Address Switch
Address Switch
Address setting via EE-PCS Product Conguration Software:
All Dip-Switches at position 0 → address has to be set via Product Conguration Software
Modbus (Slave device): factory setting EE650: 65 (permitted values: 1…247).
BACnet (Master device): factory setting EE650: 65 (permitted values: 0…127).
Example: Slave address is set via conguration software.
Address setting via Dip-Switch:
Modbus (Slave device): Setting the Dip-Switch to any other address than 0, overrules the slave
address set via configuration software (permitted values: 1…247).
BACnet (Master device): Setting the Dip-Switch to any other address than 0, overrules the slave
address set via configuration software.
BACnet Note: permitted values are 0…127. The 8th bit of the Dip-Switch is ignored
(ID 127 = 0111 111).
To set address 0 via Dip-Switch, the 8th bit shall be set to 1 (ID 0 = 1000 0000).
Example: Slave address set to 11 (= 0000 1011 binary).
FLOAT (read register):
Function code /
Register number1) [Dec]
Register address2)
[HEX]
Parameter
name
31003 0x03EA Temperature [°C]
31005 0x03EC Temperature [°F]
31041 0x0410 Airow [m/s]
31043 0x0412 Airow [ft/min]
SHORT (read register)3):
Function code /
Register number1) [Dec]
Register address2)
[HEX]
Parameter
name
34002 0x0FA1 Temperature* [°C]
34003 0x0FA2 Temperature** [°F]
34021 0x0FB4 Airow* [m/s]
34022 0x0FB5 Airow*** [ft/min]
* Values are stored with the scale 1:100 (e.g.: 2550 is equivalent to 25.5 °C)
** Values are stored with the scale 1:50 (e.g.: 2550 is equivalent to 51 °F)
*** Values are stored with the scale 1:1
INFO (read register):
Function code /
Register number1) [Dec]
Register address2)
[HEX]
Parameter
name
30001 0x00 Serial number (as ASCII)
30009 0x08 Firmware version
INTEGER (write register):
Function code /
Register number1) [Dec]
Register address2)
[HEX]
Parameter
name
60001 0x00 Slave-ID* (modbus address)
60002 0x01 Modbus protocol settings3)
* If the ID is set via DIP-Switch the response will be NAK.
Please see PICS (Product Implementation Conformance Statement) - available on www.epluse.com
BACnet Setup
Address Setting
QUICK GUIDE
EE650 - Air Velocity Transmitters with RS485 Interface
(Full User‘s Guide at www.epluse.com/EE650)