EMKO TRANS-AMF User manual

Introduction Brochure. ENG TRANS-AMF 01 V48 02/20
TRANS-AMF
AUTOMATIC MAINS FAILURE UNIT
1.2 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship.
This warranty is provided for a period of two years. The warranty period starts from the delivery date. This
warranty is in force if duty and responsibilities which are determined in warranty document and instruction
manual performs by the customer completely.
1.3 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device before
accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of these
solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or
water to clean the external plastic case.
1. Introduction
1.1 General Specifications
The unit provides for automatic transfer of a load from mains to generator in the event of a mains
failure. Intended for unattended operation, it is able to detect failure of any phase of the mains and to
start and switch over to a generator if the mains voltage goes outside pre-set limits. Both automatic
and manual control is possible. A test mode is also available which allows the generator to be run
without taking the load.
The unit has Dual Working feature. In the event of a mains failure, group with high priority starts and
takes the load. If both groups has no priority, the group with less working hour will start and take the
load. To use Dual Working feature Dual Set expansion module must be used.
The unit calculates engine RPM from Magnetic Pickup sensor (MPU) and/or generator voltage signal.
The unit monitors J1939 ECU messages and provides remote start/stop control via J1939 protocol
(supported ECUs: Volvo EMS2, Volvo EDC4, Perkins, Scania S6, MAN MFR and standard messages).
The unit monitors generator operation and gives warning of any faults that are detected.
The configurable input-3 can be used as the water level sensing input.
The configurable input-7 can be used as the cabin temperature analog input.
The unit has got the “Event Log” that will record last 500 events.

ü
Ýçindekiler
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit , power off
the system and seperate the electrical connection of the device from the system.
Keep the power off until all of the wiring is completed so that electric shock and trouble with
the unit can be prevented.
To reduce the effect of electrical noise on device, Low voltage line (especially sensor input
cable) wiring must be separated from high current and voltage line.
If possible, use shielded cable and shield must be connected to ground only one side.
Before commissioning the device, parameters must be set in accordance with desired use.
Incomplete or incorrect configuration can cause dangerous stiuations.
Before beginning installation of this product, please read the instruction
manual and warnings below carefully.
2. Installation
Ýçindekiler
2.1 Unit Configuration
Ýçindekiler
2.2 Panel Mounting
The unit is designed for panel mounting. Fixing is by two screw fixings.
Insert the unit in the panel cut-out from the front.
Insert the fixings in the slotted at the corners of the unit and tighten the fixing screws to secure
the unit against the panel.
1-
2-
During the equipment is putted in hole on the metal panel while mechanical
installation some metal burrs can cause injury on hands, you must be careful.
Figure 2.1 Front View Figure 2.2 Panel Cut-Out
The unit can be programmed using the buttons and LCD display on the front panel or PC
Software.
2
182mm
135mm
152mm
229mm
!
!

2.3 Electrical Connection
3
TRANS-AMF three phase connections schematic
1- Connect the unit as shown in the appropriate diagram. Be sure to connect the battery
supply the right way round and battery negative should be grounded.
2- The CAN interface requires that a 120 Ohms terminator is fitted to each end of the
communications link. This termination resistor is fitted internally into the unit. So it is not
required externally. The screen is grounded at one end ONLY.
Screened cable must be used for connecting the Magnetic Pickup, ensuring that the
screen is grounded at one end ONLY.
i
3-
4- Current transformers secondary should be grounded. The CT of 5VA s recommended.
!
25
Level Sender or
Configurable Analog Input-1
Temperature Sender
Oil Sender
24 23
35 21
22
BATTERY -
BATTERY +
40
42 41
5A
BATTERY +
27 26
Configurable Analog Input-2
Sender Common
18 19
17
H(+) L(-)
J1939 ECUs
34 33
BATTERY -
32 31 30 29 28
High Temperature or
Configurable Input-5
Low Oil Pressure or
Configurable Input-4
Water Level or
Configurable Input-3
Configurable Input-2
Configurable Output-5
Configurable Output-6
5A
To Engine
Earth
USB
SCR
FUSE-7
FUSE-8
*
*IT CAN BE USED
AS A DIGITAL INPUT
BY SELECTING
FROM THE PROGRAM
PARAMETERS
***
3
1
Configurable Output-3
39 38 37 36
Configurable Output-4
TRANSISTOR OUTPUTS
MAX. 1 A
BATTERY +
20
-(SCR) +
MPU
2
Emergency Stop or
Configurable Input-1
Configurable Input-6
62
73
8
8A
8A
14
910 5
L1
GENERATOR
MAINS
L2
L3
N
M
LOAD
G
L1
L2
L3
N
Electrical interlock
Mechanical interlock
11 12 13 14 15 16
Mains
Contactor
Relay
Generator
Contactor
Relay
FUSE 1-
FUSE 2-
FUSE 3-
FUSE-4
FUSE-5
FUSE-6
4
!
!!
!
Fuel Or Output-1Configurable
Crank Or Output-2Configurable
D+(W.L.)
Charge Alt.
Max. 300VVMax. 300VV
Cabin Temperature or
Configurable Input-7
FUSE FUSE FUSE-5, FUSE-6 FUSE-3, FUSE-4 8A. T
FUSE-7 6A. T
FUSE-8 Max. 10A. T
-1, -2, 2A. T
44 45
43
A(+) B(-)
RS-485
(Optional)

4
MAINS
V12: 380V V1 V
Wait for start
: 220
V23: 380V V2: 220V
V31: 380V V3: 220V
3. Changing And Saving Parameters Values
ü
Operation Screen
When the Prog button is
pressed, the parameters
section is asked for
accessing to parameters.
ü
ü ü
üü
ü ü
ü ü
üü
Press the Up or
Down buttons to
select the section
you wish to
view/change.
Press the
Enter
button.
Enter password
with cursor (Right,
Left,
) .
Up and
Down buttons
Press the Enter button to confirm
password. If the password is
incorrect, the unit will drop out of
program mode.
Press the Up or
Down buttons to
select the main
parameter group
you wish to
view/change.
Note1: If Enter button is pressed
and the technician password is
zero, Password screen is ignored.
Press Enter button to access to
all parameters page in currently
main parameter group.
Parameter can be
changed with Up
and Down buttons.
Press Enter button to
confirm the changed value.
PROGRAM
Operator setting
Technician setting
Factory adjustment
PROGRAM
Operator setting
Technician setting
Factory adjustment
TECHNICIAN SETTING
Password
0162
TECHNICIAN SETTING
Password
0000
TECHNICIAN SETTING
System
Mains
Generator
Engine
TECHNICIAN SETTING
System
Mains
Generator
Engine
GENERATOR
Volt level
Frequency level
Current level & act.
Power level
GENERATOR VOLT LEVEL
Under volt shutdown
320 Vac
GENERATOR VOLT LEVEL
volt reset
Over volt shutdown
Under volt shutdown
Under volt prealarm
Under
Press the Enter
button to view
parameter value.
Press Enter button to
access to all parameters in
currently parameter page.
GENERATOR VOLT LEVEL
Under volt shutdown
325 Vac
GENERATOR VOLT LEVEL
volt reset
Over volt shutdown
Under volt shutdown
Under volt prealarm
Under
Operation
Screen
GENERATOR
Volt level
Frequency level
Current level & act.
Power level
When the Escape button is
pressed any time, previous
page can be accessed.
MAINS
V12: 380V V1 V
Wait for start
: 220
V23: 380V V2: 220V
V31: 380V V3: 220V
To exit from
programming mode any
time, press Prog button.

5
Note: dis = disable
600
60
60
60
600
600
600
VV
VV
VV
VV
60
Min DefaultMAINS VOLT LEVEL ( )Mains->Volt level Max
Mains Under Voltage
Mains Under Voltage Reset
Mains Over Voltage
Mains Over Voltage Reset
320
340
440
420
Under volt trip
4.1 Operator Parameters
Under volt reset
Over volt trip
Over volt reset
Unit
4. Parameters
Min DefaultMAINS FREQ. LEVEL ( )Mains-> levelFrequency Max
Mains Under Frequency
Hz
Hz
Hz
Hz
20.0 75.0
20.0 75.0
20.0 75.0
20.0 75.0
45.0
48.0
55.0
52.0
Mains Under Frequency Reset
Mains Over Frequency
Mains Over Frequency Reset
Under freq trip
Under freq reset
Over freq trip
Over freq reset
Unit
600
60(dis)
60
60
600
600
600
VV
VV
VV
VV
60(dis)
Min Default
Max
Generator Under Voltage Shutdown
Generator Under Voltage Pre-Alarm
Generator Under Voltage Pre-Alarm Reset
Generator Over Voltage Shutdown
Generator Over Voltage Pre-Alarm
320
340
350
440
60(dis) 600
60 600
420
400
Generator Over Voltage Pre-Alarm Reset
VV
VV
Under volt shutdown
Under volt prealarm
Under volt reset
Over volt shutdown
Over volt prealarm
Over volt reset
Unit
Shutdown delay time
Generator Voltage Shutdown Delay Time
GENERATOR VOLT LEVEL ( )Generator-> levelVolt
0.0 10.0 1.0 Sec
75.0
30.0(dis)
75.0
75.0
Hz
30.0(dis)
Min Default
Max
Generator Under Frequency Pre-Alarm
Generator Under Frequency Pre-Alarm Reset
Generator Over Frequency Shutdown
Generator Over Frequency Pre-Alarm
Generator Over Frequency Pre-Alarm Reset
45.0
46.0
58.0
55.0
54.0
Generator Frequency Shutdown Delay Time
Hz
Hz
Hz
Hz
30.0
30.0(dis)
30.0
75.0
75.0
Under freq prealarm
Under freq reset
Over freq shutdown
Over freq prealarm
Over freq reset
Shutdown delay time
Unit
GENERATOR LEVEL ( )FREQ Generator-> levelFrequency
75.0
75.0
Hz
30.0
Nominal Alternator Frequency 50.0
43.0 Hz
Nominal frequency
Under freq shutdown Generator Under Frequency Shutdown 30.0(dis)
0.0 10.0 1.0 Sec
4.1.1 Mains
4.1.2 Generator
Min Default
Max
Generator Under Current Pre-Alarm Reset
Generator Over Current IDMT Alarm
Generator Over Current Set
Generator Over Current Pre-Alarm
Generator Over Current Pre-Alarm Reset
Under cur. reset
Over cur. IDMT alarm
Over cur. set
Over cur. prealarm
Over cur. reset
Unit
GENERATOR ( )CUR LEVEL Generator->Current level
Generator Under Current Set
Under cur. set
Under cur. prealarm Generator Under Current Pre-Alarm
0 9999 9980 AV
0
0(dis)
0
0
0(dis)
9999
9999
9999
9999
9999
1
dis
5
DISBL
9999
9990
AV
AV
AV
AV
AV
ENABL/DISBL

6
Note: dis = disable
Min Default
Max
Working Calendar Disable or Enable
Working Calendar Work Start Time on Monday
Working Calendar Work Stop Time on Monday
Working Calendar Work Start Time on Tuesday
Working Calendar Work Stop Time on Tuesday
Working Calendar Work Start Time on Wednesday
Working Calendar Work Start Time on Thursday
Working Calendar Work Start Time on Friday
Working Calendar Work Start Time on Saturday
Working Calendar Work Start Time on Sunday
Disable/enable select
Start time on monday
Stop time on monday
Start time on tues.
Stop time on tuesday
Start time on wednes.
Start time on thurs.
Start time on friday
Start time on satur.
Start time on sunday
Unit
Stop time on wednes.
Stop time on thursday
Stop time on friday
Stop time on saturday
Stop time on sunday
Working Calendar Work Stop Time on Wednesday
Working Calendar Work Stop Time on Thursday
Working Calendar Work Stop Time on Friday
Working Calendar Work Stop Time on Saturday
Working Calendar Work Stop Time on Sunday
GEN ( )WORKING CALENDAR Generator->Working calendar
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
23.59
23.59
23.59
23.59
23.59
23.59
23.59
DISBL ENABL/ DISBL
9999
9999
9999
9999
9999
9999
kVA
kVA
kVA
kVA
0
0(dis)
0
0
0(dis)
0
Min Default
Max
Generator Under SetPower
Generator Under Pre-AlarmPower
Generator Under Pre-Alarm ResetPower
Generator Over SetPower
Generator Over Pre-AlarmPower
0
5
Generator Over Pre-Alarm ResetPower
kVA
kVA
Under setpower
Under prealarmpower
Under resetpower
Over setpower
Over prealarmpower
Over resetpower
Unit
Reverse power set
Reverse Power Set
GEN LEVEL ( )POWER Generator->Power level
-9999 0 0 kW
dis
0
0
dis
Generator Over IDMT AlarmPower
Over IDMT alarmpower
ENABL/DISBL DISBL
Generator Over Load Step 1
Generator Over Load Step 1 Reset
0
0
9999
9999
9999
9999
KVA
KVA
Over load step 1
Over load step 1 rest
Generator Over Load Step 2
Generator Over Load Step 2 Reset
0
0
9999
9999
9999
9999
KVA
KVA
Over load step 2
Over load step 2 rest

4.2 Technician Parameters
4.2.1 System
Min Default
Max
Current Transformer Ratio
Earth Fault Current Transformer Ratio
Voltage Transformer Ratio
Select AC system;
Generator Phase Sequence (dis, L123 or L321)
Generator kVA rating set
Power unit
Current Transformer Location;
kVA kW kVAr point position;, ,
CT ratio
Earth fault CT ratio
PT ratio
Type of AC system
Phase sequence
Generator kVA rating
Power unit
CT location
kVA,kW,kVAr point
Unit
SYSTEM NETWORK ( )System->Network
9999
3
9999
100
kVA
1
0
0
1
100
1
300
kVA
1
DISBL
0- 1 Phase 2 Wire
1- 3 Phase 4 Wire
2- 2 Phase 3 Wire L1-L2
3- 2 Phase 3 Wire L1-L3
DISBL, L123, L321
99991 100
kVA/kW
3
1
0
0
0
0
0-> 0
1-> 0.0
2-> 0.00
3-> 0.000
0-> Generator
1-> Load
0-LAST MODE
1-AUTO MODE
2-TEST MODE
3-MANUAL MODE
4-STOP MODE
0-LAST
MODE
Power on mode
Power On Mode Selection
7
Min Default Unit
BREAKERS ( )System->Breakers
Max
Hardware Breaker Selection
Gen Close Breaker Contact Type
Gen Close Breaker Relay Type
Gen Close Timer
0
Gen Open Breaker Relay Type
0 2
Gen Open Timer
Mains Close Breaker Contact Type
Mains Close Breaker Relay Type
Mains Close Timer
NO / NC 0
NOR / PULS
5
1 250
0
Sec
0
NOR / PULS
0
1 250 5
0
NOR / PULS
0
1 250 5
5
NOR / PULS
0.0
0.0
0
10.0
10.0
250 2
Mains Open Breaker Relay Type
Mains Open Timer
Breaker Close Pulse Time
Breaker Open Pulse Time
Transfer Time
Spring Loading Time
Retry Number
NO / NC
Gen.brk.cls.contact
Gen.brk.cls.relay
Gen.brk.cls.time
Gen.brk.open relay
Gen.brk.open time
Type of Breaker
Mains.brk.cls.relay
Mains.brk.cls.time
Mains.brk.open relay
Mains.brk.open time
Break.close puls.time
Mains.brk.cls.contact
Transfer time
Spring loading time
Retry number
Break.open pulse time
Sec
Sec
1 250
0.5
0.5
Sec
Sec
Sec
Sec
Sec
3
5
1 250
1 250
Note:
NO / NC : Normally Open / Normally Close
NOR / PULS : Normal / Pulse
dis = disable

8
Min DefaultDATE & TIME SET ( )System->Date & time set Max
Year
Month
0 99
112
Date 131
Day of week 17
Hour 023
Minute 059
Second 059
Year
Month
Day
Week
Hour
Minute
Second
Unit
Min Default Unit
COMMUNICATION ( )System->Communication Max
Slave Address 1
1 247
05 3
Baud Rate: 0 - 1200 baud
1 - 2400 baud
2 - 4800 baud
3 - 9600 baud
4 - 19200 baud
5 - 38400 baud
Datalog Period
Timeout
ModBus ASCII/RTU Selection
Stop Bit (0-> 1 stop bit,1-> 2 stop bit)
020
0.0(dis)
0(dis)
0
999.9
999
1
1.0
3
ASCII
0
Slave address
Baud rate
Parity
Datalog period
Timeout
ASCII/RTU selection
Stop bit
Parity: 0-> None, 1-> Odd, 2-> Even
Min
Min
ASCII / RTU
Note: dis = disable
Min Default Unit
PASSWORD SETTINGS ( )System->Password settings Max
Operator Password
Technician Password
0
0 9999
09999 0
Operator password
Technician password
Min Default Unit
DEFAULT SETTINGS ( )System->Default settings Max
Save setting to default
Reset default sets
Save setting to def.
Reset default sets
YES / NO NO
Reset factory sets
Reset factory sets
YES / NO NO
YES / NO NO
Min Default Unit
LCD DISPLAY ( )System->LCD display Max
Language Selection
Contrast Setting
ENGLISH/CHINESE
5
4 9
Contrast
Auto backlight off
Language
Auto Scroll Time
Auto Scroll Number
Scroll Time For Error Messages
Back To Genset Screen
0
0 (dis) 250 Sec
5
24
2
0 (dis)
1
0 (dis)
250
250
Auto scroll number
Err. mesg scroll time
Back to genset screen
Auto scroll time
Sec
Sec
1
ENGLISH
Auto Backlight Off
0-DISABLE
1-ENABLE
2-ENABLE(only when engine is not running)
0
02

600
60(dis)
60
60
600
600
600
VV
VV
VV
VV
60(dis)
Min Default
Max
Generator Under Voltage Shutdown
Generator Under Voltage Pre-Alarm
Generator Under Voltage Pre-Alarm Reset
Generator Over Voltage Shutdown
Generator Over Voltage Pre-Alarm
320
340
350
440
60(dis) 600
60 600
420
400
Generator Over Voltage Pre-Alarm Reset
VV
VV
Under volt shutdown
Under volt prealarm
Under volt reset
Over volt shutdown
Over volt prealarm
Over volt reset
Unit
Shutdown delay time
Generator Voltage Shutdown Delay Time
GENERATOR VOLT LEVEL ( )Generator-> levelVolt
0.0 10.0 1.0 Sec
75.0
30.0(dis)
75.0
75.0
Hz
30.0(dis)
Min Default
Max
Generator Under Frequency Pre-Alarm
Generator Under Frequency Pre-Alarm Reset
Generator Over Frequency Shutdown
Generator Over Frequency Pre-Alarm
Generator Over Frequency Pre-Alarm Reset
45.0
46.0
58.0
55.0
54.0
Generator Frequency Shutdown Delay Time
Hz
Hz
Hz
Hz
30.0
30.0(dis)
30.0
75.0
75.0
Under freq prealarm
Under freq reset
Over freq shutdown
Over freq prealarm
Over freq reset
Shutdown delay time
Unit
GENERATOR LEVEL ( )FREQ Generator-> levelFrequency
75.0
75.0
Hz
30.0
Nominal Alternator Frequency 50.0
43.0 Hz
Nominal frequency
Under freq shutdown Generator Under Frequency Shutdown 30.0(dis)
0.0 10.0 1.0 Sec
4.2.3 Generator
600
60
60
60
600
600
600
VV
VV
VV
VV
60
Min DefaultMAINS VOLT LEVEL ( )Mains->Volt level Max
Mains Under Voltage
Mains Under Voltage Reset
Mains Over Voltage
Mains Over Voltage Reset
320
340
440
420
Under volt trip
4.2.2 Mains
Under volt reset
Over volt trip
Over volt reset
Unit
Min DefaultMAINS FREQ. LEVEL ( )Mains-> levelFrequency Max
Mains Under Frequency
Hz
Hz
Hz
Hz
20.0 75.0
20.0 75.0
20.0 75.0
20.0 75.0
45.0
48.0
55.0
52.0
Mains Under Frequency Reset
Mains Over Frequency
Mains Over Frequency Reset
Under freq trip
Under freq reset
Over freq trip
Over freq reset
Unit
9
Note: dis = disable
Min Default Unit
MAINS ( )ACTIONS Mains->Actions Max
Mains Failure Detection En/Dis:
Look Mains Failure at Stop Mode En/Dis
Always Look Mains Return Delay
Mains failure detect
Mains fail.stop mode
Always return delay
1
ENABL/DISBL
ENABL/DISBL
ENABL
DISBL
0-
1-
2-
DISABLE
ENABLE
ENABLE ON REMOTE
20

10
Min Default
Max
Generator Under Current Pre-Alarm Reset
Generator Under Current Actions Delay Time
Generator CurrentOver IDMT Alarm
Generator Over Current Set
Generator Over Current Pre-Alarm
Generator Over Current Pre-Alarm Reset
Generator Over Current Actions Delay Time
Generator Short Circuit Current Set
Generator Earth Fault Current Set
Generator Earth Fault Current Actions Delay Time
Under cur. reset
Under cur. act.
Under act. delay time
Over cur. IDMT alarm
Over cur. set
Over cur. prealarm
Over cur. reset
Over cur. act.
Over act. delay time
Short circuit cur.
Earth fault cur.
Earth fault cur. act.
E.F. act. delay time
Unit
GEN ( )CUR LEVEL & ACT Generator->Current level & act.
Generator Under Current Set
Under cur. set
Under cur. prealarm Generator Under Current Pre-Alarm
0
0(dis)
0
0
0
0(dis)
0
9999
3
99
9999
9999
3
99
9980
dis
2
9999
100
dis
2
AV
AV
AV
0
0(dis)
0
0(dis)
0
0
0(dis)
9999
9999
9999
3
99
9999
9999
1
dis
5
dis
2
9999
9990
AV
AV
AV
AV
AV
Sec
Sec
Sec
Generator Under Current Actions
Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
Shutdown (Alarm And Shutdown)
0 -
1 -
2 -
3 -
Generator Over Current Actions
Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
Shutdown (Alarm And Shutdown)
0 -
1 -
2 -
3 -
Generator Earth Fault Current Actions
Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
Shutdown (Alarm And Shutdown)
0 -
1 -
2 -
3 -
Unbalance Load Set
Unbalance Load Actions Delay Time
Unbalance load set
Unbalance load act.
Unbalance act. delay
0
0(dis)
0
9999
3
99
0
dis
2
AV
Sec
Unbalance Load
0 -
1 -
2 -
3 -
Actions
Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
Shutdown (Alarm And Shutdown)
ENABL/DISBL DISBL
Note: dis = disable

11
9999
9999
9999
9999
9999
9999
kVA
kVA
kVA
kVA
0
0(dis)
0
0
0(dis)
0
Min Default
Max
Generator Under SetPower
Generator Under Pre-AlarmPower
Generator Under Pre-Alarm ResetPower
Generator Over IDMT AlarmPower
Generator Over SetPower
Generator Over Pre-AlarmPower
0
5
Generator Over Pre-Alarm ResetPower
kVA
kVA
Unit
Generator Over Delay TimePower Action
Generator Over Load Step 1
Generator Over Load Step 1 Reset
Generator Over 1 Delay TimeLoad Step Action
Reverse Power Set
Reverse Power Action Delay Time
0
0
0
0(dis)
0
-9999
0(dis)
0
99
9999
9999
3
999.9
0
3
99
2
9999
9999
0(dis)
30.0
0
0(dis)
2
Sec
KVA
KVA
Sec
kW
Sec
dis
0
0
dis
Reverse Power Actions
Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
Shutdown (Alarm And Shutdown)
0 -
1 -
2 -
3 -
Under setpower
Under prealarmpower
Under resetpower
Over IDMT alarmpower
Over setpower
Over prealarmpower
Over resetpower
Over act. delay time
Over load step 1
Over load step 1 rest
Over load step 1 act.
Over load step 1 dly.
Reverse power set
Reverse power act.
Rv.pow.act.delay time
GEN LEVEL ( )POWER Generator->Power level
Generator Under Delay TimePower Action
0(dis)
0
3
99
0(dis)
2Sec
Generator Under Actions
Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
Shutdown (Alarm And Shutdown)
Power
0 -
1 -
2 -
3 -
Under power act.
Under act. delay time
0(dis) 3 0(dis)
Generator Over Actions
Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
Shutdown (Alarm And Shutdown)
Power
0 -
1 -
2 -
3 -
Over power act.
ENABL/DISBL DISBL
Generator Over Actions
Disable
Warning
Warning
Load Step 1
0 -
1 - Status
2 - Non-Latching
3 - Latching
Generator Over Load Step 2
Generator Over Load Step 2 Reset
Generator Over Delay TimeLoad Step 2 Action
0
0
0(dis)
0
9999
9999
3
999.9
9999
9999
0(dis)
30.0
KVA
KVA
Sec
Over load step 2
Over load step 2 rest
Over load step 2 act.
Over load step 2 dly.
Generator Over Actions
Disable
Warning
Warning
Load Step 2
0 -
1 - Status
2 - Non-Latching
3 - Latching
Note: dis = disable

12
Note: dis = disable
Min Default
Max
Working Calendar Disable or Enable
Working Calendar Work Start Time on Monday
Working Calendar Work Stop Time on Monday
Working Calendar Work Start Time on Tuesday
Working Calendar Work Stop Time on Tuesday
Working Calendar Work Start Time on Wednesday
Working Calendar Work Start Time on Thursday
Working Calendar Work Start Time on Friday
Working Calendar Work Start Time on Saturday
Working Calendar Work Start Time on Sunday
Disable/enable select
Start time on monday
Stop time on monday
Start time on tues.
Stop time on tuesday
Start time on wednes.
Start time on thurs.
Start time on friday
Start time on satur.
Start time on sunday
Unit
Stop time on wednes.
Stop time on thursday
Stop time on friday
Stop time on saturday
Stop time on sunday
Working Calendar Work Stop Time on Wednesday
Working Calendar Work Stop Time on Thursday
Working Calendar Work Stop Time on Friday
Working Calendar Work Stop Time on Saturday
Working Calendar Work Stop Time on Sunday
GEN ( )WORKING CALENDAR Generator->Working calendar
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
23.59
23.59
23.59
23.59
23.59
23.59
23.59
DISBL ENABL/ DISBL
Min Default Unit
GENERATOR GENERAL ( )Generator->General Max
Sensing Options Generator Frq En/Dis
Sens.option gen.freq ENABL
ENABL/DISBL
0( )dis
Sensing Opt Pickup En/Dis & Flywheel DISBL1000
All Warnings Are Latched En/Dis
Changed To Stop Mode On Shutdown Fail
Sens.opt.pickup&flywh
All warning are latch
Stop mode on shutdown
ENABL/DISBL
ENABL/DISBL
DISBL
DISBL
Min Default Unit
ENG. CRANK DISCONNECT ( )Engine->Crank disconnect Max
Crank Disconnect On Gen. Frequency
Crank Disconnect On Gen. Voltage
Crank Disconnect On Charge Alt. Voltage
30.0
Crank Disconnect On Oil Pressure En/Dis
Crank Disconnect On Oil Pressure Value
Check Oil Pressure Before Start
10.0 75.0 Hz
500
100
1.0
6000 RPM
300
60 (dis) 600 VV
dis
6.0 (dis) 30.0 VZ
1.0
30.0 BAR
Generator frequency
Engine speed
Generator volt
Charge alt. volt
Oil pres. enab./dis.
Oil pressure value
Check oil befor.start
Crank Disconnect On Engine RPM
4.2.4 Engine
ENABL/DISBL
Sec
Min Default Unit
ENGINE START OPTIONS ( )Engine->Starting options Max
Audible Alarm Prior To Starting En/Dis
Number Of Start Attempts
Cranking Time
Crank Rest Time
DISBL
3
5
1
1
10
99
10
5 99
Pickup Sensor Fail Delay
1.0
0.1 10.0
Horn prior start
No. of crank attemp
Cranking time
Crank rest time
Pickup fail dely
Sec
Sec
ENABL/DISBL
Min Default Unit
ENGINE SPEED SETS ( )Engine->Speed settings Max
Engine Under Speed Shutdown
Engine Under Speed Prealarm
Engine Under Speed Prealarm Reset
dis
Engine Over Speed Shutdown
500(dis) 5000
500(dis) RPM
500
500 5000
Engine Over Speed Prealarm Reset
Engine Speed Shutdown Delay Time
500
1.0
RPM
RPM
RPM
RPM
RPM
Sec
5000
500(dis) 5000
5000
5000
10.0
Engine Over Speed Prealarm
Under speed shutdown
Under speed prealarm
Under speed reset
Over speed shutdown
Over speed prealarm
Over speed reset
Shutdown delay time
500
0.0
Nominal Speed 1500
500 5000 RPM
Nominal speed
dis
dis
dis
500(dis)
DISBL
ENABL/DISBL ENABL

13
Note: dis = disable
Min Default
ENGINE PLANT BATTERY ( )Engine->Plant battery Max
Battery Undervolts Shutdown
Battery Undervolts Warning
Battery Undervolts Warning Reset
Battery Undervolts Volts Delay
Battery Overvolts Shutdown
Battery Overvolts Warning
11.0
Battery Overvolts Warning Reset
6.0(dis)
6.0(dis)
30.0
30.0
11.5
6.0
1.0
0.0 120.0
29.0
28.5
Charge Alternator Warning dis
30.0
30.0
30.0
6.0 30.0
Battery Overvolts Delay 1.0
0.0 120.0
30.0
6.0(dis)
6.0(dis)
6.0(dis)
Under volt shutdown
Under volt warning
Under volt reset
Under volt delay
Over volt shutdown
Over volt warning
Over volt reset
Over volt delay
Alt. chg. warning
Unit
VZ
VZ
VZ
VZ
VZ
VZ
Sec
Sec
VZ
dis
dis
CANBUS ECU ( )Engine->CanBus ECU
Baud rate
J1939 ECU type
Device address
SPN version
Min Default UnitMax
07 4
31 0
0 255 17
1 3 1
kBaud
ECU remote control
Speed control enable
Oil pres cont. enab
Temp. control enable
ENABL
Device Address
0(dis)
SPN version
ECU Remote Control via J1939
Speed Control via J1939
Oil Pressure Control via J1939
Coolant Temperature Control via J1939
Speed correction 50
Speed Correction Value
%
0 100
Speed set point 1500
1500 1800/
Speed Set Point Selection
RPM
ENABL/DISBL
ENABL/DISBL
ENABL/DISBL
ENABL/DISBL
ENABL
DISBL
DISBL
Baud Rate:
0: 20, 1: 50, 2: 100, 3: 125,
4: 250, 5: 500, 6: 800, 7: 1.000
J1939 ECU Type Selection:
0 - Disable
1 - Standard
2 - Volvo EMS1
3 - Volvo EMS2
4 - Volvo EMS2b
5 - Volvo EDC3
6 - Volvo EDC4
7 - Deutz EMR2
8 - Deutz EMR3
9 - Perkins 1300
10 - Perkins ADEM3
11 - Perkins ADEM4
12 - Scania S6
13 - MAN MFR
14 - Cummins ISB
15 - Cummins CM570
16 - Cummins CM850
17 - Cummins CM2150E
18 - Cummins CM2250
19 - Detroit DDEC
20 - John Deere
21 - MTU ADEC
22 - MTU ECU8
23 - MTU ECU8 SAM
24 - Yuchai
25 - Kubota
26 - Baudouin WISE10B
27 - Baudouin WISE15
28 - Perkins 1600
29 - Perkins A4E2
30 - Perkins A5E2
31 - Perkins A5E2v2

14
Note: dis = disable
Min Default Unit
CANBUS ERROR SET ( )Engine->CanBus error set Max
Can Fault Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
0
0 2
0
0(dis) 4
CAN fault activation
CAN fault actions
SecCan Fault Delay 10
2 250
CAN fault delay
Can Fault Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
J1939 Amber Warning Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
2
0 2
0
0(dis) 4
Amber warn.activation
Amber warn.actions
SecJ1939 Amber Warning Lamp Delay 2
0 250
Amber warn.delay
J1939 Amber Warning Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
J1939 Red Stop Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
2
0 2
0
0(dis) 4
Red stop activation
Red stop actions
SecJ1939 Red Stop Lamp Delay 2
0 250
Red stop delay
J1939 Red Stop Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active

Min Default
LOAD TEST ( )Engine->Load test Max Unit
1-NO LOAD
Disable/enable select Disable, No Load or On Load Selection 0-DISABLE
1-NO LOAD
2-ON LOAD
15
Note: dis = disable
Min Default
ENGINE MAINTENANCE ( )Engine->Maintenance Max
Running Hours Interval
Maintenance Date Interval
Force Engine Shutdown When Maintenance Is Due
Engine Running Hour
5000
0(dis) 9999
ENABL/DISBL
0
0 30000
DISBL
0(dis) 12 6
Maint. date interval
Eng. stop when maint
Engine running hour
Running hour interval
Unit
Hour
Month
Maintenance Okay NO
Maintenance okay YES/NO
Min Default
Max
Exercise Disable or Enable
Exercise Start Time on Monday1
Exercise Start Time on Monday2
Exercise Start Time on Monday3
Exercise Start Time on Monday4
Exercise Stop Time on Monday1
Exercise Stop Time on Monday2
Exercise Stop Time on Monday3
Exercise Stop Time on Monday4
Exercise Start Time on Tuesday1
Exercise Start Time on Tuesday2
Exercise Start Time on Tuesday3
Exercise Start Time on Tuesday4
Exercise Stop Time on Tuesday1
Exercise Stop Time on Tuesday2
Exercise Stop Time on Tuesday3
Exercise Stop Time on Tuesday4
Exercise Start Time on Wednesday1
Exercise Start Time on Wednesday2
Exercise Start Time on Wednesday3
Exercise Start Time on Wednesday4
Exercise Start Time on Thursday1
Exercise Start Time on Thursday2
Exercise Start Time on Thursday3
Exercise Start Time on Thursday4
Disable/enable select
Start time on monday1
Start time on monday2
Start time on monday3
Start time on monday4
Stop time on monday1
Stop time on monday2
Stop time on monday3
Stop time on monday4
Start time on tues.1
Start time on tues.2
Start time on tues.3
Start time on tues.4
Stop time on tuesday1
Stop time on Tuesday2
Stop time on tuesday3
Stop time on tuesday4
Start time on wednes.1
Start time on wednes.2
Start time on wednes.3
Start time on wednes.4
Start time on thurs.1
Start time on thurs.2
Start time on thurs.3
Start time on thurs.4
Unit
Stop time on wednes.1
Stop time on wednes.2
Stop time on wednes.3
Stop time on wednes.4
Stop time on thurs1 .
Stop time on thurs2 .
Stop time on thurs3 .
Stop time on thurs4 .
Exercise Stop Time on Wednesday1
Exercise Stop Time on Wednesday2
Exercise Stop Time on Wednesday3
Exercise Stop Time on Wednesday4
Exercise Stop Time on Thursday1
Exercise Stop Time on Thursday2
Exercise Stop Time on Thursday3
Exercise Stop Time on Thursday4
EXERCISE ( )Engine->Exercise
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
DISBL ENABL/ DISBL

16
Note: dis = disable
Min Default Unit
ENGINE GENERAL ( )Engine->General Max
Engine Fuel Selection 1-DIESEL
Stop Solenoid Time 1 2099
Ignition Delay 1 599 Sec
Gas Valve Delay 1 599 Sec
Minimum Ignition Speed 10 2001500 RPM
Fuel selection
Stop solenoid time
Ignition delay
Gas valve delay
Min. of ignition speed
Sec
Choke time Choke Time Sec
0.0 0.830.0
0-GAS
1-DIESEL
2-GASOLINE
Exercise Start Time on1 Friday
Exercise Start Time on2 Friday
Exercise Start Time on3 Friday
Exercise Start Time on4 Friday
Exercise Start Time on1 Saturday
Exercise Start Time on2 Saturday
Exercise Start Time on3 Saturday
Exercise Start Time on4 Saturday
Exercise Start Time on day1 Sun
Exercise Start Time on day2 Sun
Exercise Start Time on day3 Sun
Exercise Start Time on day4 Sun
Exercise Stop Time on1 Friday
Exercise Stop Time on2 Friday
Exercise Stop Time on3 Friday
Exercise Stop Time on4 Friday
Exercise Stop Time on day1 Satur
Exercise Stop Time on day2 Satur
Exercise Stop Time on day3 Satur
Exercise Stop Time on day4 Satur
Exercise Stop Time on day1 Sun
Exercise Stop Time on day2 Sun
Exercise Stop Time on day3 Sun
Exercise Stop Time on day4 Sun
Start time on day1 fri
Start time on day2 fri
Start time on day3 fri
Start time on day4 fri
Start time on1 satur.
Start time on2 satur.
Start time on3 satur.
Start time on4 satur.
Start time on day1 sun
Start time on day2 sun
Start time on day3 sun
Start time on day4 sun
Stop time on day1 fri
Stop time on day2 fri
Stop time on day3 fri
Stop time on day4 fri
Stop time on1 satur.
Stop time on2 satur.
Stop time on3 satur.
Stop time on4 satur.
Stop time on day1 sun
Stop time on day2 sun
Stop time on day3 sun
Stop time on day4 sun
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

17
4.2.5 Inputs
Note : These sensor types can only be used in the Trans-AMF.RS485 units.
The USB communication interface can not be used when one of these sensor types is
selected.
*1
Min Default Unit
SENDER INPUTS ( )Inputs->Sender inputs Max
Oil Pressure Input Type
Oil Pressure Pre-Alarm
Oil Pressure Pre-Alarm Reset
Coolant Temperature Input Type
1.2
0.0 (dis) 30.0 BAR
1.4
0.0 30.0 BAR
1.0
0.0 30.0 BAR
0 - Not Used (Disable)
1 - Digital NC
2 - Digital NO
3 - VDO 5 BAR
4 - VDO 7 BAR
5 - VDO 10 BAR
6 - DATCON 5 BAR
7 - DATCON 7 BAR
8 - MURPHY 7 BAR
9 - User Configured
90
0 (dis) 300
88
0 300
95
0 300
Temperature Sensor Break
High Temperature Pre-Alarm
Oil Pressure Shutdown
High Temp. Pre-Alarm Reset
High Temperature Shutdown
C
C
C
Temp. sensor break
High temp. prealarm
High temp. reset
High temp. shutdown
Conf. AI1 type
Temp. input type
Oil pressure shutdown
Oil pressure reset
Oil pressure prealarm
Oil press. input type
0 (dis) 70
Low Temperature Warning C
Low temp. warning
Conf. AI1 unit
Configurable Analog Input-1 Type
0 (dis)
0 - Not Used (Disable)
1 - Digital NC
2 - Digital NO
3 -
4 - 5
5 - DATCON
6 - MURPHY
7 - PT100
8 - User Configured
VDO 120 ºC
VDO 1 0 ºC
0 (dis)
0- Not Used (Disable)
1- Digital NC
2- Digital NO
3- VDO OHM (10-180)
4- VDO TUBE (90-0)
5- US OHM (240-33)
6- ELS11 OHM (0-190)
7- FORD (73-10)
8- ELS13 OHM (0-190)
9- ELS30 OHM (0-190)
10- DAVITEQ (RS485)
11- KUS CLS2 (RS485)
12- MSLL 790 (RS485)
13- CSFL 790 (RS485)
14- User Configured
*1
*1
*1
*1
0 (dis)
0 (dis)
Oil Pressure Unit
Oil pressure unit BARBAR/PSI/KPA
Coolant Temperature Unit
Temperature unit ºCºC/ºF
BAR/PSI/KPA/ºC/ºF/%/Lt %
Configurable Analog Input-1 Unit
0 (dis)
0 (dis) 300
Coolant Heater Control On C
Heater control ON
0300
Coolant Heater Control Off C
Heater control OFF
45
5
0 9999
Water Pump On Time
Water pump on time
09999
Water Pump Off Time Sec
Water pump off time
5
Sec
0 - Disable
1 - Enable From Safety
On (3min. delayed)
2 - Always Enable
0 (dis)

18
Note: dis = disable
Configurable Analog Input-2 Type
Conf. AI2 type
Configurable Analog Input-2 Unit
Conf. AI2 unit
0 - Not Used (Disable)
1 - Digital NC
2 - Digital NO
3 -
4 - 5
5 - DATCON
6 - MURPHY
7 - PT100
8 - User Configured
VDO 120 ºC
VDO 1 0 ºC
0 (dis) 300 ºC
0 300
300
Conf. AI2 low prealrm
ºC
ºC
0 (dis)
60
300
90
0 300
Conf. AI2 low shutdwn
Conf. AI2 high prealr
Conf. AI2 high shutd.
0 (dis)
0 (dis)
0 (dis)
0 (dis) ºC
0 (dis)
Conf. AI2 high reset
BAR/PSI/KPA/ºC/ºF/%/Lt
Config. Analog Input-2 Low Pre-Alarm
Conf. AI2 low reset
Config. Analog Input-2 Low Reset
Config. Analog Input-2 Low Shutdown
Config. Analog Input-2 High Pre-Alarm
Config. Analog Input-2 High Reset
0 (dis) 300 0 (dis)
0 (dis)
300
75
300
Conf. AI2 control ON
Conf. AI2 control OFF
0 (dis)
0
Config. Analog Input-2 High Shutdown
Config. ontrol ONAnalog Input-2 C
Config. Control OFFAnalog Input-2
ºC
ºC
ºC
ºC
ºC
0%
75
Conf. AI1 control OFF Config. Analog Input-1 control OFF
3000
0 (dis)0 (dis) 3000 %
Conf. AI1 control ON
Config. Analog Input-1 control ON
Conf. AI1 high shutd.
Config. Analog Input-1 High Shutdown
0 (dis) 3000 %
0 (dis)
0 (dis) Sec
0 (dis)
Fuel filling max.time Fuel Filling Maximum Time
30000
Fuel fill.alarm reset
Fuel consumpt. reset
Fuel tank capacity
Fuel Filling Alarm Reset
Fuel Consumption Reset
Fuel Tank Capacity
NO
NO
100
YES/NO
YES/NO
2500 Sec
0
Conf. AI1 active dely Configurable Analog Input-1 A
D ( )
ctive
elay If Conf. AI1 type is Digital
" ”
0 (dis) 3000 %
0 3000
3000
Conf. AI1 low prealrm
%
%
0 (dis)
60
3000
900 3000
Conf. AI1 low shutdwn
Conf. AI1 high prealr
0 (dis)
0 (dis)
0 (dis) %
%
0 (dis)
Conf. AI1 high reset
Config. Analog Input-1 Low Pre-Alarm
Conf. AI1 low reset
Config. Analog Input-1 Low Reset
Config. Analog Input-1 Low Shutdown
Config. Analog Input-1 High Pre-Alarm
Config. Analog Input-1 High Reset
2
4
20
0 0
Conf. A indicationI2
Conf. A activationI2
If Conf. A type is Digital
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
I2 " ”
If Conf. A type is Digital
0- Active From Starting
1- Active From Safety On
2- Always Active
I2 " ”
2500 Sec
0
Conf. A active delyI2 Configurable Analog Input-2 A
D ( I2 )
ctive
elay If Conf. A type is Digital
" ”
2
4
20
0 0
Conf. AI1 indication
Conf. AI1 activation
If Conf. AI1 type is Digital
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
" ”
If Conf. AI1 type is Digital
0- Active From Starting
1- Active From Safety On
2- Always Active
" ”
0Lt
30000

19
Min Default Unit
SENDER LINEARISATION ( )Inputs->Sender linearisation Max
Oil Pressure Sender Point-1
Oil Pressure Sender Point-2
Oil Pressure Sender Point-3
Oil Pressure Sender Point-4
Oil Pressure Sender Point-5
Oil Pressure Sender Point-6
Oil Pressure Sender Point-7
Oil Pressure Sender Point-8
Oil Pressure Sender Point-9
Oil Pressure Sender Point-10
Temperature Sender Point-1
Temperature Sender Point-2
Temperature Sender Point-3
Temperature Sender Point-4
Temperature Sender Point-5
Temperature Sender Point-6
Temperature Sender Point-7
Temperature Sender Point-8
Temperature Sender Point-9
Temperature Sender Point-10
Configurable Analog Input-1 Sender Point-1
Configurable Analog Input-1 Sender Point-2
Configurable Analog Input-1 Sender Point-3
Configurable Analog Input-1 Sender Point-4
Configurable Analog Input-1 Sender Point-5
Oil Pressure Point-1
Oil Pressure Point-2
Oil Pressure Point-3
Oil Pressure Point-4
Oil Pressure Point-5
Oil Pressure Point-6
Oil Pressure Point-7
Oil Pressure Point-8
Oil Pressure Point-9
Oil Pressure Point-10
Temperature Point-1
Temperature Point-2
Temperature Point-3
Temperature Point-4
Temperature Point-5
Temperature Point-6
Temperature Point-7
Temperature Point-8
Temperature Point-9
Temperature Point-10
Configurable Analog Input-1 Point-1
Configurable Analog Input-1 Point-2
Configurable Analog Input-1 Point-3
Configurable Analog Input-1 Point-4
Configurable Analog Input-1 Point-5
15
31
49
66
85
101
117
132
149
178
579
404
342
250
179
136
103
77
67
63
10
30
50
70
90
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
10.0
28
35
40
50
60
70
80
90
95
98
0
11
22
33
44
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
BAR
BAR
BAR
BAR
BAR
BAR
BAR
BAR
BAR
BAR
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
%
%
%
%
%
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
300
300
300
300
300
300
300
300
300
300
3000
3000
3000
3000
3000
Oil pressure sender 1
Oil pressure sender 2
Oil pressure sender 3
Oil pressure sender 4
Oil pressure sender 5
Oil pressure sender 6
Oil pressure sender 7
Oil pressure sender 8
Oil pressure sender 9
Oil pressure sender 10
Temperature sender 1
Temperature 2sender
Temperature 3sender
Temperature 4sender
Temperature 5sender
Temperature 6sender
Temperature 7sender
Temperature 8sender
Temperature 9sender
Temperature 0sender 1
Conf. AI1 sender 1
Conf. AI1 sender 2
Conf. AI1 sender 3
Conf. AI1 sender 4
Conf. AI1 sender 5
Oil pressure 1
Oil pressure 2
Oil pressure 3
Oil pressure 4
Oil pressure 5
Oil pressure 6
Oil pressure 7
Oil pressure 8
Oil pressure 9
Oil pressure 10
Temperature 1
Temperature 2
Temperature 3
Temperature 4
Temperature 5
Temperature 6
Temperature 7
Temperature 8
Temperature 9
Temperature 01
Conf. AI1 value 1
Conf. AI1 value 2
Conf. AI1 value 3
Conf. AI1 value 4
Conf. AI1 value 5

20
Configurable Analog Input-1 Sender Point-6
Configurable Analog Input-1 Sender Point-7
Configurable Analog Input-1 Sender Point-8
Configurable Analog Input-1 Sender Point-9
Configurable Analog Input-1 Sender Point-10
Configurable Analog Input-1 Point-6
Configurable Analog Input-1 Point-7
Configurable Analog Input-1 Point-8
Configurable Analog Input-1 Point-9
Configurable Analog Input-1 Point-10
110
130
150
170
190
0
0
0
0
0
1300
1300
1300
1300
1300
55
66
77
88
100
0
0
0
0
0
R
R
R
R
R
3000
3000
3000
3000
3000
Conf. AI1 sender 6
Conf. AI1 sender 7
Conf. AI1 sender 8
Conf. AI1 sender 9
Conf. AI1 sender 10
Conf. AI1 value 6
Conf. AI1 value 7
Conf. AI1 value 8
Conf. AI1 value 9
Conf. AI1 value 10
Configurable Analog Input-2 Sender Point-1
Configurable Analog Input-2 Sender Point-2
Configurable Analog Input-2 Sender Point-3
Configurable Analog Input-2 Sender Point-4
Configurable Analog Input-2 Sender Point-5
Configurable Analog Input-2 Sender Point-6
Configurable Analog Input-2 Sender Point-7
Configurable Analog Input-2 Sender Point-8
Configurable Analog Input-2 Sender Point-9
Configurable Analog Input-2 Sender Point-10
Configurable Analog Input-2 Point-1
Configurable Analog Input-2 Point-2
Configurable Analog Input-2 Point-3
Configurable Analog Input-2 Point-4
Configurable Analog Input-2 Point-5
Configurable Analog Input-2 Point-6
Configurable Analog Input-2 Point-7
Configurable Analog Input-2 Point-8
Configurable Analog Input-2 Point-9
Configurable Analog Input-2 Point-10
579
404
342
250
179
136
103
77
67
63
0
0
0
0
0
0
0
0
0
0
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
28
35
40
50
60
70
80
90
95
98
0
0
0
0
0
0
0
0
0
0
ºC
%
%
%
%
%
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
R
R
R
R
R
R
R
R
R
R
300
300
300
300
300
300
300
300
300
300
Conf. AI2 sender 1
Conf. AI2 sender 2
Conf. AI2 sender 3
Conf. AI2 sender 4
Conf. AI2 sender 5
Conf. AI2 sender 6
Conf. AI2 sender 7
Conf. AI2 sender 8
Conf. AI2 sender 9
Conf. AI2 sender 10
Conf. AI2 value 1
Conf. AI2 value 2
Conf. AI2 value 3
Conf. AI2 value 4
Conf. AI2 value 5
Conf. AI2 value 6
Conf. AI2 value 7
Conf. AI2 value 8
Conf. AI2 value 9
Conf. AI2 value 01
Other manuals for TRANS-AMF
1
Table of contents
Other EMKO Control Unit manuals
Popular Control Unit manuals by other brands

WDT
WDT Granudos 10 Touch Operating and installation instructions

Piratelogic
Piratelogic EVE Construction manual

Parallax
Parallax 28560 manual

Bosch
Bosch DS7400 operating instructions

Kemper
Kemper kHS 686 00 Installation and operating instructions

Comunello
Comunello QUAD - 24V - 2M Installation and user manual

Elvaco
Elvaco CMi2130G3 Quick manual

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-R Series user manual

Worldwide
Worldwide WORLDDRIVE WD4X quick start guide

ABB
ABB ACQ580-04 Quick installation guide

KMC Controls
KMC Controls VEB-53 Series installation guide

Simplex
Simplex MINIPLEX 4100ES Series quick start guide