stop time on tuesday
17.30 Hour.Min
ü
GEN WORKING CALENDAR
Stop time on thursday
18.30 Hour.Min
ü
GEN WORKING CALENDAR
Stop time on saturday
14.20 Hour.Min
GEN WORKING CALENDAR
Disable/enable select
Start time on monday
Stop time on monday
Start time on tues.
GEN WORKING CALENDAR
Disable/enable select
DISBL
ü ü
GEN WORKING CALENDAR
Stop time on tuesday
Start time on wednes.
Stop time on wednes.
Start time on thurs.
GEN WORKING CALENDAR
Stop time on thursday
Start time on friday
Stop time on friday
Start time on satur.
GEN WORKING CALENDAR
Stop time on saturday
Start time on sunday
Stop time on sunday
GEN WORKING CALENDAR
Disable/enable select
Start time on monday
Stop time on monday
Start time on tues.
MAINS VOLT LEVEL
Under volt trip
Under volt reset
Over volt trip
Over volt reset
MAINS FREQ. LEVEL
Under freq trip
Under freq reset
Over freq trip
Over freq reset

3.3 Accessing To The Technician Parameters
17
PROGRAM
Operator setting
Technician setting
Factory adjustment
TECHNICIAN SETTING
Password
0000
ü ü ü
TECHNICIAN SETTING
System
Mains
Generator
Engine
ü
SYSTEM
Network
Breakers
LCD display
Communication
ü
SYSTEM NETWORK
CT ratio
Earth Fault CT ratio
PT ratio
Type of AC system
SYSTEM NETWORK
Phase sequence
Generator kVA rating
Power unit
kVA,kW,kVAr point
ü
ü
SYSTEM NETWORK
CT ratio
500 A
SYSTEM NETWORK
CT ratio
Earth Fault CT ratio
PT ratio
Type of AC system
SYSTEM NETWORK
Phase sequence
Generator kVA rating
Power unit
kVA,kW,kVAr point
ü
SYSTEM NETWORK
Phase sequence
DISBL
SYSTEM
Network
Breakers
LCD display
Communication
ü
BREAKERS
Type of Breaker
Gen.brk.cls.contact
Gen.brk.cls.relay
Gen.brk.cls.time
ü ü
BREAKERS
Type of Breaker
0
BREAKERS
Gen.brk.open relay
Gen.brk.open time
Mains.brk.cls.contact
Mains.brk.cls.relay
ü ü
BREAKERS
Gen.brk.open relay
0
BREAKERS
Mains.brk.cls.time
Mains.brk.open relay
Mains.brk.open time
Break.close puls.time
ü ü
BREAKERS
Mains close timer
5 SEC
BREAKERS
Type of Breaker
Gen.brk.cls.contact
Gen.brk.cls.relay
Gen.brk.cls.time
BREAKERS
Gen.brk.open relay
Gen.brk.open time
Mains.brk.cls.contact
Mains.brk.cls.relay
BREAKERS
Mains.brk.cls.time
Mains.brk.open relay
Mains.brk.open time
Break.close puls.time
BREAKERS
Break.open pulse time
Transfer time
Spring loading time
Retry number
ü ü
BREAKERS
Break.open pulse time
0.5 SEC
BREAKERS
Break.open pulse time
Transfer time
Spring loading time
Retry number
SYSTEM
Network
Breakers
LCD display
Communication
ü
LCD DISPLAY
Language
Contrast
Auto backlight off
Auto scroll time
ü ü
LCD DISPLAY
Auto scroll number
Err. mesg scroll time
ü ü
LCD DISPLAY
Auto scroll number
5
LCD DISPLAY
Language
Contrast
Auto backlight off
Auto scroll time
LCD DISPLAY
Auto scroll number
Err. mesg scroll time
SYSTEM
Network
Breakers
LCD display
Communication
ü
COMMUNICATION
Slave address
Baud rate
Parity
Stop bit
ü ü
COMMUNICATION
Slave address
1
COMMUNICATION
Slave address
Baud rate
Parity
Stop bit
SYSTEM
Date & time set
Default settings
Password
ü
DATE & TIME SET
Year
Month
Day
Week
ü ü
DATE & TIME SET
Year
11
DATE & TIME SET
Hour
Minute
Second
ü ü
DATE & TIME SET
Hour
18
DATE & TIME SET
Year
Month
Day
Week
DATE & TIME SET
Hour
Minute
Second
SYSTEM
Date & time set
Default settings
Password
ü
DEFAULT SETTINGS
Save setting to def.
Reset default sets
Reset factory sets
ü ü
DEFAULT SETTINGS
Save setting to def.
no
SYSTEM
Date & time set
Default settings
Password
ü
TECHNICIAN SETTING
System
Mains
Generator
Engine
ü
MAINS
Volt level
Frequency level
Actions
ü
MAINS VOLT LEVEL
Under volt trip
Under volt reset
Over volt trip
Over volt reset
ü
MAINS VOLT LEVEL
Under volt trip
320 Vac
ü
MAINS
Volt level
Frequency level
Actions
ü
MAINS FREQ. LEVEL
Under freq trip
Under freq reset
Over freq trip
Over freq reset
ü ü
MAINS FREQ. LEVEL
Under freq trip
45.0 Hz
MAINS VOLT LEVEL
Under volt trip
Under volt reset
Over volt trip
Over volt reset
MAINS FREQ. LEVEL
Under freq trip
Under freq reset
Over freq trip
Over freq reset
PASSWORD SETTINGS
Operator password
Technician password
ü ü
PASSWORD SETTINGS
Operator password
1
PASSWORD SETTINGS
Operator password
Technician password
DEFAULT SETTINGS
Save setting to def.
Reset default sets
Reset factory sets
TECHNICIAN SETTING
System
Mains
Generator
Engine
ü
GENERATOR
Volt level
Frequency level
Current level & act.
Power level
ü
GENERATOR VOLT LEVEL
Under volt shutdown
Under volt prealarm
Under volt reset
Over volt shutdown
ü
GENERATOR VOLT LEVEL
Under volt shutdown
320 Vac
ü
GENERATOR VOLT LEVEL
Under volt shutdown
Under volt prealarm
Under volt reset
Over volt shutdown
LCD DISPLAY
Language
ENGLISH
MAINS
Volt level
Frequency level
Actions
ü
MAINS ACTIONS
Mains failure detect
Mains fail.stop mode
Always return delay
ü ü
MAINS ACTIONS
Mains failure detect
ENABL
MAINS ACTIONS
Mains failure detect
Mains fail.stop mode
Always return delay

GENERATOR
Volt level
Frequency level
Current level & act.
Power level
ü
GENERATOR
Volt level
Frequency level
Current level & act.
Power level
ü ü
GEN CUR LEVEL & ACT
Under cur. set
20 A
ü
GENERATOR VOLT LEVEL
Over volt prealarm
Over volt reset
Shutdown delay time
ü
GENERATOR VOLT LEVEL
Over volt prealarm
340 Vac
ü
GENERATOR VOLT LEVEL
Over volt prealarm
Over volt reset
Shutdown delay time
GENERATOR FREQ LEVEL
Nominal frequency
Under freq shutdown
Under freq prealarm
Under freq reset
ü
GENERATOR FREQ LEVEL
Nominal frequency
50.0 Hz
ü
GENERATOR FREQ LEVEL
Over freq shutdown
Over freq prealarm
Over freq reset
Shutdown delay time
ü
GENERATOR FREQ LEVEL
Over freq shutdown
58.0 Hz
ü
GEN CUR LEVEL & ACT
Under cur. set
Under cur. prealarm
Under cur. reset
Under cur. act.
GEN CUR LEVEL & ACT
Under cur. set
Under cur. prealarm
Under cur. reset
Under cur. act.
GENERATOR FREQ LEVEL
Nominal frequency
Under freq shutdown
Under freq prealarm
Under freq reset
GENERATOR FREQ LEVEL
Over freq shutdown
Over freq prealarm
Over freq reset
Shutdown delay time
ü
ü
ü
GEN CUR LEVEL & ACT
Under act. delay time
2 SEC
GEN CUR LEVEL & ACT
Over cur. act.
DISBL
ü
ü
GEN CUR LEVEL & ACT
Earth fault cur. act.
E.F. act. delay time
Unbalance load set
Unbalance load act.
GEN CUR LEVEL & ACT
Under act. delay time
Over cur. set
Over cur. prealarm
Over cur. reset
GEN CUR LEVEL & ACT
Over cur. act.
Over act. delay time
Short circuit cur.
Earth fault cur.
GEN CUR LEVEL & ACT
Earth fault cur. act.
DISBL
ü
GEN CUR LEVEL & ACT
Earth fault cur. act.
E.F. act. delay time
Unbalance load set
Unbalance load act.
GEN CUR LEVEL & ACT
Under act. delay time
Over cur. set
Over cur. prealarm
Over cur. reset
GEN CUR LEVEL & ACT
Over cur. act.
Over act. delay time
Short circuit cur.
Earth fault cur.
18
GEN POWER LEVEL
Under act. delay time
Over power set
Over power prealarm
Over power reset
GEN POWER LEVEL
Over power act.
Over act. delay time
Reverse power set
Reverse power act.
ü
ü
ü
ü
GEN POWER LEVEL
Under act. delay time
2 SEC
GEN POWER LEVEL
Over power act.
DISBL
GEN POWER LEVEL
Under act. delay time
Over power set
Over power prealarm
Over power reset
GEN POWER LEVEL
Over power act.
Over act. delay time
Reverse power set
Reverse power act.
GENERATOR
Working calendar
General
ü
ü
ü
ü
GEN WORKING CALENDAR
Stop time on tuesday
Start time on wednes.
Stop time on wednes.
Start time on thurs.
GEN WORKING CALENDAR
Stop time on thursday
Start time on friday
Stop time on friday
Start time on satur.
GEN WORKING CALENDAR
Stop time on saturday
Start time on sunday
Stop time on sunday
ü
GEN WORKING CALENDAR
Stop time on tuesday
17.30 Hour.Min
ü
GEN WORKING CALENDAR
Stop time on thursday
18.30 Hour.Min
ü
GEN WORKING CALENDAR
Stop time on saturday
14.20 Hour.Min
GEN WORKING CALENDAR
Disable/enable select
Start time on monday
Stop time on monday
Start time on tues.
GEN WORKING CALENDAR
Disable/enable select
DISBL
ü ü
GEN WORKING CALENDAR
Stop time on tuesday
Start time on wednes.
Stop time on wednes.
Start time on thurs.
GEN WORKING CALENDAR
Stop time on thursday
Start time on friday
Stop time on friday
Start time on satur.
GEN WORKING CALENDAR
Stop time on saturday
Start time on sunday
Stop time on Sunday
GEN WORKING CALENDAR
Disable/enable select
Start time on monday
Stop time on monday
Start time on tues.
TECHNICIAN SETTING
System
Mains
Generator
Engine
ü ü
ENGINE
Starting options
Crank disconnect
Speed settings
Plant battery
ENGINE START OPTIONS
Horn prior start
No. of start attemp
Cranking time
Crank rest time
ü ü
ENGINE START OPTIONS
Horn prior start
DISBL
ENGINE START OPTIONS
Horn prior start
No. of start attemp
Cranking time
Crank rest time
GENERATOR
Volt level
Frequency level
Current level & act.
Power level
ü
GEN POWER LEVEL
Under power set
Under power prealarm
Under power reset
Under power act.
ü
GEN POWER LEVEL
Under power shutdown
150 kVA
ü
GEN POWER LEVEL
Under power set
Under power prealarm
Under power reset
Under power act.
GENERATOR
Working calendar
General
ü
GENERATOR GENERAL
Sens.option gen.freq
Sens.opt.pickup&Flywh
All warning are latch
GENERATOR GENERAL
Sens.option gen.freq
DISBL
ü ü
GENERATOR GENERAL
Sens.option gen.freq
Sens.opt.pickup&Flywh
All warning are latch
ü
GEN CUR LEVEL & ACT
Unbalance act. delay GEN CUR LEVEL & ACT
Unbalance act. delay
2 SEC
ü
GEN CUR LEVEL & ACT
Unbalance act. delay
GEN POWER LEVEL
Rv.pow.act.delay time
ü ü
GEN POWER LEVEL
Rv.pow.act.delay time
2 SEC
GEN POWER LEVEL
Rv.pow.act.delay time

19
ENGINE
CanBus ECU
CanBus error set
Maintenance
Load test
ü
CANBUS ERROR SET
CAN fault actions
CAN fault activation
CAN fault delay
Amber warn.actions
ü ü
CANBUS ERROR SET
CAN fault actions
DISBL
CANBUS ERROR SET
Amber warn.activation
Amber warn.delay
Red stop actions
Red stop activation
ü ü
CANBUS ERROR SET
Amber warn.activation
2
CANBUS ERROR SET
Red stop delay
ü ü
CANBUS ERROR SET
Red stop delay
2 SEC
CANBUS ERROR SET
CAN fault actions
CAN fault activation
CAN fault delay
Amber warn.actions
CANBUS ERROR SET
Amber warn.activation
Amber warn.delay
Red stop actions
Red stop activation
CANBUS ERROR SET
Red stop delay
ENGINE
CanBus ECU
CanBus error set
Maintenance
Load test
ü
ENGINE
Starting options
Crank disconnect
Speed settings
Plant battery
ü
ENGINE SPEED SETS
Nominal speed
Under speed shutdown
Under speed prealarm
Under speed reset
ü ü
ENGINE SPEED SETS
Nominal speed
1500 RPM
ENGINE SPEED SETS
Over speed shutdown
Over speed prealarm
Over speed reset
Shutdown delay time
ü ü
ENGINE SPEED SETS
Over speed shutdown
DISBL
ENGINE
Starting options
Crank disconnect
Speed settings
Plant battery
ü
ENGINE PLANT BATTERY
Under volt
Under volt reset
Under volt delay
Over volt
ü ü
ENGINE PLANT BATTERY
Under volt
10.0 Vdc
ENGINE PLANT BATTERY
Over volt reset
Over volt delay
Alt. chg. warning
ü ü
ENGINE PLANT BATTERY
Over volt reset
29.5 Vdc
ENGINE PLANT BATTERY
Under volt
Under volt reset
Under volt delay
Over volt
ENGINE PLANT BATTERY
Over volt reset
Over volt delay
Alt. chg. warning
CANBUS ECU
Baud rate
J1939 ECU type
Device address
Engine cont. address
ü ü
CANBUS ECU
Baud rate
4
CANBUS ECU
ECU remote control
Speed control enable
Oil Pres cont. enab
Temp. control enable
ü ü
CANBUS ECU
ECU remote control
DISBL
CANBUS ECU
Speed set point
Speed correction
ü ü
CANBUS ECU
Speed set point
1500 RPM
ENGINE
CanBus ECU
CanBus error set
Maintenance
Load test
ü
CANBUS ECU
Baud rate
J1939 ECU type
Device address
Engine cont. address
CANBUS ECU
ECU remote control
Speed control enable
Oil Pres cont. enab
Temp. control enable
CANBUS ECU
Speed set point
Speed correction
ENGINE MAINTENANCE
Running hour interval
Maint. date interval
Eng. stop when maint
Eng.running hour(lsb)
ü ü
ENGINE MAINTENANCE
Running hour interval
5000 HOUR
ENGINE MAINTENANCE
Running hour interval
Maint. date interval
Eng. stop when maint
Eng.running hour(lsb)
ENGINE SPEED SETS
Nominal speed
Under speed shutdown
Under speed prealarm
Under speed reset
ENGINE SPEED SETS
Over speed shutdown
Over speed prealarm
Over speed reset
Shutdown delay time
ENGINE MAINTENANCE
Eng.running hour
Eng.running hour(msb)
Maintenance okay
ü ü
ENGINE MAINTENANCE
Eng.running hour
0
ENGINE MAINTENANCE
Eng.running hour
Eng.running hour(msb)
Maintenance okay
LOAD TEST
Disable/enable select LOAD TEST
Disable/enable select
DISBL
ENGINE
CanBus ECU
CanBus error set
Maintenance
Load test
ü ü ü
LOAD TEST
Disable/enable select
ENGINE
Exercise
General
ü ü
EXERCISE
Disable/enable select
Start time on monday
Stop time on monday
Start time on tues.
ü
EXERCISE
Disable/enable select
DISBL
EXERCISE
Disable/enable select
Start time on monday
Stop time on monday
Start time on tues.
ENGINE
Starting options
Crank disconnect
Speed settings
Plant battery
ü
ENG.CRANK DISCONNECT
Generator frequency
Engine speed
Generator volt
Alt. Charge volt
ü ü
ENG.CRANK DISCONNECT
Generator frequency
30.0 Hz
ENG.CRANK DISCONNECT
Oil pressure
ü
ENG.CRANK DISCONNECT
Generator frequency
Engine speed
Generator volt
Alt. Charge volt
ENG.CRANK DISCONNECT
Oil pressure
ü
ENG.CRANK DISCONNECT
Oil pressure
DISBL
ENGINE START OPTIONS
Pickup fail delay
ü ü
ENGINE START OPTIONS
Pickup fail delay
1.0 sec
ENGINE START OPTIONS
Pickup fail delay
ü
EXERCISE
Stop time on Tuesday
Start time on wednes.
Stop time on wednes.
Start time on thurs.
ü
EXERCISE
Stop time on Tuesday
0.00 Hour.Min
EXERCISE
Stop time on Tuesday
Start time on wednes.
Stop time on wednes.
Start time on thurs.

20
SENDER INPUTS
Conf. AI1 high prealr
Conf. AI1 high reset
Conf. AI1 high shutd.
Conf. AI1 control ON
ü
SENDER INPUTS
High temp. reset
High temp. shutdown
Low temp. Warning
Heater control ON
ü
SENDER INPUTS
Heater control OFF
Water pump on time
Water pump off time
Conf. AI1 unit
ü
SENDER INPUTS
Conf. AI1 type
Conf. AI1 low prealrm
Conf. AI1 low reset
Conf. AI1 low shutdwn
ü
ü
SENDER INPUTS
High temp. reset
88 ºC
ü
SENDER INPUTS
Heater control OFF
45 ºC
ü
SENDER INPUTS
Conf. AI1 type
0-NOT USED
ü
SENDER INPUTS
Conf. AI1 high prealr
DISBL
INPUTS
Sender inputs
Sender linearisations
Conf. input-1
Conf. input-2
ü
SENDER LINEARISATION
Oil pressure sender 1
Oil pressure 1
Oil pressure sender 2
Oil pressure 2
ü ü
SENDER LINEARISATION
Oil pressure sender 1
10 R
SENDER LINEARISATION
Oil pressure sender 3
Oil pressure 3
Oil pressure sender 4
Oil pressure 4
ü ü
SENDER LINEARISATION
Oil pressure sender 3
62 R
SENDER LINEARISATION
Oil pressure sender 5
Oil pressure 5
Oil pressure sender 6
Oil pressure 6
ü ü
SENDER LINEARISATION
Oil pressure sender 5
111 R
SENDER LINEARISATION
Oil pressure sender 7
Oil pressure 7
Oil pressure sender 8
Oil pressure 8
ü ü
SENDER LINEARISATION
Oil pressure sender 7
156 R
SENDER LINEARISATION
Oil pressure sender 9
Oil pressure 9
Oil press. sender 10
Oil pressure 10
ü ü
SENDER LINEARISATION
Oil pressure sender 9
205 R
SENDER INPUTS
Conf. AI1 high prealr
Conf. AI1 high reset
Conf. AI1 high shutd.
Conf. AI1 control ON
SENDER INPUTS
High temp. reset
High temp. shutdown
Low temp. Warning
Heater control ON
SENDER INPUTS
Heater control OFF
Water pump on time
Water pump off time
Conf. AI1 unit
SENDER INPUTS
Conf. AI1 type
Conf. AI1 low prealrm
Conf. AI1 low reset
Conf. AI1 low shutdwn
SENDER INPUTS
Oil pressure shutdown
Temperature unit
Temp. input type
High temp. prealarm
ü ü
SENDER INPUTS
Oil press. shutdown
1.0 Bar
SENDER INPUTS
Oil pressure shutdown
Temperature unit
Temp. input type
High temp. Prealarm
SENDER LINEARISATION
Oil pressure sender 1
Oil pressure 1
Oil pressure sender 2
Oil pressure 2
SENDER LINEARISATION
Oil pressure sender 3
Oil pressure 3
Oil pressure sender 4
Oil pressure 4
SENDER LINEARISATION
Oil pressure sender 5
Oil pressure 5
Oil pressure sender 6
Oil pressure 6
SENDER LINEARISATION
Oil pressure sender 7
Oil pressure 7
Oil pressure sender 8
Oil pressure 8
SENDER LINEARISATION
Oil pressure sender 9
Oil pressure 9
Oil press. sender 10
Oil pressure 10
SENDER INPUTS
Conf. AI1 control OFF
Conf. AI2 unit
Conf. AI2 type
Conf. AI2 low prealrm
ü ü
SENDER INPUTS
Conf. AI1 control OFF
75 %
SENDER INPUTS
Conf. AI1 control OFF
Conf. AI2 unit
Conf. AI2 type
Conf. AI2 low prealrm
SENDER INPUTS
Conf. AI2 low reset
Conf. AI2 low shutdwn
Conf. AI2 high prealr
Conf. AI2 high reset
ü ü
SENDER INPUTS
Conf. AI2 low reset
60 ºC
SENDER INPUTS
Conf. AI2 low reset
Conf. AI2 low shutdwn
Conf. AI2 high prealr
Conf. AI2 high reset
INPUTS
Sender inputs
Sender linearisations
Conf. input-1
Conf. input-2
ü
SENDER INPUTS
Oil pressure unit
Oil press. input type
Oil pressure prealarm
Oil pressure reset
ü ü
SENDER INPUTS
Oil pressure unit
Bar
SENDER INPUTS
Oil pressure unit
Oil press. input type
Oil pressure prealarm
Oil pressure reset
TECHNICIAN SETTING
Inputs
Outputs
Timers
Expansion modules
ü
SENDER INPUTS
Conf. AI2 high shutd.
Conf. AI2 control ON
Conf. AI2 control OFF
ü ü
SENDER INPUTS
Conf. AI2 high shutd.
DISBL
SENDER INPUTS
Conf. AI2 high shutd.
Conf. AI2 control ON
Conf. AI2 control OFF
ü
EXERCISE
Stop time on Thursday
Start time on Friday
Stop time on Friday
Start time on satur.
ü
EXERCISE
Stop time on Thursday
0.00 Hour.Min
EXERCISE
Stop time on Thursday
Start time on Friday
Stop time on Friday
Start time on satur.
ü
EXERCISE
Stop time on Saturday
Start time on sunday
Stop time on Sunday
ü
EXERCISE
Stop time on Saturday
0.00 Hour.Min
EXERCISE
Stop time on Saturday
Start time on sunday
Stop time on Sunday
ENGINE
Exercise
General
ü ü
ENGINE GENERAL
Fuel selection
Stop solenoid time
Ignition delay
Gas valve delay
ü
ENGINE GENERAL
Fuel selection
1-DIESEL
ENGINE GENERAL
Fuel selection
Stop solenoid time
Ignition delay
Gas valve delay
ü
ENGINE GENERAL
Min.of ignition speed
Choke time
ü
ENGINE GENERAL
Min.of ignition speed
200 RPM
ENGINE GENERAL
Min.of ignition speed
Choke time
Other manuals for TRANS-AMF
1
Table of contents
Other EMKO Control Unit manuals
Popular Control Unit manuals by other brands

GE
GE NX-1710E - Single Door Control Module Installation and start-up manual

Digitrax
Digitrax UT1 manual

Allen-Bradley
Allen-Bradley ControlLogix 1756-ENET/B installation instructions

ABB
ABB RBIP-01 user manual

Graco
Graco PM5 238511 Instructions and parts list

Afag
Afag CR 12 Translation of the Original Montage Instructions

Honeywell
Honeywell UCIP-GPRS quick start guide

schmersal
schmersal PDM-SD-4CC-SD operating instructions

Honeywell
Honeywell ADEMCO VA8201 Installation and setup guide

ABB
ABB OMD800 Installation and operating instruction

Eaton
Eaton EWFFSC15 quick start guide

JAUDT
JAUDT SW GII 6406 Series Translation of the original operating instructions