ETC Echoflex Elaho User manual

Echoflex Installation Guide
Elaho Dual Tech Wall-mount Occupancy
Corporate Headquarters nMiddleton, WI, USA|+1 608 831 4116
©2023 Echoflex Solutions, Inc. |Trademark and patent info: echoflexsolutions.com/ip
Third-party license agreement info:etcconnect.com/licenses |Product information and specifications subject to
change.Echoflexintends this document to be provided in its entirety.
8186M2185RevCReleased2023-06
Overview
The Elaho Dual Tech Wall-mount Occupancy Sensor uses passive infrared
(PIR) technology and acoustic detection to provide reliable occupancy and
vacancy sensing for lighting control.
The wall-mount unit offers up to 140 degree field
of detection with optimized lens options to
accommodate wide or narrow angle spaces.
Wall-mount - Wide Angle Lens - coverage
• 18.3 m (60 ft) at mounting height of
2.1–3m(7–10ft)
• 140 degree field of detection
Wall-mount - Narrow Angle Lens - coverage
• 4.9x22.9 m (16x75 ft) at mounting height of
1.8–2.1 m (6–7 ft)
• 40 degree field of detection
See
Sensor Coverage on page 11
.
Custom Configuration
This document guides you through the installation and local DIP switch
setup of the sensor. For more detailed information about custom
configuration options available using ElahoAccess, see the ElahoAccess
App integrated help system.
Note:
To use the configuration settings applied using
ElahoAccess, DIP switch 2 must be enabled. See DIP Switches on
page7.

Echoflex Installation Guide
Dual Tech Wall-mount Occupancy Sensor
Prepare for Installation
Elaho Dual Tech Wall-mount Occupancy Sensors ship with electronics, a
decorator style wall plate, and a termination kit. The sensor may be
installed into an industry-standard back box (provided by others) or
surface-mounted back box (sold separately and available from Echoflex).
Compliance
• cULus Listed
• CE compliant
For use with Echoflex Elaho Control Systems, powered by an Elaho station
power supply.
Environment
Ambient
For indoor, commercial controls use only. Operating temperature
0°C–40°C (32°F–104°F), humidity maximum 90%(non-condensing).
Location
Echoflex recommends paying special attention to the installation
environment:
• When operating in PIR only modes, the sensor must have an
unobstructed view of the room. Do not mount behind or near tall
cabinets, shelves, hanging light fixtures, etc.
• Do not install the sensor within eight feet from an HVAC airflow
duct/vent.
• Install the sensor where it cannot easily sense movement in areas
outside of the intended space, such as hallways, glass partitions, or
adjacent rooms.
Note:
In areas of increased noise activity, enabling PIR only mode
may allow for better detection results. See DIP Switches on page
7.
Dual Tech Wall-mount Occupancy Sensor Page 2 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Wall-mount Occupancy Sensor
Wire Specification
The Dual Tech Wall-mount Occupancy Sensor connects to the
EchoConnect communication bus. EchoConnect is a bi-directional
protocol that uses one pair of wires (data+ and data–) for both data and
power. Echoflex recommends using Belden 8471 Class 2 wire (or
approved equal – see the Echoflex cable cross database
echoflexsolutions.com/files/Elaho_Data_Cable_Wire_Specs for equal
alternatives). The total combined length of an EchoConnect wire run
using Belden 8471 may not exceed 500m (1,640ft), with a maximum
distance of 400m(1,312ft) between any two devices.
Note:
All control wiring should be installed and terminated by a
qualified installer and should follow standard wiring installation
practices. Leave approximately 25.4cm (10in) of wiring in the
back box for connection and to allow slack for future service
needs.
Note:
Echoflex requires that all stations and devices be grounded
for ESDprotection. Pull an additional 2.5 mm2(14AWG) wire for
grounding when control wires are not installed in grounded metal
conduit.
Note:
When using Category 5 (or equivalent) cable on the
EchoConnect communication bus, please note the following:
• Cat5 wiring must be terminated using EchoConnect Cat5
Termination Kits and must be installed using a bus topology.
Refer to the instructions provided with the Cat5 Termination
Kit (8186A1207) for information to terminate Cat5 wiring.
• Not all topologies are supported using Cat5; careful
planning is required to ensure the proper termination kits
are available and the wire is pulled appropriately.
Supplies
The following supplies are provided with the sensor:
• mounting bracket with pre-routed EchoConnect and ground wires
• 2 each mounting screws, 6-32x3/4in and 6-32x1 3/4in
• WAGO connectors, 3-position
• decorator style wall plate
Dual Tech Wall-mount Occupancy Sensor Page 3 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Wall-mount Occupancy Sensor
Installation
Note:
NEC Class 2 product to be wired in accordance to NEC
Article 725 and local jurisdiction requirements.
The wall-mount sensor is provided with a mounting bracket with pre-
routed wires that can be mounted to a back box. Follow the detailed
instructions for installation.
1. Pull the Belden 8471 (or equivalent) and one 2.5 mm2(14 AWG)
ground wire to the mounting location (back box or surface mounted
back box) and strip each wire 11 mm (7/16 in).
2. Connect the EchoConnect pigtail wires from the mounting bracket
to the installed wall wires.
a. Connect the data– (black) EchoConnect wire from mounting
bracket to the incoming data– (typically black) wire using a
WAGO wire termination connector (provided).
b. Repeat the above steps for the data+ (white) EchoConnect wire
and for the ESD ground wire (green/yellow), using a new WAGO
connector for each termination type.
3. Orient the mounting plate to the back box with the directional
arrows in the upright position and secure it in place using the
screws provided.
Dual Tech Wall-mount Occupancy Sensor Page 4 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Wall-mount Occupancy Sensor
4. Install the wall plate to the
mounting plate.
a. Align the top of the wall
plate to the mounting plate,
angling the bottom slightly.
b. Hook the top of the wall
plate to the tabs located on
the mounting plate.
c. Swing the wall plate down,
ensuring the neck of the
sensor extension and wires
feed through the opening,
until the magnets engage.
d. If the wall plate does not
fully attach, wiggle the
bottom of the plate until all of the magnets are seated properly.
a
b
c
d
5. Attach the sensor
head.
a. Slide the
removable cover
off the sensor
head.
b. Route the
three-position
connector with
wiring pigtail
through the
sensor head.
c. Loosen the set
screw on the
sensor retaining
ring.
d. Slide the sensor
onto the ball socket, and then tighten the set screw until secure.
6. Connect the three-position connector to the receptacle on the
sensor electronics.
Dual Tech Wall-mount Occupancy Sensor Page 5 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Wall-mount Occupancy Sensor
Settings
MODE AUX
The Elaho Dual Tech Wall-mount Occupancy
Sensor participates in an Elaho control
system using the configured Space and
Address, which are selectable using the
rotary switches on the sensor electronics
located behind the removable cover.
DIP switches and the [MODE] button, also
located on the sensor electronics, set the
sensor functionality and the occupancy
detection action when set to Basic
configuration mode. See
Configuration on page8
.
Note:
When the sensor is placed into Custom configuration
mode, DIP switch 2 set to On, all other DIP switch and Mode
button settings are ignored.
Set Space and Address
Two rotary switches on the sensor electronics provide for Space and
Address assignment for the sensor. By default, these switches are set to
Space1, Address1. Commands are shared by all devices within a given
space.
1. Set the Space rotary switch to the desired number (1 through 16)
for the space you want the sensor to control.
2. Set the Address rotary switch to desired address (1 through 16) for
the sensor identification in the selected space.
Note:
Do not duplicate a device Address within the same Space.
Dual Tech Wall-mount Occupancy Sensor Page 6 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Wall-mount Occupancy Sensor
DIP Switches
DIP switches on the sensor electronics provide for additional
configuration options including Use Custom Config, Vacancy Timeout,
Enable/Disable detection LEDs, PIR Only Mode, and the ability to restore
the sensor to its factory defaults.
Switch # Use
1Unused (leave Off)
2Enable/Disable Custom Config Mode
• When “Custom Config” is set to On (the default
setting), all other local DIP switch settings are
ignored. Instead, the settings made by the
ElahoAccess App are used.
• When “Custom Config” is set to Off, also known as
Basic configuration mode, the local DIP switch
settings for Vacancy Timeout, Enable PIR LED, and
dual technology features are used. Sensor actions
can be adjusted using the program [MODE] button.
See
Configuration on page 8
.
3 and 4 Vacancy Timeout
• 5 min = Switches 3 and 4 are Off
• 15 min = Switch 3 is Off and Switch 4 is On (default)
• 30 min = Switch 3 is On and Switch 4 is Off
• Auto = Both switches are On
5Detection LEDs
• When set to On (the default setting), the occupancy
detection LEDs illuminate when movement is
detected.
• When set to Off, the occupancy detection LEDs are
disabled unless the unit is in Walk Test mode.
6PIR Only Mode
• When set to On, acoustic detection technology is
disabled for the sensor.
• When set to Off (the default setting), both PIR and
acoustic detection technologies are used by the
sensor.
7Unused (leave Off)
8Restore to Defaults at boot
• When set to On and power is cycled to the sensor,
the unit restores to its factory default settings.
• Off is the default setting.
Dual Tech Wall-mount Occupancy Sensor Page 7 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Wall-mount Occupancy Sensor
Power Up
All EchoConnect terminations in the system must be made before
applying power to the system and sensor. When the sensor is powered,
the PIR and acoustic detection LEDs illuminate for one minute for
calibration and warm-up, and then return to normal operation according
to the configuration.
Both the PIR and acoustic detection features of the sensor will
automatically adjust the sensitivity threshold to eliminate nuisance
tripping. During this time, configuration is not allowed and no events are
triggered.
Operation
Dual Technology
When both PIR and acoustic detection are used, the following logic is
used:
• When the space is vacant, PIR detection and manual control can
switch the state to occupied.
• When the space is occupied, PIR, acoustic detection, and manual
control can reset the vacancy timeout.
• When occupancy in the space has only been triggered by acoustic
detection for 60 minutes, acoustic detection is disabled until the
next PIR detection event.
PIR (only) Detection
When acoustic detection is disabled (DIP switch 6 set to On), the
following logic is used:
• When the space is vacant, PIR detection and manual control can
switch the state to occupied.
• When the space is occupied, PIR detection and manual control can
reset the vacancy timeout.
Configuration
Basic
A sensor that is set for Basic configuration mode (DIPswitch 2 set to Off)
can be further configured locally using the other available DIPswitch
settings, and the [MODE] and Auxiliary [A] buttons and their associated
LEDs. See
Program Mode on the facing page
.
Custom
A sensor that is set for Custom configuration mode (DIPswitch 2 set to
On, the default setting) can be customized using the ElahoAccess App.
For more detailed information about custom configuration options
available, see the ElahoAccess App integrated help system.
Dual Tech Wall-mount Occupancy Sensor Page 8 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Wall-mount Occupancy Sensor
Program Mode
MODE AUX
Program Mode allows for local configuration of a
sensor that is set for Basic configuration mode (DIP
switch 2 set to Off). All basic configuration is set
locally on the sensor using the other available DIP
switches, the [MODE] button and associated amber
Mode LED, and the Auxiliary [A] button and
associated blue Auxiliary LED.
The mode and auxiliary buttons and LEDs are
located on the sensor electronics, accessible with
the cover removed. See
Preset below
and
Vacancy Timeout below
for
local Elaho Program Mode configuration instructions.
Preset
While in Basic configuration mode (DIPswitch 2 set to Off), use the
[MODE] and Auxiliary [A] buttons to program the preset that is activated
with an occupancy detected state change. By default, this is Preset1.
When vacancy is detected, the default action event is Off.
Follow these steps to configure the preset for your sensor:
1. Access the sensor electronics and press and hold the [MODE]
button for three seconds to enter “Program Mode.” The Mode LED
lights in amber to indicate the sensor is in Program Mode and the
Auxiliary LED flashes to indicate the preset number controlled by
the occupancy action. By default, this is Preset 1, therefore the LED
will flash one time, pause two seconds and flash again.
2. Press and release the Auxiliary [A] button the number of times that
corresponds to the preset that you want to use. For example, press
the [A] button eight times to set Preset 8. The LED flashes the
number of the preset used.
3. Press and release the [MODE] button to save the current setting.
Vacancy Timeout
Vacancy timeout is the amount of time the sensor waits to take action
after no movement is detected. By default, vacancy timeout is set to 15
minutes (indicated by DIP switch 3 set to Off and 4 set to On; see
DIP
Switches on page 7
). When the vacancy timeout ends, the grace period
begins.
When the sensor detects vacancy, the vacancy timeout period begins. If
the sensor does not detect occupancy again during the vacancy timeout
period, the lights turn off and a 30 second grace period begins.
Dual Tech Wall-mount Occupancy Sensor Page 9 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Wall-mount Occupancy Sensor
Grace Period
The sensor features a 30 second grace period after a vacancy timeout
occurs. During this grace period, if the sensor detects occupancy, it will
turn on or restore the previous lighting condition.
Auto Vacancy Timeout
The “Auto” vacancy timeout setting varies the vacancy timeout between
5 and 30 minutes depending on how often it identifies an occupancy
trigger after a vacancy timeout occurs (during the grace period).
Walk Test
The sensor offers a Walk Test mode, which shortens the vacancy timer to
10seconds and allows for simple and quick verification of the sensor’s
coverage and range in the installed space.
[Walk Test]
button
1. Prepare the site for configuration.
a. Make certain the sensor and lighting loads are powered and
connected for control by the Elaho control system.
b. You will need direct access to the sensor in order to place it into
Walk Test mode.
2. Press the [Walk Test] button on the bottom of the sensor to enable
the Walk Test feature. A green LED flashes, indicating Walk Test is
enabled and the vacancy timer is shortened to 10seconds.
3. Move throughout the space, including corners and areas that may
be obscured from line of sight to the sensor. Each time the sensor
detects movement, the lens illuminates red. If acoustic detection is
enabled, any sound detected illuminates the lens green.
4. As needed, adjust the angle of the sensor head to obtain optimal
detection in the space.
5. Walk Test mode automatically exits and the sensor returns to
normal operation after five minutes. You can also manually
terminate by pressing the [Walk Test] button again.
Dual Tech Wall-mount Occupancy Sensor Page 10 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Wall-mount Occupancy Sensor
Sensor Coverage
Narrow Lens
(100 ft)
30.5 m18.3 m
(60 ft)
2.2 m
(7 ft)
1 m
(3 ft)
2.1 m
(6.8 ft)
3 m
(10 ft) 10.7 m
(35 ft)
6.56°
2.5 m
(8 ft)
0C
L
77°
29°
21.5°
14°
5 m
(16 ft)
5 m
(16 ft)
2.5 m
(8 ft)
Top View
Side View
Dual Tech Wall-mount Occupancy Sensor Page 11 of 12 Echoflex

Echoflex Installation Guide
Dual Tech Wall-mount Occupancy Sensor
Wide Lens
19.4°
0
5 m
10 m
(16 ft)
(33 ft)
5 m
10 m
(16 ft)
(33 ft)
15.3 m
7.7 m
4.6 m
1.7 m
(50 ft)(25 ft)(15 ft)(6 ft)
2.1 m
(6.8 ft)
140°
Top View
Side View
Dual Tech Wall-mount Occupancy Sensor Page 12 of 12 Echoflex
Other manuals for Echoflex Elaho
4
Table of contents
Other ETC Security Sensor manuals

ETC
ETC echoflex MOS-IR A Series User manual

ETC
ETC Echo Dual Tech Wall-mount Occupancy Sensor User manual

ETC
ETC Echo Dual Tech User manual

ETC
ETC echoflex MOS-IR Series User manual

ETC
ETC Echoflex Elaho Dual Tech Wall-mount Vacancy... User manual

ETC
ETC Unison Aero UARVSS-5 User manual

ETC
ETC Unison Paradigm User manual

ETC
ETC Echo Dual Tech User manual
Popular Security Sensor manuals by other brands

PCB Piezotronics
PCB Piezotronics 4115K-09A Installation and operating manual

Keysight
Keysight 8478B Operating and service manual

SubSurface Instruments
SubSurface Instruments AQUA TRAC 300 user manual

Ecom
Ecom ECD2800 user guide

Indexa
Indexa HA06 Operation and safety notes

Eterna
Eterna EX360PIRWH installation instructions