manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Ensy
  6. •
  7. Fan
  8. •
  9. Ensy AHU-400 BH Manual

Ensy AHU-400 BH Manual


Startupprocedure
for
Ensy®AHU-units
















393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage2
Informationcanbefoundonthedataplaqueinsidetheunit.Thissignshows.AHU‐400BH

Unittype:AHU‐_____________

Serialno:010______________.____/_____

Date of start up first time:___________

Wheretheunitisinstalled:

Name:____________________________________________________

Address:__________________________________________________

HerearesomepointstobecheckedafterEnsy®AHUunitis
installed.

1. Inserttheplugintoagroundedsocket.
Thenyouwillhaveapicturelikethisindisplay.
(Timeandtemperatureswillshowothervaluesthenshownhere)


Overviewpushbuttons.

2. ControltoseeiftherearecontactbetweenDisplayandMaster
softwareinunit.

Presscontrolbutton3oncetogetintotheinformationmenu.
Presscontrolbutton3oncetogetintotheProgramversionmenu.
Press(Enter)controlbutton4.
YouthanwillseethattherearecontactwithDisplayandMastercardsoftwareinmenupicture(3.2).

Latestdisplay
softwareare021and
Masterare034.




Presscontrolbutton1(Return)twicetogetbacktostartupmenu.

Note!Ifyouhaveinstalledanextradisplaythenyouhavetoprogramoneofthedisplayswith
nameDisplay2.(Bothdisplaysmusthavesamesoftwareversion.)Fillinthreelastnumbers:
Presscontrolbutton4oncetogetinto4.Preferences.  Display1Ver:_________
Presscontrolbutton3fourtimestogettoSetup.  Display2Ver:_________
Press(Enter)controlbutton4togetinto4.5PINcode.  MasterVer:___________
Controllbutton1. 2.3. 4.
393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage3
Presscontrolbutton3(+)onceandyouwillhave1000indisplay.
Presscontrolbutton4(enter)fourtimesandOKwillshowupin
display.
Presscontrolbutton3(OK)togetinto4.5.1Setup.
Presscontrolbutton3ninetimestogettoDisplaynumber.
Presscontrolbutton4oncetogetinto4.5.1.10Displaynumber.
Presscontrolbutton3(+)onceuntilitshowsDisplay2.
Presscontrolbutton1(Return)threetimestogetbacktostart
upmenu.


3. Howtocontrolthefanspeed.

ThefanspeedissettoOFF0%fromfactory.

Presscontrolbutton1oncetogetinto4.1Fanspeed.
TherearedifferentvaluesonMIN,NORMandMAX
dependingontheunittype.Factorysettingsyoucanfind
in«UsermanualsandInstallationGuide»undermenu
4.5.1.3.Fancontrol.

Presscontrolbutton3(+)totesttheunitonMINspeed.
(Itisthevalueforsupplyairfanthatshowsindisplay)

Ifadjusted.Whatisnewvalueafterinstallation?
Supp:_____%Extr:_____%



Presscontrolbutton3(+)totesttheunitonNORM
speed.(Itisthevalueforsupplyairfanthatshowsin
display)

Ifadjusted.Whatisnewvalueafterinstallation?
Supp:_____%Extr:_____%



Presscontrolbutton3(+)totesttheunitonMAXspeed.
(Itisthevalueforsupplyairfanthatshowsindisplay)

Ifadjusted.Whatisnewvalueafterinstallation?
Supp:_____%Extr:_____%


SettheunittoNORMfanspeedafterinstallation.

Presscontrolbutton2or3(under–and+)togetbacktoNORMfanspeed.
Presscontrolbutton1(Return)oncetogetbacktostartupmenu.
393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage4
4. Howtoadjust%forMIN,NORMandMAXtogetbalancedventilation.




Presscontrolbutton4oncetogetinto4Preferences.




Presscontrolbutton3fourtimestogettoSetup.



Press(Enter)controlbutton4togetinto4.5PINcode
menu.


Presscontrolbutton3(+)onceandyouwillhave1000in
display.

Presscontrolbutton4(enter)fourtimesandOKwillshow
upindisplay.




Presscontrolbutton3(OK)togetinto4.5.1Setup.


Presscontrolbutton3twicetogettoFancontrol.

Presscontrolbutton4(enter)togetinto4.5.1.3Fan
controlmenu.

TherearedifferentvaluesonMin,NormalandMax
dependingontheunittype.Factorysettingsyoucanfindin
«UsermanualsandInstallationGuide»undermenu4.5.1.3.
Ifyouneedtodoadjustmentsheretogetbalanced
ventilationthenpleasefillinthenewsettingsonprevious
page.
Changevalueswithcontrolbuttons2(‐)or3(+).
MovebetweenSupp.andExtr.withcontrolbutton4.

Afteradjustmentsusecontrolbutton1(Return)threetimestogetbacktothestartupmenu.

 Which % intervals are there on the different operating steps?
OFF=0%
MIN=30‐49%
NORM=50‐79%
MAX=80‐100%
393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage5

5. Adjusttodesiredsupplyairtemperature.

Supplyairtemperatureissetto17°Cfromfactoryandcan
beadjustedbetween15and21°C.

Presscontrolbutton2oncetogetinto2Temperature
menu.

Changevalueswithcontrolbuttons2(‐)or3(+).

Afteradjustmentsusecontrolbutton1(Return)oncetoget
backtothestartupmenu.

Writedownsettemperature:________________
(Thiscanofcoursebechangedbythelandlordifdesired)

6. Settingtimeanddate.
Thisisimportanttogetanalarmwhenit'stimeforfilterchange.
Presscontrolbutton4oncetogetinto4.Preferences.
Presscontrolbutton4onemoretimetogetinto4.1Time/datemenu.
Changevalueswithcontrolbuttons2(‐)or3(+).
Presscontrolbutton4oncetogettonextstep.
Ifyouneedtogobackandwantstocorrectafieldyoucanstartoverbypressingcontrolbutton4
numberoftimestillyouarebackinthefieldyouneedtochange.

Writedowndate:

________________




Presscontrolbutton3(OK)oncetogetbackto4Preferencesmenu.

Presscontrolbutton3twicetogettoFilter.
Presscontrolbutton4oncetogetinto4.3Filtermenu.

Usecontrolbuttons2(‐)or3(+)tosetwantedinterval
beforenextfilterchange.Canbesetto6,9or12months.
Writedownchoseninterval:______Months

(Thiscanofcoursebechangedbythelandlordifdesired)

Presscontrolbutton4once(FilterOK!)andyouwillgetNext
replacedateindisplay.
Writedownnextreplacedate:________________
Presscontrolbutton1(Return)twicetogetbacktostartup
menu.

Landlordor,whoisresponsibleforserviceinlargerprojects,tomakeanagreementforwhoto
changefiltersandfromwhomtoordernewfilters.

Anyagreementsmade,YESorNOI:____________
393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage6

7. Verifythatthesignalfromcookerhood/kitchenventilatorworks.

Thisisimportanttoavoidrotoralarm..

Ifacookerhoodisconnectedtowardstheventilationunititisimportantthatthereissignalfrom
cookerhoodintoKVconnectionplugontheventilationunit.
Thissignalcanbetakenfromthecookerhooddirectlyorviaapressureswitchinthepipingbetween
cookerhoodanventilationunit.

Ifatwo‐stepkitchenventilatorisusedthenitisimportantthatinthefirststep,whereonlythe
damperopens,therealsoissignalfromventilatorintoKVconnectionplugontheventilationunit.
Thissignalcanbetakenfromthecookerhooddirectly,ifpossible,orviaapressureswitchinthe
exhaustpipingfromtheventilator.

Kitchenventilatorwithintegratedfanisnotallowedtoconnectdirectlytothe«Cookerhood»inlet
ontheventilationunit.Forthisyouneedtomakeitsownexhaustpipingthroughwall.Anywayyou
needtomakeasignalfromkitchenventilatorintoKVconnectionplugontheventilationunit.This
signalcanbetakenfromthekitchenventilatordirectly,ifpossible,orviaapressureswitchinthe
exhaustpipingfromtheventilator.


Innallcasesitisimportanttoseethattherearesignalindisplaywhenactivatinganysteps
oncookerhood/ventilator.

Dothissignalshowindisplayonallstepswhenactivatingcookerhood/ventilator.
YesorNO:____________

Ifapessureswitchisusedtogetsignalitisimportantthetitisadjustedwithsuchahighvaluethatit
don’tgivesignalswhencookerhood/ventilatorisnotactivated.
393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage7

8. Checkingsettingsforthefanswhenactivatingcookerhood/kitchen
ventilator.

Togetbalancedventilationwhenyouactivatethecookerhoodorkitchenventilatoryoushould
adjustthesettings.

Ifacookerhoodisused.

Presscontrolbutton4oncetogetinto4.Preferences.
Presscontrolbutton3threetimestogettoSetupmenu.


Press(Enter)controlbutton4togetinto4.5PINcodemenu.




Presscontrolbutton3(+)onceandyouwillhave1000in
display.




Presscontrolbutton4(enter)fourtimesandOKwillshowupin
display.




Presscontrolbutton3(OK)togetinto4.5.1Setup.


Presscontrolbutton3fourtimestogettoCookerhood.

Presscontrolbutton4(enter)togetinto4.5.1.5Cookerhood
menu.

Setto100%fromfactory.

MovebetweenSupplyairandExtractairwithcontrolbutton4.
Changevalueswithcontrolbuttons2(‐)or3(+).

Aftersettingpresscontrolbutton1(Return)threetimestogetbacktostartmenu..

HerethevaluesforSupplyairandExtractairshouldbesettosamevaluesasforMAXinmenu
4.5.1.3.Fancontrolintheusermanualthatfollowsthisunit.

Ifanactivekitchenventilatorisused.
Ifanactivekitchenventilatorisused,thenExtractairshouldbesetto50%orlesstocompensatefor
theairthatisextractedviakitchenventilator.
393803‐2Startup procedure for EnSy AHU units REV:0_08.09.2016.KJK
Wereservetherighttochangetechnicaldatawithoutnoticehttp://www.ensy.noPage8
Alltheabovepointsmustbecheckedbeforetheunitisapprovedbytheinstaller.

Thecompletedformisattachedtodocumentationfolderthatshallfollowtheunit.

Other"options"thatcanbeusedtogetherwiththeunitcanbefoundintheinstructionssupplied
unit.

Allpaperworksandinstructionsyoucanfindonwww.ensy.no



























Thecompanythathaveinstalledthisunit: Contact:

_____________________________________________________________________
Phone:  e‐mail:
_____________________________________________________________________




EnsyAS
Mohagasvingen1
N‐2770JAREN
http://www.ensy.no

This manual suits for next models

1

Other Ensy Fan manuals

Ensy AHU-400 BV User manual

Ensy

Ensy AHU-400 BV User manual

Ensy InoVent AHU-200 Series User manual

Ensy

Ensy InoVent AHU-200 Series User manual

Ensy AHU-300 HV User manual

Ensy

Ensy AHU-300 HV User manual

Ensy AHU-200 KV SLIM User manual

Ensy

Ensy AHU-200 KV SLIM User manual

Ensy AHU-700 BV/1 User manual

Ensy

Ensy AHU-700 BV/1 User manual

Ensy AHU-300 BV User manual

Ensy

Ensy AHU-300 BV User manual

Popular Fan manuals by other brands

Emerson LK70 owner's manual

Emerson

Emerson LK70 owner's manual

EdenPURE A5716 instruction manual

EdenPURE

EdenPURE A5716 instruction manual

TLV SA3 instruction manual

TLV

TLV SA3 instruction manual

Progress Lighting AirPro P2554 installation manual

Progress Lighting

Progress Lighting AirPro P2554 installation manual

S&P PC80X installation instructions

S&P

S&P PC80X installation instructions

Alpha Fan PRIMA-5B/56 LED instruction manual

Alpha Fan

Alpha Fan PRIMA-5B/56 LED instruction manual

Sencor SFN 4040SL user manual

Sencor

Sencor SFN 4040SL user manual

Excelsior Excelair ETF 901 instruction manual

Excelsior

Excelsior Excelair ETF 901 instruction manual

emmeti RECUPERA ONE-40-S Installation manual and using instructions

emmeti

emmeti RECUPERA ONE-40-S Installation manual and using instructions

Craftmade Cole CLE44 installation guide

Craftmade

Craftmade Cole CLE44 installation guide

Vents VKP EC SERIES user manual

Vents

Vents VKP EC SERIES user manual

Flexit K2.1 user manual

Flexit

Flexit K2.1 user manual

TCF TCVA Installation, operation & maintenance manual

TCF

TCF TCVA Installation, operation & maintenance manual

Faro Barth installation guide

Faro

Faro Barth installation guide

Progress Lighting AirPro P2578 Installation guides

Progress Lighting

Progress Lighting AirPro P2578 Installation guides

Fantech AEV Series installation manual

Fantech

Fantech AEV Series installation manual

Fanimation Torrento FP920 Series Specification sheet

Fanimation

Fanimation Torrento FP920 Series Specification sheet

Pacific International Fans EM-E installation manual

Pacific International Fans

Pacific International Fans EM-E installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.