FLS K315U User manual

K315U - Frequency Output & MIN alarm KIT for Ultra
Low Flow Sensor
INSTRUCTION MANUAL
EN 03-04
Table of Contents
1. Introduction………………………………………………………………… 2
1.1. Safety Instructions………………………………………………………………. 2
1.2. Unpacking………………………………………………………………………… 2
2. Description……………………………………………………………….… 2
3. Specifications…………………………………………………………….... 3
3.1. Technical Data…………………………………………………………………… 3
3.2. Dimensions……………………………………………………..……………..…. 3
4. Installation………………………………………………………………….. 4
4.1. Sensor Assembly………………………………………………………………… 4
4.2. Wiring………………………………………………………………………………. 5
5. Calibration………………………………………………………………….. 7
5.1. Calibration Mode………………………………………………………………... 7
5.2. Operative Mode……………………………………………………………..…… 7
6. Troubleshooting………………………………………………………..…. 8
7. Ordering Data……………………………………………………………… 8
K315U – Frequency Output & MIN Alarm
1

1. Introduction
1.1. Safety Instructions
General Statements
Do not install and service the device without following the Instruction Manual.
This unit is designed to be connected to other instruments which can be
hazardous if used improperly. Read and follow all associated instrument
manuals before using with this sensor.
Installation and wiring connections should only be performed by qualified staff.
Do not modify product construction.
Installation and Commissioning Statements
Remove power to the device before wiring any connection.
When the unit is powered and the cover is open, protection against electric
shocks is not ensured.
Do not exceed published specifications using this instrument.
To clean the device, use only chemical compatible products.
1.2. Unpacking
Please verify that the product is complete and without any damage. The following
items must be included:
• K315U – Frequency Output & MIN Alarm KIT for Ultra Low Flow Sensor with
PVC plate included
• Instruction Manual
2. Description
This Kit consists of an additional IP65
housing mounted aside the sensor via a
PVC plate. It is equipped with an open
collector frequency output and a
mechanical SPDT contact. The MIN alarm
set-point can be freely set by a
potentiometer up to 21 l/h (0.09 gpm) for
ULF01 and 53 l/h (0.23 gpm) for ULF03.
When the flow velocity drops below the
adjusted limit the relay output opens and
the Local Status Indicator changes colour.
It has been designed to protect a pump
from running dry or pumping against a
closed valve in the main pipeline.
K315U – Frequency Output & MIN Alarm
2

3. Specifications
3.1. Technical Data
Associated Flow Sensor: Hall effect (ULFXX.H)
Supply voltage: 12 to 24 VDC regulated
Output signal: square wave
Output type: transistor NPN open collector
Output current: 10 mA max.
Relay Output: mechanical SPDT contact, 3 A @ 30 VDC, 3 A @ 230VAC resistive load
Flow trip point: freely adjustable
- up to 21 l/h (0.09 gpm) for ULF01
- up to 53 l/h (3.34 gpm) for ULF03
Local Status Indicator: GREEN Led = Flow RED Led = No Flow
Enclosure: IP65
Operating temperature: 0 to 60°C (32 to 140°F)
Relative humidity: 0 to 95% non-condensing
Housing material: PVC
Standards & Approvals
Manufactured under ISO 9002
CE
3.2. Dimensions
K315 KIT
K315U – Frequency Output & MIN Alarm
3

ULF3.15 Sensor with O.C. output & MIN alarm
. Installation
4.1. Sensor Assembly
crew down completely the sensor onto the PVC plate and connect electric cables
4
S
according to specifications.
K315U – Frequency Output & MIN Alarm
4

4.2. Wiring
top cover to reach the electrical connections. All wiring connections to
K315U are made via removable terminals.
wer supply is switched off before working on the device.
Terminals accept 26 to 12 AWG (0.08 to 2.5 mm2)
al.
per part of the terminals for an easy cabling.
Sensor Wiring Diagram Power Wiring Diagram
Unscrew the
General recommendation
Always ensure the po
Strip around 10 mm (0.4”) of insulation from the wire tips and tin bare ends to
avoid fraying.
Ferrules are suggested when connecting more than one wire to a single termin
Remove the up
Insert wire tip or ferrule completely into the terminal and fix with the screw until
finger tight
K315U – Frequency Output & MIN Alarm
5

Frequency Output Wiring Diagram
elay Wiring Diagram
The alarm is OFF during
ormal operation.
tor
The FlowX3 monitor does not
provide power supply to the K315U
onnection to a PLC/Instrument with separate power supply
R
n
In alarm condition the
Local Status Indica
(LED) is RED.
Connection to FlowX3 Instruments
KIT.
External power supply is required.
onnection to a PLC with built-in power supply
C
C
K315U – Frequency Output & MIN Alarm
6

5. Calibration
Mode
FF position.
esponding to your Alarm
ondition (it should be as stable as possible).
3.
5.1. Calibration
1. Switch 1 must be in O
2. Induce in the pipe the flow rate corr
c
Turn the potentiometer (clockwise) until the led becomes
reen (not necessary if the led is already green).
4. ise
2
1
g
Turn the potentiometer in the opposite direction (anti clockw ) until the led turns
d. You must stop turning the potentiometer as soon as the led turns red.
5.
position.
most
uitable switch delay:
ct the 3 second
switch delay
• select the 10 seconds switch delay
n seconds.
re
Now the Alarm calibration is complete.
5.2. Operative Mode
Switch 1 must be in ON
Switch 2 can be used to select the
s
• OFF position to sele
ON position to
The electronics recognise switch 2 modification after te
2
1
2
1
K315U – Frequency Output & MIN Alarm
7

K31
8
www.flsnet.it
5U – Frequency Output & MIN Alarm
6. Troubleshooting
Problem
Reason
Solution
o nal
• No or wrong power supply
Incorrect handling of O.C.
• r doesn’t turn
Ve
Power supply (sec. 4.2. Wiring)
ections between K315U and
• inal
ing)
N output sig
•
output
• Incorrect cabling
The roto
rify :
•
• Conn
other electronic devices
(sec. 4.2. Wiring)
Wire insertions into in term
holes (sec. 4.2. Wir
• Flow velocity: it must be ≥
0,15m/s
•
• Incorrect setting alarm
rify :
•
• Wire
holes (sec. 4.2. Wiring)
• Unit Calibration
(sec 5. Calibration)
Relay no activated
• No or wrong power supply
Incorrect cabling
Ve
Power supply (sec. 4.2. Wiring)
insertions into in terminal
. Ordering Data
using Gaskets Enclosure Description
7
Part No. Ho
U Frequency Output &
MIN Alarm KIT
LF.K315U PVC EPDM IP65
F.I.P. Formatura Iniezione Polimeri S.p.A.
Loc. Pian di Parata, 16015 Casella (GE) – Italy
Tel +39 010 96211 – Fax +39 010 9621209
Table of contents
Other FLS Accessories manuals
Popular Accessories manuals by other brands

Qimarox
Qimarox PRORUNNER mk1 Assembly instructions

Salonserve
Salonserve Swan Steamer Installation and user guide

Heidolph
Heidolph EKT Hei-Con instruction manual

SafeTrust
SafeTrust 8845-000 quick start guide

Sonifex
Sonifex SignalLED Series User handbook

Broil King
Broil King DPA51 Installation and operation instructions

Philips
Philips OccuSwitch Classic LRL2390 Installation and programming guide

Philips
Philips Home Power SPS1461WA/37 user manual

Goobay
Goobay 41268 user manual

Novital
Novital Covatutto 108 User Instruction Poster

Wetelux
Wetelux 83 63 55 instruction manual

Millefiori
Millefiori Hydro NA-393 quick start guide