Evacuator Synergy Zone Leader User manual

www.evacuatoralarms.com
Antenna
Evacuator Synergy Zone Leader
Evacuator Synergy Zone Leader user operating instructions and Setup
Thank you for choosing the Evacuator Synergy RF Wireless Alert system. In order for you to realise
the full potential and reliability of this Category One Wireless system it is vitally important that you
read this user manual in full before attempting to use the system. Failure to understand the correct
installation method and functions of the system may lead to intermittent and unreliable
connectivity.
We would be delighted to assist all Evacuator Alarm clients with free Telephone Support during
office normal hours. For assistance please contact our Technical Support Team on 0845 130 7258 or
alternatively email us on technical@evacuatoralarms.com.
Specification Overview (All models)
Cable and wire free operation. 40 Devices per Zone. Zone Master allows multiple zones to be
controlled by One Base Station. The Base Station will scroll through its connected zones in numerical
order
Zone LED
Device LED
Sounder Flasher
Antenna

www.evacuatoralarms.com
Device Numbering Synergy Board
As you can see above there are 3 dials, dial 1 on the left is NOT needed for device numbering. Dial 2
and 3 are used for your device numbering, as you can see dial 2 is set to 0 and dial 3 to number 3.
This makes the device number 03. to set a device to number 20 for example dial 2 would be set to 2
and dial 3 set to 0.
Note: When setting the dials, please use the setting driver supplied
Zone Dial (Dial 1)
This dial is factory set to "0" and will not need to be changed unless you wish to separate a number
of systems that will be operating within 2km of each other. This will be used for example if there are
several contractors using the system on the same site or in the same area. It may also be beneficial
to separate zones for floors on larger projects.
Device Dials (Dial 2 and 3)
These dials are used to number the Devices as above. Dial 2 will only be used from 0-4, Dial 3 will use
0-9.
Please Note –This PCB will always need to be set to Device number 01, this allows communication
between the Synergy and Zone Master PCB

www.evacuatoralarms.com
Device Numbering Zone Master PCB
Frequency Dial
This dial must be common to your 600 Zone Master Touch Screen Panel, from default this is set
Frequency 0. Your chosen frequency must be common throughout the site
Device/Zone Dial
This Dial is your Zone number dial, this is Dial assigns your zone leader its number. This must go up in
numerical order so the first Zone will be number 1, second number 2 etc. Your 600 Touch Screen
panel will be set to 0 at all times
Fitting the Antennas
The rubber duck antenna should now be fitted to the Silver TNC docking point located on the front
cover. The Antenna should be placed over the TNC connector and screwed in a clockwise motion
until it locates into place. Test that it has been located correctly by gently pulling on the Antenna in
an outwards motion.
Pairing The Zone Master System
1. Power on the 600 Touch Screen Base Station ensuring it is set to the correct Zone Number
(0) and the Antenna is in place
2. Within 30 seconds of powering on the Touch Scree Base Station connect the battery of Zone
Master number 1 ensuring all the dials, antennas etc have been set and are in place
3. The Zone Master “ZONE”LED should settle in to a steady couple of times per minute flash
after a short wait. Once this happens this shows connection between the Zone Master and
600 Touch Screen Base Station
4. Connecting the Synergy Side of the system is the same as a usual system. Set your “00”
device ensuring the frequency dial is common to the dial on the Synergy PCB in the Zone
Master. Connect the battery on the “00”device and the “DEVICE”LED will settle down into
its twice per minute flash
5. You are now free to add further Zone Masters, do this by connecting the power cable and
repeating steps 3 & 4. There will be no need to switch further Zone Masters on within the 30
second Base Station bootup, these can be switched on and paired as and when needed
(Please make sure the zone numbers go in numerical order as repeating a zone number
will confuse the system)
Frequency Dial
Device/Zone
Dial

www.evacuatoralarms.com
Status LED
LED
Status
Red & Green alternate flashing
Power Up Sequence
Green Flashing (30 sec interval)
Standby
Blue Flashing (30 sec interval)
Standby Master Device (Set 00)
Red Blinking
Low Battery
Blue Solid
Test Mode
Red Solid
Reset Mode
White Flashing
Alarm Mode
Green Rapid Flashing
Out of Range
Red Rapid Flashing
Out of Range & Low Battery
Final notes before use.
The Evacuator Synergy Category one Alert System has the flexibility to be utilised in a variety environments and is
suitable for a variety applications. However, It is the responsibility of the user/s to determine the application and
suitability of the products/s before use. Because we have no control over the systems use, installation or application,
FMC Fire, Evacuator Alarms its agents, distributors or employees accept no liability for loss or damages to property or
persons that may have been incurred by the use of this product.
We would therefore insist that a full risk assessment of the site and of the Synergy systems intended use is carried out
before installation of the system.
If you are not completely convinced or satisfied that this product will meet your safety or alert requirements then the
Synergy Wireless System should not be used and must be returned to your place of purchase immediately in its original
packaging.
E&OE.
Evacuator 3 Month Limited Warranty
This warranty is limited to the original purchaser and is not transferable. REPAIR OR REPLACEMENT
AS PROVIDED UNDER THIS WARRANTY IS THE EXCLUSIVE REMEDY OF THE PURCHASER.
This warranty covers only these products purchased from an authorized Evacuator dealer. Third
party transactions are not covered by this warranty. Proof of purchase is required for warranty
claims. Further, Evacuator alarms reserves the right to change or modify this warranty without
notice.
Table of contents
Other Evacuator Fire Alarm manuals