Fema M Series User manual

Series M . M40-T
Meter for temperature signals
Panel meter for temperature signals. Accepts signals from Pt100 / RTD (2 and 3 wires) and thermo-
couples J, K, T, E, S, R, N, C, L and X. Reading congurable in ºC or ºF. Manual oset congurable. Con-
gurable cold juncon compensaon. Sensor break detecon. Standard 96 x 48 mm size (1/8 DIN).
Reading with 4 digit display with oponal ‘º’ symbol on display. Fast access to alarm setpoints, ‘on
power up’ funcon, congurable reading brightness. Universal AC and DC power. Up to 3 oponal
modules for output and control (relrelays, transistor, control SSR, analog outputs, Modbus RTU com-
municaons, RS-485 ASCII, RS-232, ...) www.fema.es
User’s Manual
ELECTRONICS FOR INDUSTRIAL AUTOMATION
PANEL METERS . SIGNAL CONVERTERS . LARGE DISPLAYS
PANEL METERS
2185r08

FEMA ELECTRÓNICA . Series M . M40-T
2
1. Panel meter M40-T
Panel meter 96 x 48 mm (1/8 DIN) for temperature signals
Panel meter 96 x 48 mm (1/8 DIN) for temperature signals from Pt100
/ RTD (2 and 3 wires) and thermocouples J, K, T, E, S, R, N, C, L and
X. Congurable reading in º Celsius or º Fahrenheit. Thermocouple
cold juncon compensaon congurable (see secon 1.11.2). Con-
gurable oset for display reading (see secon 1.11.2). Selectable
behavior in case of sensor break (see secon 1.11.2). Reading with
4 digits and negave sign, with oponal symbol ‘º’ on display (see
secon 1.11.2).
Opons for output and control with 1, 2 and 3 relays, transistor out-
puts, controls for SSR relays, isolated analog outputs, communica-
ons in Modbus RTU, RS-485 ASCII and RS-232. Special opons with
4 and 6 relay outputs.
Independent alarms congurable as maximum or minimum, with 1
or 2 setpoints per alarm, hysteresis, independent acvaon and de-
acvaon delays and control for inverted relay.
Front protecon IP65. Connecons by plug-in screw terminals. For
industrial applicaons.
• ‘Fast access’ menu to selected funcons, accessible with key UP (5)
(see secon 1.11.5)
• ‘On power up’ for system protecon on rst ‘cold’ start-up (see
secon 1.11.7)
Display lters, memory for maximum and minimum reading, pass-
word protecon, 5 brightness levels.
1.1 How to order
Index
1. Panel meter M40-T. . . . . . . . . . . . . . . . . . . . . . . 2
1.1 How to order . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Front view . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Rear view . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Power connecons . . . . . . . . . . . . . . . . . . . . . 3
1.5 Signal connecons - Pt100 / RTD . . . . . . . . . . . . . 3
1.6 Signal connecons - Thermocouple. . . . . . . . . . . . 3
1.7 Mechanical dimensions (mm) . . . . . . . . . . . . . . . 3
1.8 Technical specicaons . . . . . . . . . . . . . . . . . . 4
1.9 Messages and errors . . . . . . . . . . . . . . . . . . . . 5
1.10 How to operate the menus. . . . . . . . . . . . . . . . 6
1.11 Conguraon menu. . . . . . . . . . . . . . . . . . . . 7
1.11.1 Inial set-up . . . . . . . . . . . . . . . . . . . . . . 7
1.11.2 Temperature conguraon . . . . . . . . . . . . . . 7
1.11.3 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.11.4 Display lters. . . . . . . . . . . . . . . . . . . . . . 9
1.11.5 Fast access . . . . . . . . . . . . . . . . . . . . . . . 9
1.11.6 Super fast access . . . . . . . . . . . . . . . . . . . 9
1.11.7 Menu ‘On Power Up’ . . . . . . . . . . . . . . . . . 10
1.11.8 Menu ‘Key LE’ . . . . . . . . . . . . . . . . . . . . .10
1.11.9 Funcon ‘Password’ . . . . . . . . . . . . . . . . . 10
1.11.10 Factory reset . . . . . . . . . . . . . . . . . . . . .10
1.11.11 Firmware version. . . . . . . . . . . . . . . . . . . 11
1.11.12 Brightness . . . . . . . . . . . . . . . . . . . . . . 11
1.11.13 Access to oponal modules . . . . . . . . . . . . . 11
1.12 Full conguraon menu . . . . . . . . . . . . . . . . . 12
1.13 To access the instrument . . . . . . . . . . . . . . . . .14
1.14 Modular system . . . . . . . . . . . . . . . . . . . . . .14
1.15 Precauons on installaon . . . . . . . . . . . . . . . .15
1.16 Factory conguraon . . . . . . . . . . . . . . . . . . .15
1.17 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.18 CE declaraon of conformity . . . . . . . . . . . . . . . 15
2. Output and control modules . . . . . . . . . . . . . . . . . 16
2.1 Module R1. . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.2 Module T1. . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.3 Module SSR . . . . . . . . . . . . . . . . . . . . . . . . .17
2.4 Module AO . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.6 Module RTU. . . . . . . . . . . . . . . . . . . . . . . . . 18
2.5 Module S4. . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.7 Module S2. . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.8 Modules R2, R4, R6. . . . . . . . . . . . . . . . . . . . . 19
3. Other opons . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.1 Opon NBT . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2 Opon G. . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . .21
4.1 THM benchtop housing . . . . . . . . . . . . . . . . . . 21
4.2 Adapter DRA-M . . . . . . . . . . . . . . . . . . . . . . . 21
4.3 Adapter KA96 . . . . . . . . . . . . . . . . . . . . . . . .21
4.4 WME housing . . . . . . . . . . . . . . . . . . . . . . . .21
4.5 Protector KIP . . . . . . . . . . . . . . . . . . . . . . . . 21
M40 T
Model Power
-
Opon 1 Others
H- - -
Opon 2
-
Opon 3
-
-R1 (1 relay)
-AO (analog output)
-RTU (Modbus RTU)
-S4 (RS-485)
-S2 (RS-232)
-T1 (1 transistor)
-SSR (1 control SSR)
- (empty)
-H (85-265 Vac/dc)
-L (11/60 Vdc,
24 Vac, 48 Vac)
-NBT (no buons)
-G (green led)

FEMA ELECTRÓNICA . Series M . M40-T
3
1.2 Front view
1.3 Rear view
Earth connecon - Although a
terminal is provided for earth
connecon, this connecon is
oponal. The instrument does
not need earth connecon for
correct operaon nor for com-
pliance with the security regu-
laons. ~
~+
-
8 9 0
Fuse - To comply with security regulaon 61010-1, add to the power
line a protecon fuse acng as disconnecon element, easily acces-
sible to the operator and idened as a protecon device.
Power ‘H’ fuse 250 mA me lag
Power ‘L’ fuse 400 mA me lag
1.4 Power connecons
1.5 Signal connecons - Pt100 / RTD
Buon ‘UP’
Logo
Alarms
Units
Buon ‘SQ’
Buon ‘LE’
‘Conguraon menu’
(see secon 1.11)
‘Fast access‘
(see secon 1.11.5)
Signal
(see secon
1.5 and 1.6)
Opon 1 Opon 2Opon 3
Power
(see secon 1.4)
Detail of the plug-in screw terminals provided with
the instrument. The instrument is provided with all
terminals needed, both male and female.
Symbol ‘º’ congurable
(see secon 1.11.2)
For Pt100 / RTD with 2 wires
For Pt100 / RTD with 3 wires
Pt100 2 wires
123
123
Pt100 3 wires
123
+
-
1.6 Signal connecons - Thermocouple
1.7 Mechanical dimensions (mm)
123 890
44
92
Panel
cut-out
16 8
75
96
48

FEMA ELECTRÓNICA . Series M . M40-T
4
Digits
number of digits 4
led 7 segments led
color red or green
digit height 14 mm
Reading
overrange 9999 with ash reading
underrange -9999 with ash reading
symbol ‘º’ on display congurable (see secon 1.11.2)
in case of sensor break
reading ‘to_high’ or ‘to_low’ (see secon 1.11.2)
Signal ranges (see Table 1)
Accuracy at 25 ºC (see Table 1)
Thermal dri (see Table 1)
Signals accepted Pt100 / RTD (see Table 1)
thermocouples (see Table 1)
temperature scale ITS90
units ºC or ºF, congurable
Pt100 / RTD 2 or 3 wires, congurable
resoluon 1º or 0.1º, congurable
ranges (see Table 1)
max. error at 25ºC (see Table 1)
oset dri (see Table 1)
span dri* (see Table 1)
(*span dri includes oset dri)
cable compensaon automac up to 14 Ohms
readings 4 / second
Thermocouples J, K, T, E, S, R, N, C, L and X
(thermocouple X is 10 uV/ºC linear signal)
resoluon 1º
ranges (see Table 1)
max. error at 25 ºC (see Table 1)
oset dri (see Table 1)
span dri* (see Table 1)
(*span dri includes oset dri)
thermocouple CJC automac (see secon 1.11.2)
cold juncon accuracy <1.0 ºC
cold juncon dri <0.04 º/ºC
readings 3 / second
Power
power ‘H’ 85 a 265 Vac/dc
power ‘L’ 11 a 60 Vdc y 24/48 Vac
isolaon* 2500 Ve with power ‘H’
1500 Ve with power ‘L’
*all units tested during 60 seconds
consumpon <1.5 W only meter
<4.0 W meter with opons
Conguraon 3 buons front keypad
(and rear jumper)
Front protecon IP65
Output and control opons relays, analog outputs, serial communi-
caons, ... (see secon 2)
Mechanical
1.8 Technical specicaons
Sensor Range (en ºC) Error max.
at 25 ºC
Range (en ºF) Oset dri Span dri*
*includes oset dri
Pt100 / RTD 800 / -200 ºC <0.2 ºC 1562 / -328 ºF 0.05 º/ºC 0.10 º/ºC
Thermocouple J 1200 / -200 ºC <2 ºC 2192 / -328 ºF 0.05 º/ºC 0.20 º/ºC
Thermocouple K 1372 / -200 ºC <2 ºC 2372 / -328 ºF 0.05 º/ºC 0.20 º/ºC
Thermocouple T 400 / -200 ºC <2 ºC 752 / -328 ºF 0.02 º/ºC 0.02 º/ºC
Thermocouple E 1000 / -200 ºC <2 ºC 1832 / -328 ºF 0.05 º/ºC 0.20 º/ºC
Thermocouple S 1768 / -50 ºC <4 ºC 2282 / -58 ºF 0.20 º/ºC 0.20 º/ºC
Thermocouple R 1600 / -50 ºC <4 ºC 2912 / -58 ºF 0.20 º/ºC 0.20 º/ºC
Thermocouple N 1300 / -200 ºC <2 ºC 2372 / -328 ºF 0.05 º/ºC 0.20 º/ºC
Thermocouple C 2320 / 0 ºC <2 ºC 4192 / 32 ºF 0.02 º/ºC 0.02 º/ºC
Thermocouple L 900 / -200 ºC <2 ºC 1652 / -328 ºF 0.05 º/ºC 0.20 º/ºC
Thermocouple X 4000 / -200 ºC <2 ºC 7232 / -328 ºF 0.02 º/ºC 0.02 º/ºC
Table 1 - Technical specicaons for each sensor

FEMA ELECTRÓNICA . Series M . M40-T
5
Funcons included Secon
‘Fast access’ yes 1.11.5
Symbol ‘º’ on display congurable 1.11.2
Manual oset congurable 1.11.2
Thermocouple cold juncon
congurable 1.11.2
Sensor break detecon congurable 1.11.2
Display lters steps 1.11.4
Memory max. and min. readings 1.11.4
Password conguraon block 1.11.9
Alarms double setpoints
acvaon delays
deacvaon delays
hysteresis
inverted relays
locked alarms
1.11.3
Display brightness 5 levels 1.11.12
‘On Power Up’ yes 1.11.7
Table 2 - Funcons included
mounng panel
connecons plug-in screw terminal
housing material ABS, polycarbonate (V0)
weight <150 grams
front size 96 x 48 mm (1/8 DIN)
panel cut-out 92 x 44 mm
depth from panel 91 mm (including terminals)
Temperature
operaon from 0 to +50 ºC
storage from -20 to +70 ºC
warm-up me 15 minutes
1.8 Technical specicaons (cont.)
Messages and errors
‘h.oVr’ Hardware overrange (‘h.ovr’). Input signal is higher than
the maximum signal the instrument can detect (80 mV)
‘h.udr’ Hardware underrange (‘h.udr’). Input signal is lower than
the minimum signal the instrument can detect (-30 mV).
‘d.udr’
‘d.oVr’
display underrange (‘d.udr’) / overrange (‘d.ovr’). The in-
strument already displays the minimum / maximum value
possible (-9999 / 9999).
‘brk’ instrument will display ‘brk’ message in the following
cases
• when measuring Pt100 / RTD, the resistance measured
is higher than 390 Ohms (higher than 850 ºC)
• when measuring Pt100 / RTD, the third wire (sense
wire) presents an impedance higher than 15 Ohms
• when measuring thermocouples, the thermocouple cir-
cuit is open circuit
‘Err.1’ incorrect password.
‘Err.2’ at ‘oPt.X’ menu entry. Installed module is not recognized.
Table 3 - Messages and error codes
The error messages are shown on display in ash mode.
1.9 Messages and errors

FEMA ELECTRÓNICA . Series M . M40-T
6
The instrument has two menus accessible to the user :
‘Conguraon menu’ (key SQ) (<)
‘Fast access’ menu (key UP) (5)
Conguraon menu
The ‘conguraon menu’ modies the conguraon parameters to
adapt the instrument to the applicaon needs. To access the ‘con-
guraon menu’ press for 1 second the SQ (<) key. This access can
be blocked by acvang the ‘Password’ (‘PASS’) funcon. While
operang the ‘conguraon menu’, the alarm status is ‘hold’ to the
status they had before accessing the menu, and the output and con-
trol modules remain in ‘error’ state. When leaving the ‘conguraon
menu’, the instrument applies a system reset, followed by a brief
disconnecon of the alarms and the output and control modules.
Funconality is then recovered.
For a detailed explanaon on the ‘conguraon menu’ see secon
1.11, and for a full view of the ‘conguraon menu’ structure see
secon 1.12.
‘Fast access’ menu
The ‘fast access’ menu is an operator congurable menu, providing
fast and direct access to the most usual funcons of the instrument
with a single key pad stroke. Press key UP (5) to access this menu.
See secon 1.11.5 for a list of funcons eligible for ‘fast access’ in
this instrument. The ‘Password’ (‘PASS’) funcon does not block ac-
cess to this menu. Accessing and modifying parameters in the ‘fast
access’ menu does not interfere with the normal funconality of the
instrument, and it does not generate any system reset when validat-
ing the changes.
Front key pad descripon
Key SQ (<) - press the SQ (<) key for 1 second to access the ‘con-
guraon menu’. Inside the menu, the SQ (<) key funcons as a
‘ENTER’ key. It selects and accesses the menu opon currently dis-
played. At menus with numerical value entries, it validates the num-
ber displayed.
Key UP (5) - the UP (5) key gives access to the ‘fast access’ menu.
Inside the menus, it moves vercally through the dierent menu op-
ons. At menus with numerical value entries, it modies the digit
selected by increasing its value to 0, 1, 2, 3, 4, 5, 6, 7, 8, 9.
Key LE (3) - inside the menus, the LE (3) key funcons as the ‘ES-
CAPE’ key. It leaves the selected menu, and eventually, will leave the
whole menu. When leaving the ‘conguraon menu’ with the LE (3)
key, the changed parameters are acvated. At menus with numeri-
cal value entries, the LE (3) key allows to select the acve digit. To
modify the value of the selected digit use the UP (5) key.
Menu ‘rollback’
Aer 30 seconds without interacon from the operator, the instru-
ment will rollback and leave the ‘conguraon menu’ or the ‘fast ac-
cess’ menu. All changes will be discarded.
1.10 How to operate the menus
Input
Example of operaon inside the
‘conguraon menu’.
1. The SQ (<) key enters into the
‘conguraon menu’.
2. The SQ (<) key enters into the
‘InP’ opon menu.
3. The UP (5) key moves through
the menu opons.
4. The SQ (<) key selects the
desired range and returns to the
‘InP’ menu.
5. The LE (3) key leaves the ac-
tual menu level and moves to the
previous menu level.
6. The LE (3) key leaves the ‘con-
guraon menu’. Changes are ap-
plied and saved at this moment.
(2)
(3)
(3)
(3)
(3)
(3)
(4)
(4)
(4)
(4)
(5)
(5)
(5)
(5)
(3)
(3)
(6)
(6)
(1)

FEMA ELECTRÓNICA . Series M . M40-T
7
1.11 Conguraon menu
To congure the inial set up of the instrument, select the type of
sensor to be connected to the instrument.
Access the ‘Input’ (‘InP’) menu to select the type of sensor. Opons
available are Pt100 / RTD with 2 and 3 wires, and thermocouples J, K,
T, E, S, R, N, C, L and X. Thermocouple X is a linear signal os 10 uV/ºC.
1.11.1 Inial set-up
The ‘Temperature conguraon’ (‘cnF.t’) menu allows to congure
several funcons associated to the measure and working with tem-
perature signals.
• at the ‘Degree’ (‘dEG’) menu, select ‘ºc’ to measure in Celsius
degrees, or select ‘ºF’ to measure in Fahrenheit degrees.
• at the ‘Resoluon Pt100’ (‘P.rES’) menu, select the reading res-
oluon for the Pt100 / RTD. Select ‘1º’ for 1º resoluon or select
‘0.1º’ for 0.1º resoluon.
• at the ‘Reading oset’ (‘oFFS’) menu, congure a number of
counts to be added to the reading. Applies both to the measure in
Pt100 / RTD and thermocouples. This oset allows to correct read-
ing errors associated to dierent types of probes, which can not
be corrected by other means. Oset value allows for ‘±100’ display
counts.
• the ‘Thermocouple CJC’ (‘t.cJc’) menu allows to acve or deac-
vate the automac compensaon of the thermocouple cold junc-
on. When working with a real thermocouple, compensaon must
be on. In case of using an electronic thermocouple simulator, it may
be needed to deacvate the automac cold juncon compensaon.
• at the ‘on break’ (‘on.bk’) menu select the behavior of the instru-
ment in case of sensor break detecon. Select ‘to_h’ to set reading
to overrange, or select ‘to_L’ to set reading to underrange.
• at the ‘Alpha’ (‘ALPh’) menu congure the alpha for the
Pt100 / RTD. The standard values in industry are ‘385’ and ‘390’.
• the ‘Degree symbol’ (‘ºLEd’) menu allows to light the symbol ‘º’
on display, to the right of the temperature value.
1.11.2 Temperature conguraon
Press ‘SQ’ (<) for 1 second to access the ‘conguraon menu’.
For a descripon on how to operate inside the menus see secon
1.10. For a full vision of the ‘conguraon menu’ structure see
secon 1.12.
Input
Temperature
conguraon
Degrees
Degrees Celsius
Degrees Fahrenheit
Resoluon Pt100
1º resoluon
0.1º resoluon
Reading oset
Thermocouple
CJC
‘On break’
Reading to maximum
Reading to minimum
Alpha
Alpha 385
Alpha 390
Degree symbol
Symbol º on display
Pt100 / RTD 2 wires
Pt100 / RTD 3 wires
Thermocouple J
Thermocouple K
Thermocouple T
Thermocouple E
Thermocouple S
Thermocouple R
Thermocouple N
Thermocouple C
Thermocouple L
Thermocouple X

FEMA ELECTRÓNICA . Series M . M40-T
8
Alarm 1
Setpoint
Hysteresis
Setpoint 2
Acve
Alarm type
Alarms
Acvaon delay
Deacvaon delay
1.11 Conguraon menu (cont.)
The ‘Alarms’ (‘ALr’) menu congures the independent acvaon of
up to 3 relay outputs (or transistor or SSR modules), installed with
the R1 oponal modules (or T1 or SSR) (see secon 2.1). For out-
puts up to 4 and 6 relays, see special modules R2, R4 and R6 at sec-
on 2.6. The alarm states are indicated in the front display with leds
marked as ‘1’, ‘2’ and ‘3’.
To congure an alarm, enter into the alarm menu (‘ALr1’, ‘ALr2’ or
‘ALr3’) and congure the following parameters :
• select ‘Acve’ (‘Act’) to ‘on’
• at ‘Alarm type’ (‘TypE’) select the alarm acng as a maximum
type alarm (‘MAX’) or a minimum type alarm (‘MIn’). The maxi-
mum type alarm (or minimum type alarm) acvates when the dis-
play value is higher (or lower) than the setpoint value.
• at ‘Setpoint’ (‘SEt’) enter the value for the alarm acvaon point.
This parameter is eligible for conguraon through the ‘Fast access’
menu (see secon 1.11.5).
• congure the hysteresis value at ‘Hysteresis’ (‘hySt’). The hys-
teresis applies to the deacvaon process of the alarm. The alarm
deacvates when the reading has passed the setpoint value plus
the hysteresis value. Hysteresis helps to avoid repeve switching
of the alarm relays, due to uctuang input signals around the set-
point.
• at ‘Acvaon delay’ (‘dEL.0’) congure the delay to apply before
alarm acvaon. The acvaon delay starts counng when the set-
point value is passed. Value from 0.0 to 99.9 seconds.
• at ‘Deacvaon delay’ (‘dEL.1’) congure the delay to apply
before alarm deacvaon. The deacvaon delay starts counng
when the setpoint value plus the hysteresis value, is passed. Value
from 0.0 to 99.9 seconds.
• to work with ‘windowed alarms’ (see graphical example below)
acvate ‘Setpoint 2’ (‘SEt2’) to ‘on’ and then congure the desired
second setpoint value. Second setpoint must always be higher in
value than the rst setpoint.
• the ‘Relay inverted’ (‘r.Inv’) parameter inverts the normal relay
connecons. When set to ‘on’ the relay will be acve when alarm is
inacve. For security applicaons where an inacve relay controls
the shutdown of the system.
• the ‘Locked alarm’ (‘A.Lck’) parameter disables the automac
deacvaon of the alarm. Alarm deacvaon must be performed
manually, by pressing the ‘LE’ front buon (see secon 1.11.8)
1.11.3 Alarms
Reading
Time
setpoint
hysteresis
Alarm as maximum,
no hysteresis, no delays
on
o Time
acvaon
delay
on
o
deacvaon
delay
Time
Alarm as maximum,
with hysteresis and delays
on
o Time
Alarm as minimum,
no hysteresis, no delays
Reading
Time
Setpoint 2
Setpoint 1
Alarm as minimum,
with double setpoint,
no hysteresis, no delays
on
o Time
Relay inverted
Locked alarm

FEMA ELECTRÓNICA . Series M . M40-T
9
1.11 Conguraon menu (cont.)
The instrument provides several funcons associated to the reading
of the display values
• the ‘Steps’ (‘StEP’) funcon allows to dene minimum reading
steps, which will be done in steps of 1, 2, 5, 10, 20 or 50 counts.
Example - selecng a step of 20 congures the reading to change in
steps of 20 counts (‘1420’, ‘1440’, ‘1460’, ...).
• the ‘Memory of maximum’ (‘MAX’) funcon displays the maximum
reading value stored in memory. It also provides a way to reset the
value. This parameter is eligible for conguraon through the ‘Fast
access’ menu (see secon 1.11.5).
• the ‘Memory of minimum’ (‘MAX’) funcon displays the minimum
reading value stored in memory. It also provides a way to reset the
value. This parameter is eligible for conguraon through the ‘Fast
access’ menu (see secon 1.11.5).
1.11.4 Display lters
Steps
Display
Memory of
maximum
Memory of
minimum
Tools Key UP
(‘Fast access’)
Memory of
maximum
Memory of
minimum
Setpoint 1
Setpoint 2
Setpoint 3
The ‘UP’ (5) key at the front of the instrument gives access to a list
of funcons congurable by the operator. See secon 1.10 for an ex-
planaon on how to operate the ‘fast access’ menu.
The ‘Key UP (Fast access)’ (‘K.uP’) menu allows to select which func-
ons will be accessible through the ‘fast access’ menu. Select ‘on’ to
acvate each funcon.
• the ‘Setpoint 1’ (‘ALr1’) funcon allows to visualize and modify the
alarm 1 setpoint through the ‘fast access’ menu.
• the ‘Setpoint 2’ (‘ALr2’) funcon allows to visualize and modify the
alarm 2 setpoint through the ‘fast access’ menu.
• the ‘Setpoint 3’ (‘ALr3’) funcon allows to visualize and modify the
alarm 3 setpoint through the ‘fast access’ menu.
• the ‘Memory of maximum’ (‘MAX’) or ‘Memory of minimum’
(‘MIn’) funcons allow to visualize the maximum or minimum read-
ing value stored in memory. To reset this value, visualize the memory
value at the ‘fast access’ menu with key UP (5) and when message
‘rSt’ is displayed, press (<) to reset.
1.11.5 Fast access
If only a single funcon is selected for the ‘fast access’ menu, press-
ing the the ‘UP’ (5) key will shortly display the funcon name and
then automacally jump to the funcon value.
1.11.6 Super fast access

FEMA ELECTRÓNICA . Series M . M40-T
10
1.10 Conguraon menu (cont.)
The ‘On Power Up’ (‘on.Pu’) menu congures funcons to apply at
start-up. It applies only to instrument restart aer power loss. It does
not apply to instrument restart due to change in conguraon.
• parameter ‘Delay’ (‘dLAy’) assigns a waing me in seconds. The
instrument waits the congured me before starng normal func-
on. During this waing me, the display shows all decimal points
on in ash mode, all alarms are in the state dened at the ‘Alarm 1’,
‘Alarm 2’ and ‘Alarm 3’ entries, there is no signal acquision and
there is no communicaons or control being performed. Aer the
congured me is over, the instrument starts in normal funcon. De-
lay value between 0 and 200 seconds.
Applicaon - the start-up process for an automaon system implies
that dierent parts of the system (engines, actuators, controllers, ...)
have dierent start-up mes. The ‘Delay’ funcon gives me to the
instrument to wait unl the slowest part of the system is fully func-
onal before execung acons on the system (signal reading, relay
acvaon, ...)
• the ‘Alarm 1’ (‘ALr1’), ‘Alarm 2’ (‘ALr2’) and ‘Alarm 3’ (‘ALr3’) pa-
rameters allow to dene the status of the alarms while the instru-
ment is starng from a power loss. Select ‘on’ for acve alarm, select
‘oFF’ for deacvated alarm.
1.11.7 Menu ‘On Power Up’
At the ‘Password’ (‘PASS’) menu select a 4 digit code to block access
to the ‘conguraon menu’. Instrument conguraon will not be ac-
cessible to non authorized personnel. To acvate the ‘Password’ se-
lect ‘on’ and introduce the code.
The code will be requested when trying to access the ‘conguraon
menu’ (key ‘SQ’ (<)). The ‘fast access’ menu is not password pro-
tected.
At the ‘Factory reset’ (‘FAct’) menu, select ‘yes’ to load the default
factory conguraon for the instrument (see secon 1.16).
The ‘LE’ (3) key at the front of the instrument can be congured to
acvate several funcons. Only one funcon can be assigned to the
‘LE’ (3) key
• the ‘No funcon’ (‘nonE’) value assigns no funcon.
• the ‘Alarm unlock’ (‘A.Lck’) value assigns the manual unlock of the
alarms funcon, for instruments with the ‘Locked alarms’ (‘A.Lck’)
funcon acvated (see secon 1.11.3)
Password
Factory reset
Key LE
Alarm unlock
No funcon
On Power-Up Delay Seconds
Alarm 1
Alarm 2
Alarm 3
1.11.8 Menu ‘Key LE’
1.11.9 Funcon ‘Password’
1.11.10 Factory reset

FEMA ELECTRÓNICA . Series M . M40-T
11
1.10 Conguraon menu (cont.)
The ‘Version’ (‘VEr’) menu informs of the current rmware version
installed in the module.
At the ‘Brightness’ (‘LIGh’) menu select the light intensity for the
front leds. With this funcon it is possible to adapt the instrument to
the environment light intensity.
1.11.11 Firmware version
Menus ‘OPt.1’, ‘OPt.2’ and ‘OPt.3’ give access to the ‘conguraon
menus’ of the output and control modules installed at slots Opt.1,
Opt.2 and Opt.3.
See secon 2 for a list of output and control modules available for
each slot. The ‘conguraon menu’ of each module is described at
the User’s Manual of each module.
1.11.12 Brightness
1.11.13 Access to oponal modules
Opon 1
Conguraon menu for the module installed at Opt.1
Opon 2
Conguraon menu for the module installed at Opt.2
Opon 3
Conguraon menu for the module installed at Opt.3
Version
Minimum
Brightness
Maximum
Standard

FEMA ELECTRÓNICA . Series M . M40-T
12
1.12 Full conguraon menu
Press ‘SQ’ (<) for 1 second to access the ‘Conguraon
menu’. See secon 1.11 for a descripon of each menu entry.
Steps
Display
Memory of
maximum
Memory of
minimum
Alarms
Alarm 1
Setpoint
Hysteresis
Setpoint 2
Acve
Type of alarm
Acvaon delay
Deacvaon
delay
Menu for Alarm 2
Menu for Alarm 3
Inverted relay
Locked alarm
Pt100 / RTD 2 wires
Pt100 / RTD 3 wires
Thermocouple J
Thermocouple K
Input
Temperature
conguraon
Thermocouple T
Thermocouple E
Thermocouple S
Thermocouple R
Thermocouple N
Thermocouple C
Thermocouple L
Thermocouple X
Degrees
Degrees Celsius
Degrees Fahrenheit
Resoluon Pt100
1º resoluon
0.1º resoluon
Reading oset
Thermocouple
CJC
‘On break’
Reading to maximum
Reading to minimum
Alpha
Alpha 385
Alpha 390
Degree symbol
Symbol ‘º’ on display

FEMA ELECTRÓNICA . Series M . M40-T
13
1.11 Full conguraon menu (cont.)
Opon 1
Conguraon menu for the module installed at Opt.1
Opon 2
Conguraon menu for the module installed at Opt.2
Opon 3
Conguraon menu for the module installed at Opt.3
Minimum
Brightness
Maximum
Standard
Tools Key UP
(fast access)
Memory of
maximum
Memory of
minimum
Setpoint 1
Setpoint 2
Setpoint 3
Password
Firmware version
Factory reset
Key LE
Alarm lock
no funcon
On Power-Up Delay Seconds
Alarm 1
Alarm 2
Alarm 3

FEMA ELECTRÓNICA . Series M . M40-T
14
1.13 To access the instrument
1.14 Modular system
Series M panel meters are designed to create a modular system. This
modular system allows for addion, replacement or substuon of
any of the internal modules conforming the instrument. Below is a
graphic explanaon for the posion of each module.
Risk of electric shock. Removing the front cover will
grant access to the internal circuits. Disconnect the
input signal to prevent electric shock to the operator.
Operation must be performed by qualied personnel
only.
To open the housing, use a at screwdriver to free the xaon clips,
if possible, in the following order : D, C, B and A. Remove the front
cover. Let the inside of the instrument slide out of the housing.
To reinsert the instrument make sure that all modules are correctly
connected to the pins on the display module. Place all the set into
the housing, assuring that the modules correctly t into the internal
guiding slides of the housing. Once introduced, place again the front
cover in front of the housing, placing rst corner ‘X’ and then insert-
ing clips ‘A’, ‘B’, ‘C’ and ‘D’ in this order.
XA
C
BD
Front Filter Display Module Oponal Control Modules
Input Signal Module
Housing
Power Supply Module
Opt.3
Opt.2
Opt.1

FEMA ELECTRÓNICA . Series M . M40-T
15
This instrument has been designed and veried conforming to the 61010-1 CE Security
Regulaon, for industrial applicaons.
Installaon of this instrument must be performed by qualied personnel only. This manual
contains the appropriate informaon for the installaon. Using the instrument in ways not
specied by the manufacturer may lead to a reducon of the specied protecon level.
Disconnect the instrument from power before starng any maintenance and / or instal-
laon acon.
The instrument does not have a general switch and will start operaon as soon as power is
connected. The instrument does not have protecon fuse, the fuse must be added during
installaon.
1.15 Precauons on installaon
Risk of electrical shock. Instrument terminals can be connected
to dangerous voltage.
Instrument protected with double isolaon. No earth connecon
required.
Instrument conforms to CE rules and regulaons.
1.16 Factory conguraon
1.17 Warranty
1.18 CE declaraon of conformity
This instrument is warranted against all manufacturing defects for a
period of 24 MONTHS from the shipment date. This warranty does
not apply in case of misuse, accident or manipulaon by non-autho-
rized personnel. In case of malfuncon get in contact with your local
provider to arrange for repair. Within the warranty period and aer
examinaon by the manufacturer, the unit will be repaired or subs-
tuted when found to be defecve. The scope of this warranty is lim-
ited to the repair cost of the instrument, not being the manufacturer
eligible for responsibility on addional damages or costs.
Sensor Pt100 / RTD 2 wires
Temperature conguraon
Degrees ºC
Pt100 / RTD resoluon 0.1º
Reading oset 0 counts
Thermocouple CJC on
On break to_h
Alpha 385
Symbol ‘º’ oFF
Alarms 1,2 and 3
Acve o (disabled)
Type alarm as maximum
Setpoint 1000
Hysteresis 0 counts
Acvaon delay 0.0 seconds
Deacvaon delay 0.0 seconds
Setpoint 2 o
Inverted relay o
Locked alarms o
Display
Steps o
Maximum memory -9999
Minimum memory 9999
Tools
‘Fast access’ o
‘On power-up’
Delay 0 seconds
Alarm 1 o
Alarm 2 o
Alarm 3 o
Key LE no funcon
Password o
Brightness 3
The instrument is designed to be panel mounted. An appropriate venlaon of the in-
strument must be assured. Do not expose the instrument to excess of humidity. Maintain
clean by using a humid rag and do NOT use abrasive products such as alcohols, solvents,
etc.
General recommendaons for electrical installaons apply, and for proper funconality
we recommend : if possible, install the instrument far from electrical noise or magnec
eld generators such as power relays, electrical motors, speed variators, ... If possible, do
not install along the same conduits power cables (power, motor controllers, electrovalves,
...) together with signal and/or control cables.
Before proceeding to the power connecon, verify that the voltage level available matches
the power levels indicated in the label on the instrument.
In case of re, disconnect the instrument from the power line, re alarm according to local
rules, disconnect the air condioning, aack re with carbonic snow, never with water.
Manufacturer FEMA ELECTRÓNICA, S.A.
Almira 14 - Pol. Ind. Sanga
E08210 - Barberà del Vallès
BARCELONA - SPAIN
www.fema.es - info@fema.es
Products M40-T
The manufacturer declares that the instruments indicated comply with the
direcves and rules indicated below.
Electromagnec compability direcve 2014/30/EU
Low voltage direcve 2014/35/EU
ROHS direcve 2011/65/EU
Security rules EN-61010-1
Instrument Fixed. Permanently connected
Polluon degree 1 and 2 (without condensaon)
Isolaon Double
Electromagnec compability rules EN-61326-1
EM environment
Industrial
Immunity levels
EN-61000-4-2 By contact ±4 KV Criteria B
By air ±8 KV Criteria B
EN-61000-4-3 Criteria A
EN-61000-4-4 On AC power lines : ±2 KV Criteria B
On DC power lines : ±2 KV Criteria B
On signal lines : ±1 KV Criteria B
EN-61000-4-5 Between AC power lines ±1 KV Criteria B
Between AC power lines and earth ±2 KV Criteria B
Between DC power lines ±1 KV Criteria B
Between DC power lines and earth ±2 KV Criteria B
Between signal lines and earth ±1 KV Criteria B
EN-61000-4-6 Criteria A
EN-61000-4-8 30 A/m at 50/60 Hz Criteria A
EN-61000-4-11 0 % 1 cycle Criteria A
40 % 10 cycles Criteria A
70 % 25 cycles Criteria B
0 % 250 cycles Criteria B
Emission levels
CISPR 11 Instrument Class A, Group 1 Criteria A
Barberà del Vallès September 2017
Xavier Juncà - Product Manager
According to direcve 2012/19/EU, electronic equip-
ment must be recycled in a selecve and controlled
way at the end of its useful life.

FEMA ELECTRÓNICA . Series M . M40-T
16
2. Output and control modules
The R1 module provides 1 relay output to to install at digital panel
meters from Series M, up to a maximum of 3 relays in a single meter.
Note : for more than three relays per instrument or larger relay den-
sity per module, see special modules R2, R4 and R6.
Conguraon is performed from the frontal keypad of the meter, by
seng the parameters at the alarm menu. Check the parameters of
at the alarm menu for full informaon.
Relay with 3 contacts (common, normally open, normally closed)
with up to 250 Vac switching voltage and 8 A.
Modules R1 can be ordered pre-installed into a Series M digital panel
meter, or standalone for delayed installaon, as they do not require
soldering or special conguraon.
2.1 Module R1
For more informaon : hp://fema.es/docs/4254_SERIES_M-K-S_
OPTIONS_manual_i.pdf
Type of relay 3 contact relay (NC, NO, common)
Current maximum 8 A per relay (resisve load)
Voltage maximum* 250 Vac connuous
Isolaon 3500 Ve
Type of terminal plug-in screw terminal, pitch 5.08 mm
Slots allowed ‘Opt.1’, ‘Opt.2’, ‘Opt.3’
Terminal A Common
Terminal B NO - Normally open
Terminal C NC - Normally closed
Power
Opt.2
Opt.1
Opt.3
A B C
A B C
Signal
A B C
The T1 module provides 1 transistor output to install at digital panel
meters from Series M, up to a maximum of 3 transistors in a single
meter.
Conguraon is performed from the frontal keypad of the meter, by
seng the parameters at the alarm menu. Check the parameters of
at the alarm menu for full informaon.
Transistor output is optoisolated, provides 2 terminals for connec-
on, and can switch up to 35 V and 50 mA.
Modules T1 can be ordered pre-installed into a Series M digital panel
meter, or standalone for delayed installaon, as they do not require
soldering or special conguraon.
2.2 Module T1
For more informaon : hp://fema.es/docs/4254_SERIES_M-K-S_
OPTIONS_manual_i.pdf
Type of output transistor
Max. voltage 35 Vdc
Max. current 50 mA
Isolaon 3500 Ve
Type of terminal plug-in screw terminal, pitch 5.08 mm
Slots allowed ‘Opt.1’, ‘Opt.2’, ‘Opt.3’
‘B’
‘A’
Schemac for T1 output
Power
Opt.2
Opt.1
Opt.3
A B C
A B C
Signal
A B C

FEMA ELECTRÓNICA . Series M . M40-T
17
Output ranges 4/20 mA acve, 4/20 mA passive 0/10 Vdc
Accuracy (at 25 ºC) <0.1% FS
Isolaon 1000 Vdc
Slots allowed ‘Opt.1’, ‘Opt.2’, ‘Opt.3’
2.3 Module SSR
The AO module provides 1 analog output with 4/20 mA or 0/10 Vdc
congurable output range. Output current loop congurable as ac-
ve (the instrument provides the excitaon for the loop) or passive
(the loop is externally powered). Signal output proporonal to the
instruments reading. Fully congurable scaling, in direct (posive
slope) or inverse (negave slope) scaling.
Up to a maximum of 3 analog output modules can be installed in a
single instrument, all outputs isolated between them and isolated
from the power and input signal circuits.
Conguraon from instrument front keypad, through menu entries
‘Opt.1’, ‘Opt.2’ or ‘Opt.3’, depending on the posion the module is
installed.
The AO module can be ordered pre-installed into a Series M panel
meter, or standalone for delayed
installaon, as it does not require
soldering or special conguraon.
Terminal A Vexc
Terminal B Signal in mA or Vdc
Terminal C GND
Jumper M closed for mA
Jumper V closed for Vdc
For more informaon : hp://fema.es/docs/4254_SERIES_M-K-S_
OPTIONS_manual_i.pdf
Power
Opt.2
Opt.1
Opt.3
A B C
A B C
Signal
A B C
MVMV
MV
The SSR module provides 1 output to control SSR relays, to install at
digital panel meters from Series M, up to a maximum of 3 SSR con-
trols in a single meter.
Conguraon is performed from the frontal keypad of the meter, by
seng the parameters at the alarm menu. Check the parameters of
at the alarm menu for full informaon.
The module provides +15 Vdc voltage and up to 45 mA.
Modules SSR can be ordered pre-installed into a Series M digital
panel meter, or standalone for delayed installaon, as they do not
require soldering or special conguraon.
For more informaon : hp://fema.es/docs/4254_SERIES_M-K-S_
OPTIONS_manual_i.pdf
Type of output to control an SSR relay
Voltage output 15 Vdc
Max. current 45 mA
Isolaon 1000 Vdc
Type of terminal plug-in screw terminal, pitch 5.08 mm
Slots allowed ‘Opt.1’, ‘Opt.2’, ‘Opt.3’
Schemac for SSR control module
‘B’
‘A’
Relé SSR
+15 Vdc ‘C’
Power
Opt.2
Opt.1
Opt.3
A B C
A B C
Signal
A B C
2.4 Module AO

FEMA ELECTRÓNICA . Series M . M40-T
18
Protocol ASCII
Bus type RS-485, up to 57.6 Kbps
Isolaon 1000 Vdc
Slots allowed ‘Opt.1’, ‘Opt.2’, ‘Opt.3’
2.5 Module S4
The S4 module provides a RS-485 communicaons module for Series
M of panel meters. ASCII protocol with ‘Master’ / ‘Slave’ architec-
ture. Addressable with up to 31 modules. Frames codied in rep-
resentable ASCII characters (codes 32 to 255), directly visible using
‘hyperterminal’ or similar programs.
• Congurable for direct retransmission to remote meters M60-
485 (14 mm digit height) and BDF Series (60 mm and 100 mm digit
height).
• Access to display values, alarm status, memory of maximum and
minimum, alarm setpoints, ...
Conguraon from instrument front keypad, through menu entries
‘Opt.1’, ‘Opt.2’ or ‘Opt.3’, depending on the posion the module is
installed.
The S4 module can be ordered pre-installed into a Series M panel
meter, or standalone for delayed installaon, as it does not require
soldering or special conguraon.
Power
Opt.2
Opt.1
Opt.3
B A G
B A G
Signal
B A G
Terminal B B signal from RS-485 bus
Terminal A A signal from RS-485 bus
Terminal G GND
For more informaon : hp://fema.es/docs/4254_SERIES_M-K-S_
OPTIONS_manual_i.pdf
Protocol Modbus RTU
Funcons implemented 4 (Read_Input_Registers)
Bus type RS-485, up to 57.6 Kbps
Isolaon 1000 Vdc
Slots allowed ‘Opt.1’, ‘Opt.2’, ‘Opt.3’
The RTU module provides a Modbus RTU communicaons module
for Series M of panel meters. The RTU module implements funcon
‘4’ (‘Read Input Registers’) of the Modbus RTU protocol, to access the
instrument registers (reading value, alarm status, memory of maxi-
mum and minimum, ...)
Conguraon from instrument front keypad, through menu entries
‘Opt.1’, ‘Opt.2’ or ‘Opt.3’, depending on the posion the module is
installed.
The RTU module can be ordered pre-installed into a Series M panel
meter, or standalone for delayed installaon, as it does not require
soldering or special conguraon.
2.6 Module RTU
Terminal B B signal from RS-485 bus
Terminal A A signal from RS-485 bus
Terminal G GND
For more informaon : hp://fema.es/docs/4254_SERIES_M-K-S_
OPTIONS_manual_i.pdf
Power
Opt.2
Opt.1
Opt.3
B A G
B A G
Signal
B A G

FEMA ELECTRÓNICA . Series M . M40-T
19
2.7 Module S2
Protocol ASCII
Bus type RS-232, up to 57.6 Kbps
Isolaon 1000 Vdc
Slots allowed ‘Opt.1’, ‘Opt.2’, ‘Opt.3’
2.8 Modules R2, R4, R6
The R2, R4 and R6 modules provide 2, 4 and 6 relay outputs for Series
M panel meters. Relays with 3 contacts each, with switching capabil-
ity up to 250 V @ 6 A.
Modules R2, R4 and R6 are installed on slot ‘Opt.1’ (see secon 1.14)
and are congured from instruments front keypad, and provide set-
point conguraon, hysteresis, independent acvaon and deacva-
on delays, and second alarm setpoint for windowed alarms.
Only one module R2, R4 or R6 can be installed per instrument. Mod-
ules R2, R4 and R6 are not compable with standard R1,T1 and SSR
modules.
The R2, R4 and R6 modules can be ordered pre-installed into a Series
M panel meter, or standalone for delayed installaon, as they do not
require soldering or special conguraon.
The S2 module provides a RS-232 communicaons module for Series
M of panel meters. ASCII protocol with ‘Master’ / ‘Slave’ architec-
ture. Addressable with up to 31 modules. Frames codied in rep-
resentable ASCII characters (codes 32 to 255), directly visible using
‘hyperterminal’ or similar programs.
• Access to display values, alarm status, memory of maximum and
minimum, alarm setpoints, ...
Conguraon from instrument front keypad, through menu entries
‘Opt.1’, ‘Opt.2’ or ‘Opt.3’, depending on the posion the module is
installed.
The S2 module can be ordered pre-installed into a Series M panel
meter, or standalone for delayed installaon, as it does not require
soldering or special conguraon.
Relay Common Normally Open
(NO)
Normally Closed
(NC)
relay 1 A B C
relay 2 D E F
relay 3 G HI
relay 4 J K L
relay 5 M N O
relay 6 PQ R
Table 4 - Connecons for modules R2, R4 and R6
For more informaon : hp://fema.es/docs/4254_SERIES_M-K-S_
OPTIONS_manual_i.pdf
For more informaon : hp://fema.es/docs/4254_SERIES_M-K-S_
OPTIONS_manual_i.pdf
Type of relay 3 contact relay (NC, NO, common)
Current maximum 6 A per relay (resisve load)
Voltage maximum* 250 Vac connuous
Isolaon 2500 Ve
Type of terminal plug-in screw terminal, pitch 3.81 mm
* terminals approved for 300 V (according to UL1059, groups B and
D) and 160 V (according to VDE on CAT-III and polluon degree 3).
Module R2 occupies Opt.1
Module R4 occupies Opt.1 and Opt.2
Module R6 occupies Opt.1, Opt.2 and Opt.3
ABCDEF GHIJKL
MNOPQR
Power
Opt.2
Opt.1
Opt.3
Signal
Terminal E GND
Terminal D Rx1
Terminal C Tx1
Terminal B Rx2
Terminal A Tx2
Opt.2Opt.1
Opt.3
Power
ABCDE ABCDE
ABCDE
Signal

FEMA ELECTRÓNICA . Series M . M40-T
20
Green led digits opon.
Green digits
Instruments without front key-
pad. To congure the instrument,
remove the meter from the panel
and remove the front lter. Inter-
nal press buons for conguraon
are accessible. Oponally, request
the instrument precongured
from factory.
Without front keypad
3. Other opons
3.1 Opon NBT 3.2 Opon G
Other manuals for M Series
1
This manual suits for next models
1