
Micropilot FMR60/62/67
12 Endress+Hauser
Exceptions:
Error code 1) Current output (message type) Note
M272 ≥21.0 mA or ≤3.6 mA Main electronic failure
C484 ≥21.0 mA or ≤3.6 mA Simulation failure mode
S942 ≥21.0 mA or ≤3.6 mA In safety distance
1) The error codes are listed in the Operating Instructions.
When SIL locking is active on the device, additional diagnostics are activated (e.g. a comparison
between the readback-current with the nominal value). If one of these diagnostics results in an
error message (e.g. F803 loop current) and the SIL locking is then deactivated, the error
message remains while the error persists, even it the diagnostic is no longer active in the unlock
state. In this case, the device must be disconnected briefly from the power supply (e.g. by
unplugging the terminals). When the device is then restarted, a self-check is carried out, and
the error message is reset where applicable.
Parameter configuration for
safety-related applications
Calibration of the measuring point
Calibration of the measuring point is described in the Operating Instructions (→ 7).
Check th initial factory setting of the E (zero point) and F (range) parameters in accordance with the
desired measuring range and correct if necessary.
Methods of device configuration
When using the devices in process control safety systems, the device configuration must comply with
two requirements:
• Confirmation concept:
Proven, independent testing of safety-related parameters entered.
• Locking concept:
Locking of the device once configuration is complete (as required by IEC 61511-1 §11.6.4 and
NE79 §3).
To activate the SIL mode, the device must run through an operating sequence, during which the
device can be operated by means of the device display or any asset management tool (FieldCare,
Pactware, AMS, PDM, Field Communicator 375/475, ...) for which integration is available.
Two methods of configuring the device are provided, which differ mainly with regard to the
confirmation concept:
• "Increased safety mode"
While running through the commissioning sequence here, critical parameters which control
functions in the safety path are either set automatically by the device to safe values or transferred
to the display/operating tool via an alternative data format, to enable checking of the setting.
This mode can be used for standard applications. As there are only a few safety-related
parameters which can be freely configured, the risk of operating errors is greatly reduced, and the
level in the tank does not need to be changed during commissioning in order to check the settings.
• "Expert mode"
A larger number of safety-related parameters can be freely configured here. This means that the
device can be adapted to difficult applications. However, the settings must be checked by directly
approaching the level in the tank or a similar method.
A mechanical swivel reflector can be used for example as a method for checking in the case of
MAX monitoring. When using a swivel reflector, the device must be correctly configured in the
operating menu: Setup → Advanced setup → Level
Set: Max. filling speed liquid = Very fast > 2m (80in) /min.
A detailed description of both modes is provided in the following sections.
It is only in the case of SIL devices (ordering feature 590 "Additional Approval", option LA "SIL")
that the SIL commissioning sequence is visible on the display and in external operating tools.
For this reason, SIL locking can only be activated on these devices.