ETNA AVS User manual

AVS Control Panel Manual

2
1. Product Information
AVS is a pump control panel having 4.3“ TFT touch screen, uniquely designed high ecient
variable speed control and relay board. The touch control panel is located on front casing
while relay module is located inside. Other than these, Manual / Auto / O Selection
Button, Manual Control Buttons and Interlock Switch are available on front casing. AVS
panel provides control and screen up to 6 pumps with the help of EPLC-6 control system,
relays and switching components. System parameters can be changed on touch screen
with user-friendly interface.
AVS Panel can be used on constant pressure booster or dierential pressure circulation
systems with the help of receiving data from an analog pressure sensor. The panel
especially is recommended to use with frequency inverted pump applications. Apart from
that, it is also possible to use the panel on constant cycle pump systems.
Figure 1: AVS Panel
EPLC-6 Control Panel
Manual / Auto / O
Selection Button
Manual Control
Buttons
Interlock Switch

3www.etna.com.tr
Figure 2: AVS Panel Internal View
* The inside image of the panel may dier from the picture above.
EPLC-6 Control
Unit
Interlock
Switch
Auto/Man Mod
Selection Button
Manual
Operation
Buttons
Panel Project
Pocket
Modbus
Connectors
Control
Connectors
Motor
Connectors
Swichgear
Driver
Contactors
Fuses
EPLC-6 Relay Board
Relays
Electronic Thermic Relay
Power
Supply
Cooling
Fan
Thermostatic
Switch For
Cooling Fan

4
2. AVS Technical Specifications
• Epoxy coated DKP steel body
• Internal cooling with thermostatic control
• IP 54 protection class
• Manual / Autorun option
• Phase absence / unbalance /sequence protection by phase protection relay
• Thermal-magnetic motor protection
• Waterless run protection on booster applications by external floater connection
• Interlocking switch system
• 24V DC external power supply
• Remote control option via dry contact
• Possibility to send Run, Thermal Fault, General Fault data to Building Management System
(BMS) for each pump individually
• Possibility to transfer system parameters to Building Management System (BMS) via MODBUS-
RS 485 data communication protocol (Please check next page for MODBUS Address Table)
• Enabling to control up to 6 cascade assembled pumps by 1 frequency inverter and uniquely
designed controller with 4,3’’ TFT touch screen
• Ability to view; number of pumps working, pump mode, driver frequency, set pressure,
instant pressure, fault indications and date-time information.
• Preventing unauthorized access thanks to password protection support
• Possibility to change settings while system running
• Ability to view working hours of each pump
• Capability of collecting data with high precision using advanced pressure sensor calibration
and o-set menu
• High pressure protection with adjustable value and duration
• Low pressure protection with adjustable value and duration against low water level and
cavitation
• Optimum reaction time according to system needs with the help of adjustable pump on/o
time
• Adjustable wake-up pressure
• Adjustable cyclic change over time
• Manual pump back up
• Booster and circulating mode selection
• Selection mode of with/without driver
• Adjustable PID reaction speed
• Adjustable driver switch o frequency value on frequency inverted systems
• Ability to run pumps with maximum speed via mains supply contactors in case driver in fault
mode
• Ability to run pumps with maximum speed via mains supply contactors in case driver in fault
mode preventing system blockage
• Adjustable maximum driver working frequency
• Adjustable minimum inverter working frequency
• Periodic maintenance reminder
• Turkish / English language option
• 100 events history logging capacity
• Real-time date / time information
• 12 V DC internal isolated 4-20 mA transmitter supply and 2 transmitter inputs

5www.etna.com.tr
3. Menus
To reach device menus, tap the symbol on the main screen to reach the password
screen. Once you enter your password, you can make any desired changes in the settings
menu, either when the system is working or after halting it. Changes made to the system
will not be saved unless the symbol on screen is tapped. Simply tap the relevant
symbol for the sub-menu to reach it, and to return to a previous menu, simply tap the
symbol.
The up-down arrow symbol seen in menus is used to increase or decrease the value
in the box to its left. Simply tap the up arrow icon to increase the value, and the down
arrow icon to decrease it. When the symbol is pressed and held, the value will continually
increase or decrease until the allowed limit. For 3-digit numbers, the relevant digit can be
tapped to make changes.
4. Device Settings
All options about how the system works
can be found in the "Device Settings"
sub-menu that can be reached from the
settings menu. Detailed information
about the content and the eects of
the "Device Settings" is listed below.
4.1 Device Working Mode
Depending on the selection of booster
pump and circulation in the Device
Operation Menu, the EPLC-6 control
unit can work in two dierent modes.
In booster pump mode, the EPLC-6
control unit compares a single data
collected from the 4-20 mA pressure
transmitter to the set value at which
the device is desired to work.
If the pressure data collected from the transmitter is larger than the set value, the system
stays in standby state. If the pressure data collected from the transmitter is smaller than
the set value, the least used pumps are activated in order. If there is a driver in the system,
the first pump is activated by the driver. In the event that a single pump cannot meet the
demand; if there are other pumps, they are activated in order depending on the demand
and work to bring the system's current pressure up to the set value. When demand
decreases -or as the current pressure value surpasses the set value- the pump with the
driver slows down and attempts to match the reference pressure value. The pumps are
deactivated if they are no longer needed.
DEVICE SETTING
SENSOR SETTINGS PROTECTION SETTINGS
DRIVER SETTINGS
MANUAL PUMP CONTROL
PUMP SETTINGS
DEVICE WORKING MODE
MAINTENANCE PERIOD
BACK
OPERATING MODE
HYDROPHORE
CIRCULATION
SAVE BACK
Figure 3: Device Settings Menu
Figure 4: Device Operation Mode Selection Menu

6
If in circulation mode, the EPLC-6 control unit first calculates the dierence between two
sets of data collected from the 4-20 mA pressure transmitters (transmitter1-transmitter2,
where transmitter1 is the value gathered from the transmitter at the entrance of the fixture
and transmitter2 is from the transmitter at the exit of the fixture) and then compares
this to the set dierential pressure value at which the device is desired to work. When
the system is run, if the dierence between the values acquired from the transmitters is
larger than the set value, the system keeps running with a single pump. If there is a driver
in the system, it operates at minimum frequency. If the dierence in pressure between
transmitters is smaller than the set value, and if there is a driver in the system, the pump
with the driver accelerates and attempts to match the reference dierential pressure. If
necessary, that is to say, if a single pump cannot meet the demand, the other pumps are
activated in order and deactivated if the need is met. If the dierence between the two
transmitter values goes above the set value again (if the demand is met), a single pump is
kept in operation. If there is a driver, it operates at minimum frequency.
PARAMETER BOOSTER CIRCULATION
MINIMUM PRESSURE PROTECTION TIME 30 seconds N/A
MAXIMUM PRESSURE PROTECTION TIME 10 seconds 10 seconds
SWITCH OFF TIME 30 seconds 30 seconds
SWITCH ON TIME 30 seconds 30 seconds
PERIODIC WORK 12 hours 12 hours
PUMP COUNT 3 pumps 3 pumps
WAKE UP PRESSURE 0,5 bar 0,2 bar
MAX. PRESSURE 12 bar 12 bar
DRIVER SWITCH OFF FREQ. 44 Hz 30 HZ
WAKEUP TIME 5 seconds 0
SLEEPING TIME 30 seconds 0
NUMBER OF REPEAT 5 5
MINIMUM PROTECTION PRESSURE 2 bar 0.1 bar
SENSOR SELECTION SENSOR 1 SEN1-SEN2
SPARE PUMP 0 0
SPARE PUMP ON/OFF 0 0
DRIVER SELECTION 1 1
SET PRESSURE 8 bar 1 bar
SENSOR TYPE 16 bar 10 bar
Table 1. Panel Factory Settings

7www.etna.com.tr
4.2 Pump Settings
Settings and changes such as adjusting
and changing the number of active
pumps in the system, the activation or
deactivation periods of back-up pumps,
cyclic change-over (periodic work) time,
the wakeup dierential pressure and the
manual spare pump specification can be
made from the "Pump Settings" menu.
PUMP SETTINGS
PUMP COUNT SWITCH ON TIME WAKEUP PRESSURE
SPARE PUMP SWITCH OFF TIME
SEC.
SEC.
HOUR
SPARE PUMP ON/OFF
PERIODIC WORK
SAVE BACK
0151 012
0156 0.2
Figure 5: Pump Settings Menu
Pump Count: The number of pumps can be determined from the number of pumps field
shown on the screenshot in Figure 5, by touching the icons. Pump number can be
increased up to 6 pumps.
Switch On Time: For systems with multiple pumps (2-6 pumps), the pump activation
period is the time required for other pumps to be activated in order after the 1st one, in
case of need. In driver mode, if the driver has reached maximum frequency and the set
value is higher than the current value, the activation period begins counting down in the
background. If the set pressure value is not reached by the end of the activation period,
a stand-by pump steps in. This process continues for all stand-by pumps until the current
pressure value reaches the set pressure value.
In systems without a driver or in case of an error in the driver;
The activation period shortens by 10 times in booster pump mode. For example, if the
activation period has been set to 30 seconds, it drops to 3 seconds.
The activation period gets multiplied in circulation mode. For example, if the activation
period has been set to 30 seconds, it lengthens out to 60 seconds in systems without
drivers or in case of driver errors. Factory setting is 30 seconds.
Switch O Time: For systems with multiple pumps (2-6 pumps), the pump deactivation
period counts down in the background when there are multiple active pumps and when
the current pressure value is higher than the set value at the same time. If the current
pressure value does not decrease below the set value by the end of the set deactivation
period, pumps deactivate in order.
In systems without a driver, or in case of an error in the driver;
The deactivation period shortens by 10 in booster pump mode. For example, if the
deactivation period has been set to be 30 seconds, it fixture is 0 but to 3 seconds.
The deactivation period gets multiplied by 2 in circulation mode. For example, if the
deactivation period has been set to 30 seconds, it lengthens out to 60 seconds in systems
without drivers or in case of driver errors. Factory setting is 30 seconds.
Wakeup Pressure: Wakeup pressure is the dierential pressure between the set system
pressure and the pressure value for pump activation.
In booster pump mode, wakeup pressure is the dierential pressure value at which the
wakeup (pump activation) period starts counting, which is identified to prevent the system
from continuously activating and deactivating and which can be adjusted as needed.

8
For example, if the set pressure is 8 bars and wakeup pressure is 0.5 bars, a standby pump
will activate after the current system pressure drops below 7.5 bars and the wakeup period
is complete. The factory settings for booster pump mode has been set to 0.5 bars.
However, the concept of wakeup pressure diers in circulation mode. Since a single pump
is always active in circulation systems, the wakeup pressure mentioned in the menu is a
variable that only applies in systems without drivers, or with driver errors. 1. This variable,
applied to the pumps activated after the first one, activates standby pumps after the
activation period is completed and the current dierential pressure is less than the set
pressure for the fixture by the wakeup pressure. If the current dierential pressure value is
as high as the wakeup pressure value than the set value, the active pumps are deactivated
after the deactivation period is complete. The factory settings for circulation mode has
been set to 0.2 bars.
Graph 1: Pump ON / OFF vs. Wake-up Pressure on Constant Pressure Mode
t1 t1
t2 t2
P (bar)
t (sn)
Pump on demand
Set Pressure
.
p
t (sn)
Wake up zone
Wake-up
pressure
p : Wake-up pressure
t1 : Pump start delay time
t2 : Pump stop delay time

9www.etna.com.tr
Graph 2: Pump ON / OFF vs. Wake-up Pressure on Circulation Mode
t2
t1
t2
t1 t2 t3 t4 t5 t6
p
.
p
.
p : Wake-up pressure
t1 : Pump start delay time
t2 : Pump stop delay time
P (bar)
t (sn)
t (sn)
Pump on demand
Stable Working Zone
Pump stopping zone
Pump requesting zone
Set Pressure
Cyclic Change-Over: The cyclic change-over (periodic work) is an algorithm developed to
ensure the pumps to be working at the same capacity. The pump with the least working
time in booster pump mode is activated as the first pump. In driver mode, no changes
based on cyclic change-over periods are made on pumps in operation that work with a
driver until the system is in sleep mode. On the next run, it operates with the least used
pump being activated.
In circulation mode, when the systems starts, it first activates the least used pump. Once
the designated cyclic change-over time is over, pumps are exchanged.
Back-up pump: If the user wants to manually deactivate any pump in the system, they
need to select the relevant pump and, after activating the Back-up Pump On/O selection,
tap the symbol.
4.3 Sensor Settings
Settings such as set pressure, sensor
calibration and sensor selection can be
made from the "Sensor Settings" menu.
NOTE: The sensor mentioned on
the menu represents the pressure
transmitter.
SENSOR SETTINGS
SEN1 CALIBRATIONMAX. PRESSURE
10 BAR
16 BAR
25 BAR
SENSOR 1
SENSOR 1
SEN 1 SEN 2
AUTOMATIC
SENSOR SELECTION
SEN2 CALIBRATION
SAVE BACK
RESET
RESET 1.00
SET PRESSURE
8.0
1.00 00
00
Figure 6: Sensor Settings Menu

10
Set Pressure: Set pressure is the pressure value at which the system is expected to work.
In booster pump mode, it is associated with the value read o of pressure transmitters.
In circulation mode, it is associated with the dierence between the values read o of
transmitter1 and transmitter2.
Maximum Pressure: Maximum pressure is the pressure value corresponding to the 20 mA
maximum value on pressure transmitters. A standard selection between 10, 16 and 25 bars
can be made on the screen.
Sensor Selection: Sensor1 is selected as the factory setting in booster pump mode. If
the Sensor1 port belonging to the EPLC-6 is damaged, Sensor2 can be selected from the
menu after the pressure transmitter is connected to the Sensor2 port. If a transmitter
is connected to both ports and Automatic is selected, the system continues operating
according to the value read o of Sensor2 without stopping when Sensor1 is damaged.
Sensor1- Sensor2 is selected as the factory setting in circulation mode. Sensor1 or Sensor2
cannot be selected alone in this mode. However, if Sensor2 is not connected or cannot be
reached when Sensor1- Sensor2 is selected, the system will issue a warning and continue
operating according to the Sensor1 value. If Sensor1 is not connected or cannot be reached,
the system is blocked.
Sensor Calibration: Through the sensor calibration settings, any dierence between the
pressure value from transmitters and the actual pressure value of the fixture can be fixed. If
the pressure value seen on the main screen is considered to be incorrect, it can be checked
as follows; when the pressure value of the fixture is 0 but the value shown
in the rightmost box is not 0, the symbol can be tapped to set the pressure value
in the fixture to 0. If the pressure of the fixture is not 0, the sensor maximum settings are
selected correctly but the pressure value collected from the manometer is incorrect, the
value in to the right of the symbol can be increased or decreased at
the rate of 20% to match the pressure value of the fixture and the pressure value shown on
the main menu. This process can be done separately for each of the two sensors.
Maximum Protective Pressure: A maximum pressure is set through this parameter to
protect the system from high pressure conditions. If system pressure is higher than the
Maximum Protective Pressure throughout the set Maximum Protective Pressure Period,
the system will enter high pressure protection mode and all operating pumps will halt. If
the system pressure falls below the set value, the system will start operating again which
means that the system will resume operating once the working conditions have been
suitably met.
4.4 Protection Settings:
The maximum and minimum pressure
values and the time period required
for the activation of these protective
pressure properties can be adjusted in the
"Protection Settings" menu. As a result, the
system is protected from working under
damaging pressure conditions, cavitation
or operating without water.
PROTECTION SETTINGS
NUMBER OF REPEATMINIMUM PRESSURE
PROTECTION TIME
MINIMUM PRESS,
PROTECTION PRESSURE
BAR
SAVE REMOVE BLOCKED BACK
0.3
MAXIMUM PROTECTION
PRESSURE
BAR
2.0
SEC.
120
MAXIMUM PRESSURE
PROTECTION TIME
SEC.
015
5
Figure 7: Protection Settings Menu

11 www.etna.com.tr
Maximum Protective Pressure Period: Maximum protective pressure period is the time
period required for the activation of this protection if the current pressure value of the
system surpasses the maximum pressure value. All operating pumps halt during this
period if the current pressure is larger than the maximum pressure.
Minimum Protective Pressure: The Minimum Protective Pressure parameter is used to
protect the system from long-term low pressure, and to prevent damage to the system
caused by cavitation or operating without water. If system pressure is lower than the
Minimum Protective Pressure throughout the set Minimum Protective Pressure Period, the
system will enter low pressure protection mode and all operating pumps will halt. If the
minimum protective pressure value is 0, the protection will be disabled.
Minimum Protective Pressure Period: Minimum protective pressure period is the time
period required for the activation of this protection if the current pressure value of the
system is below the minimum pressure value. All operating pumps halt during this period
if the current pressure is smaller than the minimum pressure.
Reboot Count: If the minimum protective pressure is activated in booster pump systems,
the system is expected to reboot periodically. Reboot count is a function that allows the
system to start operating again after a set waiting period following the halt caused by
the minimum pressure protection. Reboot count can be set up to 5. The waiting period
increases periodically after the low pressure protection kicks in. The 2 minute period of the
1st attempt is set to be 50 minutes for the 5th attempt. If the pressure does not rise after
the set reboot count, the system gets blocked.
NOTE: If the reboot count is set at 0, the system gets blocked after the 1st low pressure error.
Unblocking: If system intervention is requested without the full waiting time after the
system enters low pressure protection mode and is blocked, the symbol
can be selected for a reset.
Reaction Speed: Reaction speed is a parameter that adjusts the variation in driver speed,
or the reaction speed of the driver, depending on the dierence between set pressure
value and the current pressure value in driver mode. Reaction speed can be adjusted
to 3 levels; In the 1st level, the reaction speed on the 1st level is slow and as the level is
increased, the rotation speed in the reference speed relayed by EPLC-6 panel to the driver
also increases. Therefore, the pump rotation speed that works with the driver also varies
in proportion to the reaction speed.
4.5 Driver Settings:
The Driver Settings menu allows changes
to be made to the automatic PID settings,
as well as the reaction speed and the
driver frequency settings that are based
on it. If the driver selection symbol seen
in Figure 8 is active, the system works in
driver mode.
DRIVER SETTINGS
DRIVER SELECTION
SAVE FREQUENCY SETTINGS BACK
1
0-10V CALIBRATION
RESPONSE RATE
000
20
WAKEUP TIME
SLEEPING TIME
SEC.
SEC.
05
REVERSE WORKING
Figure 8: Driver Settings Menu

12
Sleeping Period: Sleeping period is the condition when, in booster pump mode, the
system's current pressure is higher than the set pressure and when pumps stand by ready
to work, without working. In systems with drivers, if the system pressure is above the
set value and if the driver frequency is lower than the deactivation frequency value and
remains that way throughout the sleeping period, the system enters sleep mode.
Wakeup period: In booster pump mode, when the driver is active but the system pumps
are inactive, the wakeup period is the time required to activate the pump operated by
the driver in situations where system pressure is less than the set value by the wakeup
pressure value.
Maximum Frequency: Maximum frequency is the parameter determining the maximum
frequency value the driver will operate on.
Minimum Frequency: Minimum frequency is the parameter determining the minimum
frequency value the driver will operate on. The minimum value can be set to 25 Hz.
Driver Switch-o Frequency: This parameter is only valid when the driver is active and in
booster pump mode, and can be used to adjust the frequency the driver will deactivate it.
When the relationship between valve pressure with non-operating pumps and set pressure
is evaluated, dierent operating values desired for pumps should be kept in mind and the
driver deactivation frequency should be set accordingly. In other words, if the set values
for active pumps in a system are increased, so should the driver deactivation frequency.
Parameters belonging to Danfoss FC-51 driver located in control panel are as follows;
4.5.1 Driver Frequency
Settings:
The frequency values relayed as
references by the EPLC-7 panels
(max/min driver frequencies, driver
deactivation frequency) can be
adjusted in the Driver Frequency
Settings.
DRIVER FREQUENCE SETTINGS
HZ
SAVE BACK
25
DRIVER MAX. FREQUENCE
DRIVER MIN. FREQUENCEDRIVER SWITCH OFF FREQ.
HZ
50
HZ
30
Figure 9: Driver Frequency Settings Menu

13 www.etna.com.tr
Please follow below instructions in order to copy parameters;
0-50: First must be set to 1 and press OK, all the parameters inside the driver are transferred to Keypad
0-50: After must be set to 2 and press OK, all the parameters inside Keypad are transferred to the
driver
0-50: if set to 3 and press OK, all the parameters except Motor power inside Keypad are transferred
to the driver
Relay Terminals;
01: COM
02: NO
03: NC
Parameter
No Parameter Name Set Value
0-40 [Hand On] Key on LCP 0=OFF
0-41 [O / Reset] Key on LCP 2= only Reset active
1-00 Configuration Mode 0= Speed Open Loop (Factory Setting
1-01 Motor Control Principle 0= U/F
1-20 Motor Power Must be set to value on motor label
1-22 Motor Voltage Must be set to value on motor label
1-23 Motor Frequency Must be set to value on motor label
1-24 Motor Current Must be set to value on motor label
1-25 Motor Nominal Speed Must be set to value on motor label
1-71 Start Delay 1.0 sec
3-15 Reference Resource 1 1= Analog input 53 (Factory setting)
3-41 Ramp 1 Ramp up Time Must be set according to the product and motor (ie. 3.00 sec)
3-42 Ramp 1 Ramp Down Time Must be set according to the product and motor (ie. 3.00 sec)
4-12 Motor Speed Low Limit [Hz] 25.00 Hz
4-14 Motor Speed High Limit [Hz] 50.00 Hz
5-10 Terminal 18 Digital Input 8= Forward start (Factory setting)
5-12 Terminal 27 Digital Input 1= Reset (Factory Setting)
5-40 Function Relay 2= Driver Ready
6-10 Terminal 53 Low Voltage Must be set to 5 .00 V
6-11 Terminal 53 High Voltage 10.00 V (Factory setting)
6-14 Terminal 53 Low Ref./Feedb. Value 25 Hz.
6-15 Terminal 53 High Ref./Feedb. Value 50 Hz.
14-20 Reset Mode 5= Automatically reset 5 times
14-90 [7] High Current Reset must be set 4 (automatic reset after 3 minutes)
12
Forward Start
0-10 V. input
AI1 Com
18
19
20
27
29
33
42
50
53
55
60

14
4.6 Manual Pump Control:
Manual pump control is used to
control the rotational direction of
pumps while starting them up. With
selections being made through the
pump-specific symbols on screen, the
driver or the network will keep the
selected pump active for 3 seconds
through the relevant contactors in
single-driver multiple pump systems. In
the meantime, the rotational direction
and the direction specified on the
pump should be checked to make sure
they are the same. While checking
for this issue, the automatic selection
in Figure 10 should be manually
changed and the select button on the
front cover of the panel should be
set to 0. The external start belonging
to the panel must be set to passive.
4.7 Maintenance Period:
Maintenance Period is an adjustment
screen for the panel to remind the user
of a future service and maintenance
date after the system is put to use. The
on/o selection in the upper leftmost
corner of Figure 11 can be activated to
select and set the month, day and time
of the desired date. This period is synced
with the real date and time on the panel.
5. General Settings
Settings that are not system specific
such as the system mode, operating
pressure and pump count can be
adjusted in the General Settings menu.
The error history can also be accessed
from this menu.
MANUAL PUMP CONTROL
PUMP1 DRIVER
PUMP2 DRIVER
PUMP3 DRIVER
PUMP4 DRIVER
PUMPA5 DRIVER
PUMP6 DRIVER
PUMP1 LINE AUTOMATIC
PUMP2 LINE
PUMP3 LINE
PUMP4 LINE
PUMP5 LINE
PUMP6 LINE BACK
MAINTENANCE PERIOD
SAVE BACK
HOUR
ON/OFF
23
DAY
30
MONTH
12
GENERAL SETTINGS
BACK
LANGUAGE SETTINGS COMMUNICATION SETTING
PROGRAMMED WORK SETT.HISTORY
DATE-TIME SETTINGSSPECIAL SETTINGS
Figure 10: Manual Pump Control Menu
Figure 11: Maintenance Period Menu
Figure 12: General Settings Screen

15 www.etna.com.tr
5.1 Language Settings:
A selection between Turkish and
English can be made in the language
settings menu.
5.2 Communication
Settings:
PARITY, STOP BIT, BAUD RATE and
DEVICE ID adjustments can be made
in Modbus communication settings. If
the same building automation system
will be used to communicate with a
multitude of devices, a specific ID for
each device is defined by the panel
connected to the system through the
DEVICE ID setting.
(YOK=NONE, TEK=ODD, CİFT=EVEN)
Fixed settings can be adjusted as
shown in Figure 14 for other properties.
5.3 Date and Time Settings:
The real date and time belonging to the
device can be calibrated in the Date
and Time Settings menu as shown in
figure 16.
LANGUAGE SELECT
TURKISH
ENGLISH
SAVE BACK
MODBUS COMMUNITATION SETTING
PARITY
YOK
TEK
CIFT
2400Kbps
9600Kbps
19200Kbps
38400Kbps
BALIDRATE
SAVE BACK
001
STOP BIT
DEVICE ID
1 bit
2 bit
DATE- TIME SETTINGS
SAVE BACK
DAY
13
MONTH
11
YEAR
2017
HOUR
09
MINUTE
38
SECOND
46
Figure 13: Language Selection Screen
Figure 14: Modbus Communication Settings
Figure 15: Date and Time Settings

16
Table 2: AVS Panel Modbus Address Table
REGISTER ADDRESS UNIT RATIO VALUE RANGE DESCRIPTION
40.000 - - 0 - 1 After sales service maintenance alarm. If output is 1 alarm
exists, If output is 0 alarm does not exist.
40.001 - - 0 - 1 Panel start - stop. If output is 1, panel is in start mode, If
output is 0, panel is in stop mode
40.002 - - 0 - 1 Blockage fault information. If output is 1, blockage fault
exists; If output is 0, blockage fault does not exist
40.003 - - 0 - 1 Phase fault information. If output is 1, phase fault exists; If
output is 0, phase fault does not exist.
40.004 - - 0 - 1 No water fault infromation. If output is 1, no water fault
exists; If output is 0, no water fault does not exist
40.005 - - 0 - 1 Sensor 1 fault information. If output is 1, sensor 1 fault exists;
If output is 0, sensor 1 fault does not exist.
40.006 - - 0 - 1 Sensor 2 fault information. If output is 1, sensor 2 fault exists;
If output is 0, sensor 2 fault does not exist.
40.007 - - 0 - 1 High pressure fault information. If output is 1, high pressure
fault exists; If output is 0, high pressure fault does not exist.
40.008 - - 0 - 1 Driver fault. If output is 1, driver fault exists; If output is 0,
driver fault does not exist.
40.009 Second - 0 - 65535 Low pressure countdown. In case low pressure fault,
countdown starts
40.010 Hz 0,1 450 - 650 Driver frequency
40.011 - - 0 - 1 Operating Mode. If output is 1, circulation mode; If output is
0, booster mode
40.012 Bar 0,1 0 - 65535 Line pressure.
40.013 Bar 0,1 0 - 65535 Set pressure.
40.014 - - 0 - 65535 Pump 1 data. 11 Pump Run Mode, 22 Pump Standby Mode,
33 Pump Backup, 44 Thermal Protector Fault
40.015 - - 0 - 65535 Pump 2 data. 11 Pump Run Mode, 22 Pump Standby Mode,
33 Pump Backup, 44 Thermal Protector Fault
40.016 - - 0 - 65535 Pump 3 data. 11 Pump Run Mode, 22 Pump Standby Mode,
33 Pump Backup, 44 Thermal Protector Fault
40.017 - - 0 - 65535 Pump 4 data. 11 Pump Run Mode, 22 Pump Standby Mode,
33 Pump Backup, 44 Thermal Protector Fault
40.018 - - 0 - 65535 Pump 5 data. 11 Pump Run Mode, 22 Pump Standby Mode,
33 Pump Backup, 44 Thermal Protector Fault
40.019 - - 0 - 65535 Pump 6 data. 11 Pump Run Mode, 22 Pump Standby Mode,
33 Pump Backup, 44 Thermal Protector Fault
40.020 - - 0 - 65535 Number of pumps on the system
40.021 Minutes 6 0 - 65535 Pump 1 total run time
40.022 Minutes 6 0 - 65535 Pump 2 total run time
40.023 Minutes 6 0 - 65535 Pump 3 total run time
40.024 Minutes 6 0 - 65535 Pump 4 total run time
40.025 Minutes 6 0 - 65535 Pump 5 total run time
40.026 Minutes 6 0 - 65535 Pump 6 total run time
40.027 - - 0 - 1 Low pressure fault. . If output is 1, low pressure fault exists; If
output is 0, low pressure fault does not exist.

17 www.etna.com.tr
5.4 History Records:
100 past event records with detailed
information on the date, hour and error
is shown in the Event Records section.
The up and down arrows on the right
side of the screen shown in Figure 16
can be moved to display all the errors
in the event records.
6. General Information
Device version number, drivers for each
pump, network and total operation
times can be viewed from the General
Information menu.
HISTORY RECORD
02/06/2017 09:09:05 PUMP 1 HIGH CURRENT FIXED
02/06/2017 09:09:04 PUMP 2 HIGH CURRENT FIXED
02/06/2017 09:09:04 PUMP 3 HIGH CURRENT FIXED
02/06/2017 09:09:04 PUMP 4 HIGH CURRENT FIXED
02/06/2017 09:08:58 EXTARNAL START OCCURED
02/06/2017 09:08:57 PUMP 4 HIGH CURRENT
02/06/2017 09:08:57 PUMP 3 HIGH CURRENT
02/06/2017 09:08:57 PUMP 2 HIGH CURRENT
02/06/2017 09:08:57 PUMP 1 HIGH CURRENT
11/05/2017 15:08:19 HIGH PRESSURE FIXED
11/05/2017 15:08:16 HIGH PRESSURE
11/05/2017 15:08:08 SENSOR 2 READY
11/05/2017 15:07:00 SENSOR 2 ERROR
26 / 100 BACK
GENERAL INFORMATION
DRIVER
CPU SERIAL NUMBER
<1F002A - 34355110 - 34343530 > < SV 2.1.001>
0.0
0.0
0.0
0.0
0.0
0.0
PUMP 1
PUMP 2
PUMP 3
PUMP 4
PUMP 5
PUMP 6
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
TOTAL (HOUR)
BACK
LINE
Figure 16: History Record Screen
Figure 17: General Information Screen

18
W
H
L
Figure 18: AVS Panel Dimensions
H: Height
W: Width
L: Length
7. Dimensions

19 www.etna.com.tr
Table 3: AVS Panel Dimensions Table
Motor Power 1 Pump Systems 2 Pump Systems 3 Pump Systems
HP KW L (mm) H (mm) W (mm) L (mm) H (mm) W (mm) L (mm) H (mm) W (mm)
0,5 0,37 500 700 260 500 700 260 600 800 260
0,75 0,55 500 700 260 500 700 260 600 800 260
10,75 500 700 260 500 700 260 600 800 260
1,5 1,1 500 700 260 500 700 260 600 800 260
2 1,5 500 700 260 500 700 260 600 800 260
3 2,2 500 700 260 500 700 260 600 800 260
4 3 500 700 260 600 800 260 600 800 260
5,5 4 500 700 260 600 800 260 600 800 260
7,5 5,5 500 700 260 600 800 260 600 800 260
10 7,5 500 700 260 600 800 260 600 800 260
15 11 500 700 350 700 900 350 800 1000 350
20 15 500 700 350 700 900 350 800 1000 350
25 18,5 600 800 350 800 1000 350 1000 1200 350
30 22 600 800 350 800 1000 350 1000 1200 350
Motor Power 4 Pump Systems 5 Pump Systems 6 Pump Systems
HP KW L (mm) H (mm) W (mm) L (mm) H (mm) W (mm) L (mm) H (mm) W (mm)
0,5 0,37 700 900 260 800 1000 350 800 1000 350
0,75 0,55 700 900 260 800 1000 350 800 1000 350
10,75 700 900 260 800 1000 350 800 1000 350
1,5 1,1 700 900 260 800 1000 350 800 1000 350
2 1,5 700 900 260 800 1000 350 800 1000 350
3 2,2 700 900 260 800 1000 350 800 1000 350
4 3 700 900 260 800 1000 350 800 1000 350
5,5 4 700 900 260 800 1000 350 800 1000 350
7,5 5,5 700 900 260 800 1000 350 800 1000 350
10 7,5 700 900 260 800 1000 350 800 1000 350
15 11 1000 1200 350 1000 1200 350 1200 1400 350
20 15 1000 1200 350 1200 1400 350 1200 1400 350
25 18,5 1000 1200 350 1200 1400 350 1200 1400 350
30 22 1000 1200 350 1200 1400 350 1400 1600 350

20
8. Maintenance
General Information
Danger High Voltage:
WARNING: Please wait 5 minutes before any maintenance or after sales intervention to
the capacitors be discharged.
Check List:
• Please be sure that there is no dust on cooling fun and ventilation system.
• Please be sure that ambient temperature is within the allowable range.
• Please be sure to cut the electricity before any intervention.
• Please consider pump and motor parameters always.
• Please get in contact with manufacturing company for more details.
Check History Record:
• It is possible to get information about working conditions on History Record.
9. Troubleshooting
WARNING: Please be sure to cut the
electricity before any intervention.
Warnings and Faults:
In case there is an alarm or fault
occurred, “ icon starts to blink on the
upper side of main screen. It is possible
to view existing alarms and faults by
touching that icon.
ALARM SCREEN
MINIMUM PRESSURE FAULT 38 SEC. BACK
Figure 19. Alarm Screen
Table of contents
Other ETNA Control Panel manuals