EMC note USA (FCC):
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
EMC note Canada (ICES-003):
CAN ICES-3 (A) / NMB-3 (A)
TECHNICAL DATA
Measurands
Relative Humidity
Working range 0...100 % RH
Accuracy1) at 20 °C (68 °F) ± 3 % RH (30...70 % RH) ± 5 % RH (0...95 % RH)
Output signal (0...100 %) 0 - 2.5 V
Output load ≥ 5 kΩ
Response time τ63 < 45 s duct mount
< 30 s duct mount with lateral openings
Temperature
Output signal 0 - 2.5 V
Output load ≥ 5 kΩ
Accuracy1) at 20 °C (68 °F) ± 0.3 °C (0.54 °F)
General Data
Supply voltage UV 5 V DC ±10%
Current consumption typical 2 mA without load
< 3.5 mA at 5 kΩ load
Start up time typ. 4 sec.
Electrical connection appropriate for Molex 6471 (4 pins) and female crimp contacts 4809 555L
Housing material PPO – GF20, UL94HB approved
Protection class connector side: IP30
front side: IP50 (duct mount)
IP20 (duct mount with lateral openings)
CE compatibility according2) EN61326-1 EN61326-2-3
Industrial environment
Working conditions T = -40…+85 °C (-40…185 °F)
RH = 0…100 % (non condensing)
Storage conditions T = -40…+60 °C (-40…140 °F)
RH = 0…95 % (non condensing)
1) Traceable to intern. standards, administrated by NIST, PTB, BEV... . The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2
(2-times standard deviation). The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
2) EE040 is not protected against surge