F&F PCS-517.2 User manual

PURPOSE
The timing relay PCS-517 is used to temporarily control of systems in
industrial and home automation. With the powerful features of work,
one-and two-time contained in the memory of the processor, allows
for the elimination of complex and costly control systems based on a
compilation of many channels in normal time. Unlike potentiometers
relays allow very precise setting time of enclose, for example, 3h .-
47min - 19sec.
BUTTON FUNCTIONS
PROG:
- pass to PROGRAMMING mode (hold >3sec).
- out from PROGRAMMING mode
OK:
- entering of settings and pass to next position of settings
- preview of chosen function during of realization it
+ :
- change statue of setting by +1 in chosen PROGRAMMING position
(holding a button cause continuous change by +1 in loop)
- :
-change statue of setting by - 1 in chosen PROGRAMMING position
(holding a button cause continuous change by - 1 in loop)
RESTART:
-"reset" of processor - necessary in the event of suspension of
work functions of the relay. Do not delete the settings of function and
times
+ and - ("hard" reset):
-delete (reset) of all times of all work finctions from memory (press
>3sec two button together). Timer automaticly set P00 function
(Inactivity statue)
DESCRIPTION OF DISPLAY AND CONTROL PANEL
time/work function
report of control
signal statue
START
RESET
PROG OK
+
-
report of
PROGRAMMING function
reprt of time t1
reprt of time t2
reprt of joint
statue
FUNCTIONING
The relay implement one of the set work functions accordance
with to desired times. Positions of joint indicator shows joint
status: ON - enclosed (position 1-5); OFF - disconnected (position
1-6). The display shows the currently measured time t1 (ş1
indicator on the display) or the time t2 (ş2 indicator on the
display) from the upper to zero.
Functions 1÷5 are activated by power supply. After completion of
the function, on the display appears inscription END (end).
Next realization of function will start when you turn off and re-
connecting voltage or "reboot" the CPU. For these functions indicator
of status signal START display ON symbol.
Functions 6÷17 are activated by control signal START. After enclosed
power supplay, the relay is ready to implementation of work function.
On the display appears inscription ON.
After giving of the START signal relay launching function. After the
completion of returns to standby mode (waiting for another signal to
START). For these functions giving of the START signal is indicated on
rate by the symbol signal ON. No signal is indicated by the symbol OFF.
Function 18 - is activated by control signalSTART. After enclosed the
power supply relay is in stanby mode to implementation of work
function. On the display appears inscription ON. After gave START
signal relay will start implementation of function. On the display
appears inscription END (end). The relay does not respond to
subsequent signals START. Next implementation of function will start
when you turn off and re-connecting voltage or "reboot" the CPU. For
this function giving a signal START is indicated by ON symbol on the
rate of control signal. No signal is indicated by the symbol OFF.
- To turn off the power during the performance of the work functions
cause to stop the relay. Joint will remain in a position to disconnect
(pos.1-6). Re-enclose the power will start function from the
beginning.
- Pressing the RESTART button during the implementation of the work
function cause start the functions from the beginning.
ATTENTION!
DESCRIPTION OF WORK FUNCTIONS
inactivity statue
Un
t
5 9 0 8 3 1 2 5 9 1 6 2 7
F&F Filipowski sp. j.
Konstantynowska 79/81 95-200 Pabianice
tel/fax +48 42 2152383; 2270971 POLAND
http:/www.fif.com.pl e-mail: fif@fif.com.pl
TIMING RELAY
18 functions
Do not dispose of this device in the trash along with other waste! According
to the Law on Waste, electro coming from households free of charge and can
give any amount to up to that end point of collection, as well as to store the
occasion of the purchase of new equipment (in accordance with the principle
of old-for-new, regardless of brand). Electro thrown in the trash or abandoned
in nature, pose a threat to the environment and human health.
PCS-517.2
WARRANTY. The F&F products are
covered by the 24 months warranty from
date of purchase. Effective only with
proof of purchase. Contact your dealer or
directly from us. For more information on
the procedures for filing complaints on
www.fif.com.pl/reklamacje
After give the power supply the joint stay in 1-6 position and start count
of set of lagged time. After counted time t, the joint is reconnect in the
position 1-5 (enclose). The next implementation of work mode is
possible after disconnected a the power supply and its re-enclosed.

After give the power supply the joint stay in 1-6 position and start count
of set of lagged time. After counted time t, the joint is reconnect in the
position 1-5 (enclose). The next implementation of work mode is
possible after disconnected a the power supply and its re-enclosed.
The work mode of delayed enclose is implemented out periodically
accompany with set times: t1 breaks and working t2 (enclose).
Un
t
Un
t1 t2 t2
t1
Un
t1 t2 t2
t1
The work mode of delayed exclude is implemented out periodically
accompany with set times: t1 (enclose) and break t2.
Un
t1 t2
After give the power supply the joint stay in 1-6 position and start count
of set of delay time. After counted time t, the joint is reconnect in the
position 1-5 (enclose) for time t2. The next implementation of work
mode is possible after disconnected a the power supply and its re-
enclosed.
After gave the START signal, joint is re-connected in 1-5 position
(enclose). After disappearance of the signal START joint is confirmed by
the set time t. Return of START signal During of count of t time ,break of
count it and joint is enclosed (pos. 1-5).
Renewed fading of START signal start count of t time and maintain the
joint.
Un
t
START
<t t
Un
t
START
t
After gave the START signal, joint is re-connected in 1-5 position
(enclose). After disappearance of the signal START joint is confirmed by
the set time t. During of count of t time ,relay does not respond to
subsequent START signal pulses.
Un
t
START
The enclose of joint (pos. 1-5) at time t, during the count from the value
set to "zero" only when the START signal. Failure of the signal START
pauses the countdown. After the re-emergence of a START signal is the
continuation of the count of the remaining time t. Failure power
supply "resets" the remaining time t. When you receive a power supply
and signal START is the re-count from the value of T set.
Un
tA
START
tBtX
tA+tB+...+tX=t
Enclose of joint(pos. 1-5) at time t with falling slope of signal START.
During countdown of t time, relay does not respond to next pulse of
START signal.
Un
t
START
The delay enclosing of joint (pos. 1-5) at time t growing slope signal
START. During at countdown of t time relay does not respond to
subsequent START signal pulses. After the disappearance and re-
emergence of a START signal is disconnected of joint (pos. 1-6) in time t.
Liberation of delay time t1 (pos.1-6) growing slope of signal START.
Liberation of enclose time t2 (pos.1-5) is always after the
disappearance of the STARTsignal, but no earlier than the time t1.
Un
t1
START
t2 t1 t2
Un
t
START
t
<t
Enclose of joint (pos. 1-5) at time t with falling slope of signal START.
Return of signal START and disappearance it during countdown time t
trigger count time t from begining
Un
t
START
t
<t
Enclose of joint (pos. 1-5) at time t with growing slope of signal START.
Re-enclose of signal START during countdown time t cause stop and
disconnect the joint (pos. 1-6).
Un
t
START
<t t
Enclose of joint (pos. 1-5) at time t with growing slope of signal START.
Return of signal START during countdown time t trigger coun time from
begining.
Un
t1
START
t2
Enclose of joint (pos.1-5) at time t1 with growing slope of START signal
and re-enclose it at time t2 with falling slope of START signal.

Enclose of joint (pos.1-5) at time t1 with growing slope of START signal.
During of countdown time t the relay does not respond to next pulses
of START signal.
Delay enclose of joint (pos.1-5) after time t triggered by growing slope
of START signal. Next signaf START disconnect the joint (pos. 1-6) for
time t. Return of START signal during countdown time t trigger count
time t from begining.
Un
t
START
<t t
Delay enclose of joint (pos.1-5) after time t triggered by growing
slope of signal START. During countdown of time t the relay do not
respond to next pulses of signal START. Joint will disconnect
(pos. 1-6) with decay of power supply. Re-implementation of work
mode of relay is possible after disconected the power supply and re-
enclose it.
Un
t
START
PROGRAMMING
1. Connect the power supply.
ATTENTION!
Relay automaticly pass to inactivity mode (function P00). If in memory
are stored earlier settings than relay pass to implementation of the
last set function.
2. Press button PROG >3sec.
Relay pass to chose work function mode.
By buttons +/- set number of hundredth part of a second (setting
period 25/100). Enter by OK.
4. Relay show section of seconds..
By buttons +/- set work function:.
- By button PROG out from chose work function mode.
- By button OK w pass to set time for function mode.
ş1 on display)
3. Relay show section of hundredth part of a second.
Relay pass to set mode of time t1 t1 (reprt .
By buttons +/- set number of seconds. Entrer OK.
5. Relay show section of minutes.
By buttons + /- set number of minutes. Enter by OK.
6. Relay show section of hours.Przekaźnik pokaże sekcję godzin (
sections are shifted to the right, the hundredths section is hidden, and
in its place will be moved second section, Section minutes will be
moved in place of the second. Section hour is on the left side of the
display).
All
By buttons+/- set number of hours. Enter by OK.
- for two-times functions relay pass to set time t2 mode ş2 on
display
- for one-times functions relay passs to chose work function mode. By
button
(report
). Follow as programming time t1.
PROG enter chosen function (out from PROGRAMMING
function).
Relay automaticly pass to implementation of this function
ASSEMBLY
1. Take OFF the power.
2. Put on the relay on the rail in the switchgearbox.
3. Power connect to joint 3-4 (any polarity)
4. Power of controlled receiver connect serial to joint 1-5.
5. Set work program and times of enclose the receiver.
TECHNICAL DATA
supply 24 V AC/DC
current load
activation lag delay function
working temperature -25÷50°C
connection screw terminals
dimensions 2 modules (35 mm)
÷264
<16A
joints separate1P
current of control pulse <1mA
range os time settings 0,25sek÷99h59min59sek75/100
<50msec
power consumption 1,5W
2,5mm²
fixing on rail TH-35
Un
t
START
t
ATTENTION!
In the case of erroneous data, for example, provide one of the times
as 0:
- Press OK. cause to display the error message Err (ERROR) and then
move to mode of set time of chosen work functions.
- Pressing PROG will display an error message Err (ERROR), and
automatically pass into the inactivity mode (function P00).
IN/OUT DESCRIPTION
B091208/D130823
3-4 power supply (any polarity)
1central joint COM
5 contact joint NO [ON]
6 open joint NC [OFF]
8 input control pulse
AC/DC
34
1
5
8START
6
L/N/+
Table of contents
Other F&F Relay manuals
Popular Relay manuals by other brands

Rockwell Automation
Rockwell Automation Allen-Bradley Guardmaster Dual-Input Safety... Application Technique

SEA
SEA GSM-R5-T user manual

Viking
Viking TDR-1 product manual

Marina
Marina Model GFR480-1 Installation and operation manual

Novatek-electro
Novatek-electro PH-260t operating manual

GE
GE MM200 quick start guide