manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Ensy
  6. •
  7. Fan
  8. •
  9. Ensy AHU-400 BH Manual

Ensy AHU-400 BH Manual


Startupprocedure
for
Ensy®AHU-units
















393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage2
Informationcanbefoundonthedataplaqueinsidetheunit.Thissignshows.AHU‐400BH

Unittype:AHU‐_____________

Serialno:010______________.____/_____

Date of start up first time:___________

Wheretheunitisinstalled:

Name:____________________________________________________

Address:__________________________________________________

HerearesomepointstobecheckedafterEnsy®AHUunitis
installed.

1. Inserttheplugintoagroundedsocket.
Thenyouwillhaveapicturelikethisindisplay.
(Timeandtemperatureswillshowothervaluesthenshownhere)


Overviewpushbuttons.

2. ControltoseeiftherearecontactbetweenDisplayandMaster
softwareinunit.

Presscontrolbutton3oncetogetintotheinformationmenu.
Presscontrolbutton3oncetogetintotheProgramversionmenu.
Press(Enter)controlbutton4.
YouthanwillseethattherearecontactwithDisplayandMastercardsoftwareinmenupicture(3.2).

Latestdisplay
softwareare021and
Masterare034.




Presscontrolbutton1(Return)twicetogetbacktostartupmenu.

Note!Ifyouhaveinstalledanextradisplaythenyouhavetoprogramoneofthedisplayswith
nameDisplay2.(Bothdisplaysmusthavesamesoftwareversion.)Fillinthreelastnumbers:
Presscontrolbutton4oncetogetinto4.Preferences.  Display1Ver:_________
Presscontrolbutton3fourtimestogettoSetup.  Display2Ver:_________
Press(Enter)controlbutton4togetinto4.5PINcode.  MasterVer:___________
Controllbutton1. 2.3. 4.
393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage3
Presscontrolbutton3(+)onceandyouwillhave1000indisplay.
Presscontrolbutton4(enter)fourtimesandOKwillshowupin
display.
Presscontrolbutton3(OK)togetinto4.5.1Setup.
Presscontrolbutton3ninetimestogettoDisplaynumber.
Presscontrolbutton4oncetogetinto4.5.1.10Displaynumber.
Presscontrolbutton3(+)onceuntilitshowsDisplay2.
Presscontrolbutton1(Return)threetimestogetbacktostart
upmenu.


3. Howtocontrolthefanspeed.

ThefanspeedissettoOFF0%fromfactory.

Presscontrolbutton1oncetogetinto4.1Fanspeed.
TherearedifferentvaluesonMIN,NORMandMAX
dependingontheunittype.Factorysettingsyoucanfind
in«UsermanualsandInstallationGuide»undermenu
4.5.1.3.Fancontrol.

Presscontrolbutton3(+)totesttheunitonMINspeed.
(Itisthevalueforsupplyairfanthatshowsindisplay)

Ifadjusted.Whatisnewvalueafterinstallation?
Supp:_____%Extr:_____%



Presscontrolbutton3(+)totesttheunitonNORM
speed.(Itisthevalueforsupplyairfanthatshowsin
display)

Ifadjusted.Whatisnewvalueafterinstallation?
Supp:_____%Extr:_____%



Presscontrolbutton3(+)totesttheunitonMAXspeed.
(Itisthevalueforsupplyairfanthatshowsindisplay)

Ifadjusted.Whatisnewvalueafterinstallation?
Supp:_____%Extr:_____%


SettheunittoNORMfanspeedafterinstallation.

Presscontrolbutton2or3(under–and+)togetbacktoNORMfanspeed.
Presscontrolbutton1(Return)oncetogetbacktostartupmenu.
393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage4
4. Howtoadjust%forMIN,NORMandMAXtogetbalancedventilation.




Presscontrolbutton4oncetogetinto4Preferences.




Presscontrolbutton3fourtimestogettoSetup.



Press(Enter)controlbutton4togetinto4.5PINcode
menu.


Presscontrolbutton3(+)onceandyouwillhave1000in
display.

Presscontrolbutton4(enter)fourtimesandOKwillshow
upindisplay.




Presscontrolbutton3(OK)togetinto4.5.1Setup.


Presscontrolbutton3twicetogettoFancontrol.

Presscontrolbutton4(enter)togetinto4.5.1.3Fan
controlmenu.

TherearedifferentvaluesonMin,NormalandMax
dependingontheunittype.Factorysettingsyoucanfindin
«UsermanualsandInstallationGuide»undermenu4.5.1.3.
Ifyouneedtodoadjustmentsheretogetbalanced
ventilationthenpleasefillinthenewsettingsonprevious
page.
Changevalueswithcontrolbuttons2(‐)or3(+).
MovebetweenSupp.andExtr.withcontrolbutton4.

Afteradjustmentsusecontrolbutton1(Return)threetimestogetbacktothestartupmenu.

 Which % intervals are there on the different operating steps?
OFF=0%
MIN=30‐49%
NORM=50‐79%
MAX=80‐100%
393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage5

5. Adjusttodesiredsupplyairtemperature.

Supplyairtemperatureissetto17°Cfromfactoryandcan
beadjustedbetween15and21°C.

Presscontrolbutton2oncetogetinto2Temperature
menu.

Changevalueswithcontrolbuttons2(‐)or3(+).

Afteradjustmentsusecontrolbutton1(Return)oncetoget
backtothestartupmenu.

Writedownsettemperature:________________
(Thiscanofcoursebechangedbythelandlordifdesired)

6. Settingtimeanddate.
Thisisimportanttogetanalarmwhenit'stimeforfilterchange.
Presscontrolbutton4oncetogetinto4.Preferences.
Presscontrolbutton4onemoretimetogetinto4.1Time/datemenu.
Changevalueswithcontrolbuttons2(‐)or3(+).
Presscontrolbutton4oncetogettonextstep.
Ifyouneedtogobackandwantstocorrectafieldyoucanstartoverbypressingcontrolbutton4
numberoftimestillyouarebackinthefieldyouneedtochange.

Writedowndate:

________________




Presscontrolbutton3(OK)oncetogetbackto4Preferencesmenu.

Presscontrolbutton3twicetogettoFilter.
Presscontrolbutton4oncetogetinto4.3Filtermenu.

Usecontrolbuttons2(‐)or3(+)tosetwantedinterval
beforenextfilterchange.Canbesetto6,9or12months.
Writedownchoseninterval:______Months

(Thiscanofcoursebechangedbythelandlordifdesired)

Presscontrolbutton4once(FilterOK!)andyouwillgetNext
replacedateindisplay.
Writedownnextreplacedate:________________
Presscontrolbutton1(Return)twicetogetbacktostartup
menu.

Landlordor,whoisresponsibleforserviceinlargerprojects,tomakeanagreementforwhoto
changefiltersandfromwhomtoordernewfilters.

Anyagreementsmade,YESorNOI:____________
393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage6

7. Verifythatthesignalfromcookerhood/kitchenventilatorworks.

Thisisimportanttoavoidrotoralarm..

Ifacookerhoodisconnectedtowardstheventilationunititisimportantthatthereissignalfrom
cookerhoodintoKVconnectionplugontheventilationunit.
Thissignalcanbetakenfromthecookerhooddirectlyorviaapressureswitchinthepipingbetween
cookerhoodanventilationunit.

Ifatwo‐stepkitchenventilatorisusedthenitisimportantthatinthefirststep,whereonlythe
damperopens,therealsoissignalfromventilatorintoKVconnectionplugontheventilationunit.
Thissignalcanbetakenfromthecookerhooddirectly,ifpossible,orviaapressureswitchinthe
exhaustpipingfromtheventilator.

Kitchenventilatorwithintegratedfanisnotallowedtoconnectdirectlytothe«Cookerhood»inlet
ontheventilationunit.Forthisyouneedtomakeitsownexhaustpipingthroughwall.Anywayyou
needtomakeasignalfromkitchenventilatorintoKVconnectionplugontheventilationunit.This
signalcanbetakenfromthekitchenventilatordirectly,ifpossible,orviaapressureswitchinthe
exhaustpipingfromtheventilator.


Innallcasesitisimportanttoseethattherearesignalindisplaywhenactivatinganysteps
oncookerhood/ventilator.

Dothissignalshowindisplayonallstepswhenactivatingcookerhood/ventilator.
YesorNO:____________

Ifapessureswitchisusedtogetsignalitisimportantthetitisadjustedwithsuchahighvaluethatit
don’tgivesignalswhencookerhood/ventilatorisnotactivated.
393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage7

8. Checkingsettingsforthefanswhenactivatingcookerhood/kitchen
ventilator.

Togetbalancedventilationwhenyouactivatethecookerhoodorkitchenventilatoryoushould
adjustthesettings.

Ifacookerhoodisused.

Presscontrolbutton4oncetogetinto4.Preferences.
Presscontrolbutton3threetimestogettoSetupmenu.


Press(Enter)controlbutton4togetinto4.5PINcodemenu.




Presscontrolbutton3(+)onceandyouwillhave1000in
display.




Presscontrolbutton4(enter)fourtimesandOKwillshowupin
display.




Presscontrolbutton3(OK)togetinto4.5.1Setup.


Presscontrolbutton3fourtimestogettoCookerhood.

Presscontrolbutton4(enter)togetinto4.5.1.5Cookerhood
menu.

Setto100%fromfactory.

MovebetweenSupplyairandExtractairwithcontrolbutton4.
Changevalueswithcontrolbuttons2(‐)or3(+).

Aftersettingpresscontrolbutton1(Return)threetimestogetbacktostartmenu..

HerethevaluesforSupplyairandExtractairshouldbesettosamevaluesasforMAXinmenu
4.5.1.3.Fancontrolintheusermanualthatfollowsthisunit.

Ifanactivekitchenventilatorisused.
Ifanactivekitchenventilatorisused,thenExtractairshouldbesetto50%orlesstocompensatefor
theairthatisextractedviakitchenventilator.
393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage8
Alltheabovepointsmustbecheckedbeforetheunitisapprovedbytheinstaller.

Thecompletedformisattachedtodocumentationfolderthatshallfollowtheunit.

Other"options"thatcanbeusedtogetherwiththeunitcanbefoundintheinstructionssupplied
unit.

Allpaperworksandinstructionsyoucanfindonwww.ensy.no



























Thecompanythathaveinstalledthisunit: Contact:

_____________________________________________________________________
Phone:  e‐mail:
_____________________________________________________________________




EnsyAS
Mohagasvingen1
N‐2770JAREN
http://www.ensy.no

This manual suits for next models

1

Other Ensy Fan manuals

Ensy AHU-700 BV/1 User manual

Ensy

Ensy AHU-700 BV/1 User manual

Ensy AHU-300 BV User manual

Ensy

Ensy AHU-300 BV User manual

Ensy AHU-200 KV SLIM User manual

Ensy

Ensy AHU-200 KV SLIM User manual

Ensy AHU-400 BV User manual

Ensy

Ensy AHU-400 BV User manual

Ensy InoVent AHU-200 Series User manual

Ensy

Ensy InoVent AHU-200 Series User manual

Ensy AHU-300 HV User manual

Ensy

Ensy AHU-300 HV User manual

Popular Fan manuals by other brands

KDK K15Z5 Operating and installation instructions

KDK

KDK K15Z5 Operating and installation instructions

Vasner 2016VCY1 manual

Vasner

Vasner 2016VCY1 manual

Omega Altise AP40WA instruction manual

Omega Altise

Omega Altise AP40WA instruction manual

Hinkley WINDWARD instruction manual

Hinkley

Hinkley WINDWARD instruction manual

Vents VUT 300 E2V EC Operation manual

Vents

Vents VUT 300 E2V EC Operation manual

Craftmade ELLINGTON Decorator's Choice DCF52BNK5C1 installation guide

Craftmade

Craftmade ELLINGTON Decorator's Choice DCF52BNK5C1 installation guide

Beem Air Joy Cool user manual

Beem

Beem Air Joy Cool user manual

Broan ZB110H installation guide

Broan

Broan ZB110H installation guide

Vortice ARIANTE 25 Instruction booklet

Vortice

Vortice ARIANTE 25 Instruction booklet

dalap DARK user manual

dalap

dalap DARK user manual

SKF LINCOLN 85831 Assembly guide

SKF

SKF LINCOLN 85831 Assembly guide

Bellus 614035 quick start guide

Bellus

Bellus 614035 quick start guide

aerauliqa QXD installation manual

aerauliqa

aerauliqa QXD installation manual

NuAire DAVE Installation, operating,  & maintenance instructions

NuAire

NuAire DAVE Installation, operating, & maintenance instructions

Parrot Uncle F6278 quick start guide

Parrot Uncle

Parrot Uncle F6278 quick start guide

Craftmade MND54BNK3 installation guide

Craftmade

Craftmade MND54BNK3 installation guide

NuTone 754RBNT Architectural & engineering specifications

NuTone

NuTone 754RBNT Architectural & engineering specifications

TJERNLUND EA5 DUCT BOOSTER FAN 8504029 manual

TJERNLUND

TJERNLUND EA5 DUCT BOOSTER FAN 8504029 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.