tECHniCAL dAtA
(Modification rights reserved)
Langwiesen7•A-4209Engerwitzdorf
Tel:+437235605-0•Fax:+437235605-8
LGLinzFn165761t•UID-Nr.ATU44043101
PlaceofJurisdiction:A-4020Linz•DVR0962759
BA_EE150_e//v1.0//TechnischeÄnderungenvorbehalten
TheEE150isreadytouseanddoesnotrequireanycongurationbytheuser.ThefactorysetupofEE150correspondstothetypenum-
berordered.Fororderingguidepleaseseedatasheetatwww.epluse.com/EE150.
Ifneeded,theusercanchangethefactorysetupbyusingtheoptional E+E Product ConfigurationAdapter (EE-PCA) and the E+E
ProductConfigurationSoftware(EE-PCS).Withthese one can set the output scaling, and perform one or twopointadjustmentfor
humidityandtemperature.
ForproductdatasheetEE-PCApleaseseewww.epluse.com.
TheE+EProductConfigurationSoftware(EE-PCS)isfreeandcanbedownloadedfromwww.epluse.com/configurator.
SEtUP And AdJUStmEnt
USA
FCC notice:
ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassBdigitaldevice,pursuanttopart15oftheFCCRules.Theselimitsare
designedtoprovidereasonableprotectionagainstharmfulinterferenceinaresidentialinstallation.Thisequipmentgenerates,usesandcanradiatera-
diofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstallationmanual,maycauseharmfulinterferencetoradiocommunications.
However,thereisnoguaranteethatinterferencewillnotoccurinaparticularinstallation.Ifthisequipmentdoescauseharmfulinterferencetoradioor
televisionreception,whichcanbedeterminedbyturningtheequipmentoffandon,theuserisencouragedtotrytocorrecttheinterferencebyoneor
moreofthefollowingmeasures:
- Reorientorrelocatethereceivingantenna.
- Increasetheseparationbetweentheequipmentandreceiver.
- Connecttheequipmentintoanoutletonacircuitdifferentfromthattowhichthereceiverisconnected.
- Consultthedealeroranexperiencedradio/TVtechnicianforhelp.
CANADIAN
ICES-003 Issue 5:
CANICES-3B/NMB-3B
Measured values
Relative Humidity
Workingrange 10...90%RH
Accuracyat20°C ±3%RH(30...70%RH),otherwise±5%RH
Temperaturedependency typ.±0.05%RH/°C
Temperature
Workingrange -5...55°C(23...131°F)
T-Accuracyat20°C ±0.3°C
Outputs
Analog output 0-10V RL≥10kOhm
(0...100%RH;T:seeorderingguide) 4-20mA(2-wire) RL≤500Ohm
Passive T-sensor
2-wire seeorderingguide
Wiresresistance(terminal-sensor) typ.0.5Ohm
General
Powersupply(ClassIII)
for0-10V 15-35VDCor24VAC±20%
for4-20mA 10V+RLx20mA<UV<35VDC
Currentconsumption withDCpowersupply typ.5mA
withACpowersupply typ.13mAeff
Connection Screwterminals,max.1.5mm2
Housingmaterial Polycarbonate,UL94V-0approved
Protectionclass IP65/NEMA4
Cablegland M16x1.5
Sensorprotection PTFEfilter,non-removable
Electromagneticcompatibility EN61326-1EN61326-2-3Industrialenvironment
FCCPart15ClassBICES-003Issue5ClassB
Workingconditions -5...55°C (23...131°F) 0...95%RH(non-condensing)
Storageconditions -25...60°C(-13...140°F) 20...80%RH