Fluidwell F133-P User manual

F133-P
Delivery controller / Dispenser
with pump start and valve control
Signal input flowmeter: pulse, Namur and coil.
Status inputs: start and stop.
Control outputs: two pump / valve control outputs.
Options: Intrinsically Safe, Modbus communication and backlight.
F-Series - Field mounted indicators for safe and hazardous areas.
More info: www.fluidwell.com/fseries

FW_F133P_v1702_02_EN
Page 2

FW_F133P_v1702_02_EN
Page 3
SAFETY INSTRUCTIONS
Any responsibility is lapsed if the instructions and procedures as described in this
manual are not followed.
LIFE SUPPORT APPLICATIONS: The F133-P is not designed for use in life support
appliances, devices, or systems where malfunction of the product can reasonably be
expected to result in a personal injury. Customers using or selling these products for
use in such applications do so at their own risk and agree to fully indemnify the
manufacturer and supplier for any damages resulting from such improper use or sale.
Electro static discharge does inflict irreparable damage to electronics! Before installing
or opening the unit, the installer has to discharge himself by touching a well-grounded
object.
This unit must be installed in accordance with the EMC guidelines (Electro Magnetic
Compatibility).
Do connect a proper grounding to the metal enclosure as indicated if the F133-P has an
incoming power line which carries a 115-230V AC. The Protective Earth (PE) wire may
never be disconnected or removed.
Intrinsically safe applications: follow the instructions as mentioned in Chapter 5 and
consult “Fluidwell F1..-..-XI - Documentation for Intrinsic safety”.
DISPOSAL OF ELECTRONIC WASTE
The WEEE Directive requires the recycling of disposed electrical and electronic equipment in the
European Union. When the WEEE Directive does not apply to your region, we support its policy
and ask you to be aware on how to dispose of this product.
The crossed out wheelie bin symbol as illustrated and found on our products tells that this
product shall not be disposed of into the general waste system or into a landfill.
At the end of its life, equipment shall be disposed of according to the local regulations regarding
waste of the electrical and the electronic equipment.
Please contact your local dealer, national distributor or the manufacturer’s Technical helpdesk for
information on the product disposal.
SAFETY RULES AND PRECAUTIONARY MEASURES
The manufacturer accepts no responsibility whatsoever if the following safety rules and
precautions instructions and the procedures as described in this manual are not followed.
Modifications of the F133-P implemented without preceding written consent from the
manufacturer, will result in the immediate termination of product liability and warranty period.
Mounting, electrical installation, start-up and maintenance of this device may only be carried out
by trained persons authorized by the operator of the facility. Persons must read and understand
this manual before carrying out its instructions.
This device may only be operated by persons who are authorized and trained by the operator of
the facility. All instructions in this manual are to be observed.
Check the mains voltage and information on the manufacturer's plate before installing the unit.
Check all connections, settings and technical specifications of the various peripheral devices
with the F133-P supplied.
Open the enclosure only if all leads are free of potential.
Never touch the electronic components (ESD sensitivity).
Never expose the system to heavier conditions than allowed according the classification of the
enclosure (see manufacture's plate and chapter 4).
If the operator detects errors or dangers, or disagrees with the safety precautions taken, then
inform the owner or principal responsible.
The local labor and safety laws and regulations must be adhered to.

FW_F133P_v1702_02_EN
Page 4
ABOUT THE MANUAL
This manual is divided into two main sections:
The daily use of the unit is described in chapter 2 "Operation". These instructions are meant for
users.
The following chapters and appendices are exclusively meant for electricians/technicians. These
provide a detailed description of all software settings and hardware installation guidance.
This manual describes the standard unit as well as most of the options available. For additional
information, please contact your supplier.
A hazardous situation may occur if the F133-P is not used for the purpose it was designed for
or is used incorrectly. Please carefully note the information in this operating manual
indicated by the pictograms:
A "warning !" indicates actions or procedures which, if not performed correctly, may lead to
personal injury, a safety hazard or damage of the F133-P or connected instruments.
A "caution !" indicates actions or procedures which, if not performed correctly, may lead to
personal injury or incorrect functioning of the F133-P or connected instruments.
A "note !" indicates actions or procedures which, if not performed correctly, may indirectly
affect operation or may lead to an instrument response which is not planned.
WARRANTY AND TECHNICAL SUPPORT
For warranty and technical support for your Fluidwell products,
Hardware Version : 1b03.01.03
Software Version : 03.03.01
Manual : FW_F133P_v1702_02_EN
© Copyright 2017 : Fluidwell B.V. - the Netherlands
Information in this manual is subject to change without prior notice. The
manufacturer is not responsible for mistakes in this material or for incidental
damage caused as a direct or indirect result of the delivery, performance or
use of this material.
© All rights reserved. No parts of this publication may be reproduced or used
in any form or by any means without written permission of your supplier.

FW_F133P_v1702_02_EN
Page 5
CONTENTS MANUAL
Safety instructions.................................................................................................................................3
Disposal of electronic waste..................................................................................................................3
Safety rules and precautionary measures.............................................................................................3
About the manual..................................................................................................................................4
Warranty and technical support ............................................................................................................4
Contents manual...................................................................................................................................5
1. Introduction.......................................................................................................................6
1.1. System description ......................................................................................................6
2. Operational .......................................................................................................................7
2.1. General........................................................................................................................7
2.2. Control panel ...............................................................................................................7
2.3. Operator information and functions.............................................................................7
2.4. dispenser functional diagram.......................................................................................9
3. Configuration...................................................................................................................10
3.1. How to program the F133-P......................................................................................10
3.1.1. Setup menu - Settings...............................................................................................12
3.1.2. Explanation of Setup menu 1 - Total.........................................................................13
3.1.3. Explanation of Setup menu 2 - Flow rate ..................................................................13
3.1.3. Explanation of Setup menu 3 - Display.....................................................................14
3.1.4. Explanation of Setup menu 4 - Power management.................................................14
3.1.5. Explanation of Setup menu 5 - Flowmeter ................................................................15
3.1.6. Explanation of Setup menu 6 - Control .....................................................................15
3.1.7. Explanation of Setup menu 7 - Status.......................................................................16
3.1.8. Explanation of Setup menu 8 - Communication (option)...........................................16
3.1.9. Explanation of Setup menu 9 - Others ......................................................................17
4. Installation.......................................................................................................................17
4.1. General directions......................................................................................................17
4.2. Installation / surrounding conditions..........................................................................17
4.3. Dimensions- Enclosure..............................................................................................18
4.4. Installing the hardware ..............................................................................................20
4.4.1. General installation guidelines...................................................................................20
4.4.2. Aluminum enclosure - Field mounted........................................................................21
4.4.3. Aluminum enclosure - Panel mounted.......................................................................21
4.4.4. Plastic (GRP) enclosure ............................................................................................22
4.4.3. Terminal connectors..................................................................................................23
5. Intrinsically safe applications ..........................................................................................30
5.2. Terminal connectors Intrinsically safe applications ...................................................31
5.3. Configuration examples Intrinsically Safe applications .............................................33
5.4 Battery replacement instructions ...............................................................................35
5.4.1. Safety instructions .....................................................................................................35
5.4.2. Replace the battery ...................................................................................................35
5.4.3. Disposal of batteries..................................................................................................35
6. Maintenance ...................................................................................................................36
6.1. General directions......................................................................................................36
6.2. Repair........................................................................................................................36
6.3. Repair policy..............................................................................................................36
Appendix A: Technical specification....................................................................................................37
Appendix B: Problem solving ..............................................................................................................40
Appendix C: Communication variables ...............................................................................................41
APPENDIX D: Declaration of Conformity............................................................................................44
Index of this manual............................................................................................................................45
List of figures in this manual................................................................................................................46

FW_F133P_v1702_02_EN
Page 6
1. INTRODUCTION
1.1. SYSTEM DESCRIPTION
Functions and features
The delivery controller / dispenser model F133-P is a microprocessor driven instrument designed for
the delivery of unknown quantities as well as displaying the flow rate, the delivered total and the
delivered accumulated total.
This product has been designed with a focus on:
ultra-low power consumption to allow long-life battery powered applications (type PB/PC);
intrinsic safety for use in hazardous applications (type XI),
ability to process all types of flowmeter signals;
transmitting possibilities with analog, pulse and communication outputs;
several mounting possibilities with GRP or aluminum enclosures for industrial surroundings.
Flowmeter input
This manual describes the unit with a pulse input from the flowmeter. Other versions are available to
process (0)4-20mA signals.
One flowmeter with a passive or active pulse, Namur or sine wave (coil) signal output can be
connected to the F133-P. To power the sensor, several options are available.
Standard outputs
Two transistor or relay (option) outputs: to control a pump and a valve. All kind of switch
conditions can be set to optimize the process control.
Fig. 1: Typical application
Configuration of the unit
The F133-P is designed for use in many types of applications. For that reason, a setup menu is
available to program the F133-P according to your specific requirements.
The setup includes several important features, such as K-Factors, engineering units, signal
selection, power management (to extend battery life-time), etc. All settings are stored in a non-
volatile memory and therefore kept in the event of a power failure or an exhausted battery.
Display information
The unit has a LCD with (optional) backlight to show the process information, status and alarm messages.
The display refresh rate is programmed in the setup menu.
At a key press, the display refresh rate will switch to FAST for 30 seconds. When 'OFF' is selected,
the display goes off after 30 seconds after the last key press. The display temporarily comes on after
a key press.
A backup of the total and accumulated total in EEPROM memory is made every minute.

FW_F133P_v1702_02_EN
Page 7
Options
The following options are available: full Modbus communication RS232/485/TTL (also battery
powered), intrinsic safety, mechanical relay or active output, power- and sensor-supply options,
panel -mount, wall-mount and weather-proof enclosures, flame proof enclosure and LED backlight.
2. OPERATIONAL
2.1. GENERAL
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Take careful notice of the "Safety rules, instructions and precautionary measures" in the
front of this manual.
This chapter describes the daily use of the F133-P . This instruction is meant for users / operators.
2.2. CONTROL PANEL
The control panel has three keys. The available keys are:
Fig. 2: Control Panel
Functions of the keys
This key is used to program and save new values or settings.
The PROG/ENTER key is also used to gain access to the setup menu (read
chapter 3).
This key is used to START the dispense process.
The START/key is also used to increase a value after the PROG/ENTER key has
been pressed (read chapter 3).
This key is used to pause or stop the dispense process.
The STOP/key is also used to select the batch total, the batch counter, the total
and the accumulated total.
The STOP/key is also used to select a digit or an option after the PROG/ENTER
key has been pressed (read chapter 3).
2.3. OPERATOR INFORMATION AND FUNCTIONS
In general, the F133-P operates in the operator mode. The shown information depends on the
settings which are made in the setup menu.
The signal from the connected sensor is processed by the F133-P in the background, independent
from the selected display refresh rate.
Start-up the delivery
You only can start-up when the "READY" indicator is shown on the display. When "READY" is
shown, the data of the last delivery is shown. When you press the "START" key, the F133-P initiates
a new delivery, the "RUN" indicator comes on and temporarily the total shows "8888888" and the
flow rate "88888". Depending on the setup of the F133-P, relays are switched to start the pump(s)
and to open the valve(s). In the software, a timer is started to monitor the flow rate.
When a flow is detected, the delivery will start and the total and the flow rate show the actual status.
When the flow rate is not sufficient, the delivery will not start and the Alarm indicator comes on, the
total shows "0000000" and the flow rate shows "not started". The startup sequence is stopped.
Fig. 3: Process information (typical)
Fig. 4: Delivery information (typical)
RUN
RUN

FW_F133P_v1702_02_EN
Page 8
Interrupt the delivery
After the startup sequence is completed, the
dispense sequence becomes active. During the
dispense sequence you can interrupt the
delivery temporarily with the STOP command.
The "PAUSE" indicator comes on and an
internal restart timer is started. Note that the
pump stays on and the valve is closed. The
delivery is continued when the restart timer still
active and the START command is given. When
the restart timer is lapsed, the delivery is
stopped automatically.
Fig. 5: Pause information (typical)
When "READY" is shown, following functions are available:
Batch-total
To display the batch-total, use the STOP button. This quantity equals the accumulated
delivered quantity (from the START moment till the READY moment) and cannot be initialized
by the operator. It will count up to 9999999.
Press STOP a few times to return to the main display information.
Batch-counter
To display the batch-counter, press STOP again. This counter displays the number of
deliveries that have been made successfully and cannot be initialized by the operator.
It will count up to 9999999.
Press STOP a few times to return to the main display information.
Display Total and accumulated Total
Press STOP to display the Total and Accumulated Total. These totalizers do count the
flowmeters signal continuously, even when no process is running.
The value for Total can be initialized. To do so, be sure Total is shown.
First press PROG followed by STOP. After pressing PROG, the text "PUSH STOP" is shown.
To avoid initialization in that stage, press a different key or wait for 20 seconds. Initialization of
Total DOES NOT influence accumulated Total.
Accumulated Total can never be initialized. This value will count up to 99999999999.
Press STOP a few times to return to the main display information.
Alarms
The following alarms can occur:
Flow rate alarm:
When the actual flow rate is outside the allowed range (as set in the setup menu), the delivery
will be paused automatically and an alarm message will be shown indicating the type of flow
rate alarm: "LO RATE" or "HI RATE". If pause is enabled, the delivery can be restarted.
Maximum batch:
When the total quantity delivered exceeds a certain quantity, the F133-P will switch-off all
relays and generate an "MAX BATCH" alarm.
If pause is enabled, the delivery can be restarted.
Low-battery alarm
Only use original batteries. Original batteries can be ordered at the manufacturer.
The use of unapproved batteries will void the warranty.
At the end of the battery’s life-time, the
voltage starts to drop. When the voltage
becomes too low, the battery indicator
comes on. When the battery indicator is on,
install a new and fresh battery as soon as
possible.
Fig. 6: Low-battery alarm (typical)
Alarm
When the alarm indicator is shown, refer to Appendix B: Problem Solving.
PAUSE

FW_F133P_v1702_02_EN
Page 9
2.4. DISPENSER FUNCTIONAL DIAGRAM
The function of the F133-P depends on the different settings in the setup menu. The example is
given for a typical configuration.
START THE DELIVERY
PAUSE / STOP THE DELIVERY (pause is enabled)
STOP THE DELIVERY (overrun timer is set)
LEGEND:
I: Idle, waits for new delivery.
A: Start, the START key is pushed to start a new delivery, the F133-P will reset itself.
B: Delay, time for the pump to start up.
C: Begin, pump is at delivery speed.
D: Startup, valve opens to build up the flow, flow detection is active.
E: Started, flow is present at required rate.
F: Not started, there is no flow or the flow is not sufficient, the valve closes and the display shows
NOT STARTED.
Pump, stopped
Timer, predefined by software
Pump, running
61
Timer, set by setup menu CONTROL
Valve, closed
Flow OK, restart timer active
Valve, open
Flow NOK, restart timer elapsed
Reset, predefined by software

FW_F133P_v1702_02_EN
Page 10
3. CONFIGURATION
This and the following chapters are exclusively meant for electricians and non-operators. In these,
an extensive description of all software settings and hardware connections are provided.
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must
read and understand this manual before carrying out its instructions.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Make sure, the measuring system is correctly wired up according to the wiring diagrams.
Protection against accidental contact is no longer assured when the housing cover is
removed or the panel cabinet has been opened (danger from electrical shock). The
housing may only be opened by trained persons authorized by the operator of the facility.
Take careful notice of the "Safety rules, instructions and precautionary measures" in the
front of this manual.
The setup menu is used to program the F133-P.
The setup menu is accessible at all times while the F133-P remains fully operational. Be aware that
in this case any change to the settings may have an influence on the operation.
It is possible to prevent access to the setup menu with a password. A password may be
required to enter the setup menu. Without this password, access is denied.
3.1. HOW TO PROGRAM THE F133-P
The setup menu has different
submenus. Each submenu has an
unique number which is shown in
front of the menu name.
Each setting has an unique two-
digit number which is shown in
front of the setting. The first digit
refers to the submenu and the
second digit refers to the setting.
Note that sometimes the name of
the setting is shown on the upper
line of the display.
How to enter the setup menu
When the setup menu is protected by a password, the F133-P asks for a password to access the
setup menu. When in the operator mode, press and hold the PROG/ENTER key for 7 seconds to
access the setup menu.
How to navigate in the setup menu
The setup menu has different submenus to program the F133-P. For navigation, the submenus
and the settings are identified with numbers (for the submenu: e.g. 1; for the setting: e.g. 12.).
The STOP/► key and the PROG/ENTER key are used for navigation. The explanation assumes
that you are in the submenu PRESET.
Action
Result
Remark
1
Press the STOP/► key
to select the next
submenu.
The submenu FLOW
RATE shows
-
2
Press again to go to the
next submenu.
The submenu OVERRUN
shows.
-
3
Momentarily, press the
PROG/ENTER key to
select the previous
submenu.
The submenu FLOW
RATE shows
-
4
Press again to go to the
previous submenu.
The submenu PRESET
shows
-

FW_F133P_v1702_02_EN
Page 11
The START/▲ key and the STOP/► key are used for navigation.
The explanation assumes that you are in the submenu PRESET. When you are:
in the first setting and you navigate to the previous setting, the F133-P goes back to the related
main menu.
in the last setting and you navigate to the next setting, the F133-P goes to the related main
menu.
Action
Result
Remark
1
Press the START/▲ key to
select the first setting.
The setting UNIT shows.
-
2
Press the START/▲ key
again to go to the next
setting.
The setting DECIMALS
shows.
-
3
Press the STOP/► key to
select the previous setting.
The setting UNIT shows.
-
4
Press the STOP/►key
again to go to the previous
setting.
The submenu PRESET
shows
This is normal behavior because
the setting UNIT is the first
setting of the submenu
PRESET.
How to make a setting
Changes are only saved when you press the PROG/ENTER key.
The explanation assumes that you are in the submenu PRESET and the setting UNIT. When you do
not want to save the change, wait for approximately 20 seconds or press and hold the
PROG/ENTER key for approximately 3 seconds.
Action
Result
Remark
1
Momentarily, press the
PROG/ENTER key.
The PROG indicator blinks.
The engineering unit L shows.
To access the setting.
2
Press the START /▲ key to
select the next engineering
unit.
The PROG indicator blinks.
The engineering unit m3shows.
If you wait too long, the
program mode goes off and
changes are not saved, this is
normal behavior.
3
Press the START /▲ key to
select the next engineering
unit.
The PROG indicator blinks.
The engineering unit US GAL
shows.
-
4
Press the STOP /► key to
select the previous
engineering unit
The PROG indicator blinks.
The engineering unit m3shows.
-
5
To confirm the changes:
Momentarily, press the
PROG/ENTER key.
The PROG indicator goes off.
The change is saved.
The engineering unit m3shows.
If you do not press the
PROG/ENTER key to confirm,
your selection is not saved.
To discard the changes:
Press and hold the
PROG/ENTER key for
approximately 3 seconds.
The PROG indicator goes off.
The change is discarded.
The engineering unit L shows.
-

FW_F133P_v1702_02_EN
Page 12
3.1.1. SETUP MENU - SETTINGS
1
TOTAL
11
unit
L; m3; kg; lb; GAL; USGAL; bbl; no unit
12
decimals
0000000; 111111.1; 22222.22; 3333.333
13
K-factor:
0.000010 - 9999999
14
decimals K-factor
0 - 6
15
batch-max
0 - 9999999
16
batch total
0.001 - 9999999
17
batch count
0 - 9999999
2
FLOW RATE
21
unit
mL; L; m3; mg; g; kg; ton; gal; bbl; lb; cf; rev; - - - - (no unit); scf; nm3; nL; p
22
time
/sec; /min; /hour; /day
23
decimals
0000000; 111111.1; 22222.22; 3333.333
24
K-factor
0.000010 - 9,999,999
25
decimals K-factor
0 - 6
26
calculation
per 1 - 255 pulses
27
cut-off
0.1 - 999.9 seconds
28
low flow rate alarm
0.001 - 9999999
29
high flow rate alarm
0.001 - 9999999
2A
delay time alarm
0.0 - 999.9 seconds
3
3
DISPLAY
31
light
0% (off); 20%; 40%; 60%;- 80%; 100% (full brightness)
32
BL alarm
off; on. flash
4
POWER MANAGEMENT
41
LCD new
fast; 1 sec; 3 sec; 15 sec; 30 sec; off
42
battery mode
operational; shelf
5
FLOWMETER
51
signal
npn; npn-lp; reed; reed-lp; pnp; pnp-lp; namur; coil-hi; coil-lo; 8-1 DC;
12 DC; 24 DC
6
CONTROL
61
delay
0.1 - 999.9 seconds
62
begin
0.1 - 999.9 seconds
63
start-up
0.1 - 999.9 seconds
64
no pulse
0.1 - 999.9 seconds
65
pause
disable - enable
66
restart
0.1 - 999.9 seconds
67
overrun
0.1 - 999.9 seconds
7
STATUS
71
status 1
start; stop; continue; off
72
status 2
stop; pause; both; off
8
COM MODB
81
speed
1200; 2400; 4800; 9600
82
address
1 - 247
83
mode
bus-rtu; bus-asc; off
84
databits
7 bits; 8 bits
85
parity
odd; even; none
86
comm. lock
disable; time-out; full
9
OTHERS
91
model
F133-P
92
software version
nn:nn:nn
93
serial no.
nnnnnnn
94
password
0000 - 9999
95
tag-nr
0000000 - 9999999

FW_F133P_v1702_02_EN
Page 13
3.1.2. EXPLANATION OF SETUP MENU 1 - TOTAL
UNIT
11
This setting is used to select the engineering unit for the indication of the batch
total and the accumulated total.
When you change the engineering unit, you must recalculate and
reprogram the K-factor for the (accumulated) total. When you
recalculate and reprogram the K-Factor, the history for
(accumulated) batch total is not correct anymore, because the
(accumulated) batch total is not recalculated. For future reference,
best practice is to make a note of the accumulated total before you
program the recalculated K-Factor.
DECIMALS
12
This setting is used to set the amount of digits behind the decimal point for the
(accumulated) total indication.
K-FACTOR
13
This setting is used to set the K-Factor for the total. With the K-Factor, the
flowmeter pulse signals are converted to a quantity. The K-Factor is based on the
number of pulses generated by the flowmeter per selected engineering unit, for
example per m3. A more accurate K-Factor (more decimals, as set in decimals
K-Factor) allows for a more accurate operation of the system.
Example 1: Calculating the K-Factor.
The flowmeter generates 2.4813 pulses per liter and the selected unit is m3. A
cubic meter consists of 1000 liter which gives 2.4813 pulses*1000 liter=2481.3
pulses per m3. So, the K-Factor is 2481.3. Enter for the Flowmeter K-Factor:
24813 and for the flowmeter K-Factor decimals: 1.
Example 2: Calculating the K-Factor.
The flowmeter generates 6.5231 pulses per gallon and the selected engineering
unit is gallons. So, the K-Factor is 6.5231. Enter for the Flowmeter K-Factor:
65231 and for the Flowmeter K-Factor decimals: 4.
When you recalculate and reprogram a new K-Factor, the history for
(accumulated) batch total is not correct anymore, because the
(accumulated) batch total is not recalculated. For future reference,
best practice is to make a note of the accumulated total before you
program the recalculated K-Factor.
DECIMALS K-FACTOR
14
This setting is used to set the amount of digits behind the decimal point for the
K-Factor.
BATCH MAX
15
This setting is used to set the upper limit for a batch volume. An operator
cannot set a batch volume which is beyond the upper limit.
BATCH TOTAL
16
Batch total - also shown at operator level - displays the accumulated
quantity of product being delivered. From here, this total can be
programmed to zero or to any desired quantity.
BATCH COUNTER
17
Batch count - also shown at operator level - displays the number of
deliveries executed. From here, this total can be reset to zero or being
programmed to any desired quantity
3.1.3. EXPLANATION OF SETUP MENU 2 - FLOW RATE
The settings for total and flow rate are entirely separate. In this way, different engineering units can
be used for each e.g. cubic meters for total and liters for flow rate.
UNIT
21
This setting is used to select the engineering unit for the indication of the flow rate.
Alteration of the engineering unit will have consequences for
operator and SETUP-level values, they will not be automatically
recalculated to the value of the new selected unit. The K-factor has
to be adapted as well; the calculation is not done automatically.
TIME
22
This setting is used to set the time unit for the flow rate calculation. Note that the
flow rate is given in engineering unit/time unit, e.g. liters/minute (l/min).
When you change this setting, also recalculate and change the settings
for the analog rate-min and analog rate-max.
DECIMALS
23
This setting is used to set the amount of digits behind the decimal point for the
flow rate indication.
K-FACTOR
24
This setting is used to set the K-Factor for the flow rate. With the K-Factor, the
flowmeter pulse signals are converted to a quantity. The K-Factor is based on the
number of pulses generated by the flowmeter per selected engineering unit, for

FW_F133P_v1702_02_EN
Page 14
example per m3. A more accurate K-Factor (more decimals, as set in decimals
K-Factor) allows for a more accurate operation of the system.
DECIMALS K-FACTOR
25
This setting is used to set the amount of digits behind the decimal point for the
K-Factor.
CALCULATION
26
The flow rate is calculated by measuring the time between a number of
pulses, for example 10 pulses. The more pulses the more accurate the
flow rate will be. The maximum value is 255 pulses.
This setting does influence the update interval for the flow rate and
thus, indirectly the update interval of the analog output.. (maximum
update 10 times a second). If the output response is too slow, decrease
the number of pulses. For low frequency applications (< 10Hz): do not
program more than 10 pulses, else the update time will be very slow.
For high frequency applications (> 1kHz): do program 50 or more pulses.
CUT-OFF
27
This setting is used to set the threshold for a minimum flow. If during this
time less than XXX-pulses are generated (refer to Calculation), the flow
rate will be shown as zero. The cut-off has to be entered in seconds.
LOW FLOW RATE
ALARM
28
This setting is used to activate the related alarm condition and to set the
threshold value for a this flow alarm. The setting 0.0 disables this alarm.
HIGH FLOW RATE
ALARM
29
This setting is used to activate the related alarm condition and to set the
threshold value for a this flow alarm. The setting 0.0 disables this alarm.
DELAY TIME ALARM
2A
This setting is used to set a delay time for the related alarm. When the
alarm condition is still valid after the delay time, an alarm is given.
3.1.3. EXPLANATION OF SETUP MENU 3 - DISPLAY
LIGHT
33
The backlight brightness can be adjusted from 0% (off) to 100% (full
brightness) in steps of 20%.
When the F133-P is only loop powered, the backlight is disabled. An
external power supply is required to supply the backlight.
BL ALARM
34
This setting is used to set the behavior of the backlight (bl) during an alarm
condition.
3.1.4. EXPLANATION OF SETUP MENU 4 - POWER MANAGEMENT
When used with the internal battery option (type PB/PC), the user can expect reliable measurement
over a long period of time. The F113-P has several smart power management functions to extend
the battery life time significantly. Two of these functions can be set.
LCD NEW
41
The calculation of the display-information influences the power
consumption significantly. When the application does not require a fast
display refresh rate, it is strongly advised to select a slow refresh rate.
Please understand that NO information will be lost; every pulse will be
counted and the output signals will be generated in the normal way.
At a key press, the display refresh rate will switch to FAST for 30
seconds. When 'OFF' is selected, the display goes off after 30 seconds
after the last key press. The display temporarily comes on after a key
press.
Example battery life-time with a coil pick-up:
1kHz pulse and FAST update: about 2 years;
1kHz pulse and 1 sec update: about 5 years.
BATTERY MODE
42
The F113-P has two modes: operational or shelf.
After "shelf" has been selected, the F113-P can be stored for several years; it will
not process the sensor signal; the display is switched off but all settings and totals
are stored. In this mode, power consumption is extremely low.
To wake up the F113-p again, press the select/key two times.

FW_F133P_v1702_02_EN
Page 15
3.1.5. EXPLANATION OF SETUP MENU 5 - FLOWMETER
SIGNAL
51
With this setting the type of flowmeter output is selected. The settings with
LP (low-pass) filter are used to apply a build-in noise reduction.
Selections "active pulse" offer a detection level of 50% of the supply
voltage.
TYPE OF SIGNAL
EXPLANATION
RESISTANCE
FREQ./MV
REMARK
NPN
NPN input
100 kΩ pull-up
max.6 kHz.
(open collector)
NPN - LP
NPN with low pass filter
100 kΩ pull-up
max.1.2 kHz.
(open collector)
less sensitive
REED
Reed-switch input
1 MΩ pull-up
max.1.2 kHz.
REED - LP
Reed-with low pass filter
1 MΩ pull-up
max.120 Hz.
Less sensitive
PNP
PNP input
100K pull-down
max.6 kHz.
PNP - LP
PNP with low pass filter
100K pull-down
max.1.2 kHz.
Less sensitive
NAMUR
NAMUR input
820 Ω pull-down
max.4 kHz.
External power
required
COIL-HI
High sensitive coil input
-
min. 20 mVpp
Sensitive for
interference!
COIL-HI (option ZF)
min. 10 mVpp
COIL-HI (option ZG)
min. 5 mVpp
COIL LO
Low sensitive coil input
-
min. 80 mVpp
Normal
sensitivity
8-1 DC
Active pulse input
detection level 8.2V DC
3K9
max.10KHz.
External power
required
12 DC
Active pulse input
detection level 12V DC
4K
max.10KHz.
External power
required
24 DC
Active pulse input
detection level 24V DC
3K
max.10KHz.
External power
required
3.1.6. EXPLANATION OF SETUP MENU 6 - CONTROL
Two open-collector outputs (Optional: mechanic relays or active outputs) are available to control
relays or small valves (max. 50VDC –300mA). It is advised to use relay one for pump-start and
relay two for the valve control.
DELAY TIME
61
This is the time between the moment of a start-signal and the moment before
relay 2 will be switched on. In the mean time, relay 1 will be switched to
control e.g. a pump. With time 0.0 seconds, this function is disabled.
BEGIN TIME
62
After the delay-time (61), relay 2 will be switched-on as well. and the
“begin-time” becomes valid. The unit has to receive about twice the
number of pulses as programmed with setting 26, before “start-up time”
(setup 63) becomes valid.
If not enough pulses have been received within this time, the delivery will
be cancelled. With time 0.0 seconds, this function is disabled.
START-UP TIME
63
Now, the start-up time allows the system to become operational without
having a low-flow rate alarm. After this time, the system will become full
operational. With time 0.0 seconds, this function is disabled.
NO PULSE TIME
64
As soon as the unit is full operational, the flow can be monitored. The
F133-P will switch-off relay 1 and 2 (or relay 2 only: see setting 65/66) as
soon as during X-seconds no pulses have been received from the
flowmeter. In most cases, this is “end of process” (see 65).
With time 0.0 seconds, this function is disabled.
PAUSE
65
With this function, a “pause-function” can be enabled: if during the
process “stop” will be pressed, or the process is interrupted for another
reason like “no pulse time”, “flow rate alarm” or with the “status input”, the
batch will be stopped but can be resumed. If the unit comes in “PAUSE”,
relay 2 will be switched-off but relay 1 (pump control) remains energized.
Applications where this function is useful is delivery of sub-batches for
example where you want to have one “overall” total.
RESTART TIME
66
Following setup 65, the F133-P allows the Operator to restart a delivery
within X-seconds. If this does not happen within this time, the delivery will
be finished completely. With time 0.0 seconds, this function is disabled.

FW_F133P_v1702_02_EN
Page 16
OVERRUN TIME
67
As soon as a delivery has been finished, the relays will be switched-off
but there may still be some flow till the valve is closed. During this
“overrun-time” all pulses will be counted as being part of the delivery. We
advise to program a time of one second or a couple of seconds,
depending on the response time of your system to close the valve. With
time 0.0 seconds, this function is disabled.
3.1.7. EXPLANATION OF SETUP MENU 7 - STATUS
For external control of the F133-P, the unit can be started and/or stopped with two external switches.
STATUS INPUT 1
71
Following functions can be selected:
OFF: status input is disabled.
START-function: do generate a short pulse to start a delivery.
STOP-function: do generate a short pulse to stop the delivery.
CONTINUOUSLY: do switch the input continuously to execute a delivery;
first “disconnect” when the delivery is READY.
When it is interrupted during the batch, the unit goes
always to “READY”. To start-up a new batch, the input
must be interrupted for at least 100msec. in-between
deliveries
STATUS INPUT 2
72
Following functions can be selected:
OFF: status input is disabled.
PAUSE-function: do generate a short pulse to pause the delivery.
STOP-function: do generate a short pulse to stop the delivery.
BOTH-function: do generate a short pulse to pause the delivery.
One more pulse will stop the delivery.
3.1.8. EXPLANATION OF SETUP MENU 8 - COMMUNICATION (OPTION)
This product is designed for the connection to a communication network. Products with a
communication option do not include cyber security functions. Fluidwell cannot take any
responsibility for the cyber security, omissions or errors in the communication safety. To maintain a
secure operation, automation and control, it is the sole responsibility of the owner to install and
manage the appropriate safety measures to protect the network, the product and the communication
against any kind of security breaches.
The functions described below deal with hardware that is not part of the standard delivery.
Programming of these functions does not have any effect if this hardware has not been installed.
Consult Appendix C and the Modbus communication protocol description for a detailed explanation.
SPEED
81
This setting is used to set the Baudrate.
ADDRESS
82
This setting is used to set the communication address for the F133-P.
MODE
83
This setting is used to set the Modbus transmission mode. Select OFF to
disable the communication.
DATABITS
84
This setting determines for communication the number of databits.
Select 8 bit for BUS-RTU and 7 bits for BUS-ASC.
PARITY
85
As demanded by the connected equipment, select a parity bit (odd, even or none).
COMM. LOCK
86
With this setting, you determine if the unit will be locked after a delivery
till the unit will be released through communication (read appendix C
Communication variables)
Following can be selected:
disable: function is disabled
time-out: the unit will be locked for 10 minutes or till communication
release. If nothing happens within 10 minutes, the unit will
release itself automatically.
full: the unit can only be released through communication. When
the delivery is waiting to be released, the display will show
‘FINISHING’. Note that all keys and external controls are
disabled during this time.
When you select this option you can ONLY release the unit to normal
operation after each delivery through communications. If you accidentally
lock yourself out, please remove all power (including the battery) so the unit
will restart. You can then enter the setup-level to change this setting.

FW_F133P_v1702_02_EN
Page 17
3.1.9. EXPLANATION OF SETUP MENU 9 - OTHERS
For support and maintenance it is important to have information about the characteristics of the F133-P. Your
supplier will ask for this information when support is required.
MODEL
91
This setting shows the model name.
SOFTWARE VERSION
92
This setting shows the version number of the firmware (software).
SERIAL NO
93
This setting shows the serial number.
PASSWORD
94
This setting is used to set a password (pin code) to limit the access for the
setup menu. Only persons who know the pin code can access the setup
menu. The pin code 0000 disables the pin code to allow for access by any
person.
TAG-NR
95
This setting is used to set a tag number for the F133-P.
4. INSTALLATION
4.1. GENERAL DIRECTIONS
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must
read and understand this manual before carrying out its instructions.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Make sure, the measuring system is correctly wired up according to the wiring diagrams.
Protection against accidental contact is no longer assured when the housing cover is
removed or the panel cabinet has been opened (danger from electrical shock). The
housing may only be opened by trained persons authorized by the operator of the facility.
Take careful notice of the "Safety rules, instructions and precautionary measures" at the
front of this manual.
4.2. INSTALLATION / SURROUNDING CONDITIONS
Take the relevant IP classification of the
enclosure into account (see identification plate).
Even an enclosure rated for IP67 / TYPE 4(X)
should NEVER be exposed to strongly varying
(weather) conditions.
When panel-mounted, the front panel of the
F133-P is rated for IP65 / TYPE 4(X)!
When used in very cold surroundings or varying
climatic conditions, inside the instrument case,
take the necessary precautions against
moisture.
Mount the F133-P onto a solid structure to
avoid vibrations.

FW_F133P_v1702_02_EN
Page 18
4.3. DIMENSIONS- ENCLOSURE
Fig. 7: Aluminum enclosures - Dimensions
75 mm (2.95")
130 mm (5.12") 112 mm (4.40")
120mm(4.72”)
M20 x 1,5
PG9 PG9
30mm 30mm
M20 x 1,5
M16 x 1,5 M16 x 1,5
30mm 30mm
M20 x 1,5
M20 x 1,5 M20 x 1,5
25mm 25mm
1/2"NPT
0.9”
3x 1/2"NPT
0.12" 0.12"
HA
HM
HN
HO
HP
HT
HU
6 x M12
12mm 12mm
24mm24mm
36mm
36mm
14mm17mm
115 mm (4.53”)
HB
29.1 mm (1.15”)
31 mm
(1.22”)
HZ
4x M20 x 1,5
15 15
HV
2323
16
mm
1/2"NPT 1/2"NPT
25mm 25mm
22,5mm
HL
22,5mm22,5mm22,5mm22,5mm
0.9”
15
60mm(2.36”)
98mm(3.86”)

FW_F133P_v1702_02_EN
Page 19
GRP enclosures:
Fig. 8: GRP enclosures - Dimensions
75 mm (2.95")
130 mm (5.12") 112 mm (4.40")
60 mm (2.36")
120 mm (4.72")
HD
HK
HK back box:
(flat bottom)
HE
HF
HG
HH
D=12mm
12mm 12mm
24mm24mm
36mm
36mm
14mm 17mm
22,5mm
30mm 30mm
D=16mm
D=20mm
0.9"
D=22mm (0.866")
22,5mm
25mm 25mm
D=20mm D=20mm
D=16mm
HC
75 mm (2.95") 118 mm (4.65”)
104 mm (4.09”)
HJ
0.9”
0.12” 0.12”
3x D=22mm (0.866”)
115 mm (4.53”)
98 mm (3.86”)
29.1 mm (1.15”)
31 mm
(1.22”)

FW_F133P_v1702_02_EN
Page 20
4.4. INSTALLING THE HARDWARE
Electro static discharge does inflict irreparable damage to electronics! Before installing or
opening the F133-P , the installer has to discharge himself by touching a well-grounded
object.
Do ground the aluminum enclosure properly as indicated. It is the responsibility of the
installer to install, connect and test the Protective Earth connections in accordance with
the (inter)national Rules and Regulations.
This chapter shows general information regarding the electrical installation of the F133-P .
Chapter 5 gives additional specific information regarding Intrinsically safe installation and
overrules the information given in this chapter.
4.4.1. GENERAL INSTALLATION GUIDELINES
In the F133-P , different types of bonding and earthing are used. The common (ground) is mostly
used for termination of the wire shields and the Protective Earth (PE) is used for electrical safety.
The F133-P that came with a power module type PM; 110V-230V AC or type PD/PF with an
option OR (the relays can handle 110V-230V AC) shall be connected to the Protective Earth (PE)
stud which is installed in the metal back panel. The metal front panel is connected to the
Protective Earth by the mounting screws and serrated washers.
For V AC applications, the terminal 00 shall not be connected to avoid earth loops.
For V DC applications, the terminal 00 shall be connected to the common (do NOT use for PE).
The wire screens (shield) are meant to prevent electromagnetic interference and shall be,
galvanic isolated, connected to the common ground terminals that belong to the specific sensor
connection. The wire screens shall be terminated at one side to prevent wire loops. Inside of the
Fluidwell unit, the different common ground terminals are connected to each other. It is advised,
as illustrated, to terminate the wire screens in the vicinity of the sensor and to insulated the wire
screen with a shrink tube at the Fluidwell unit side.
Separate cable glands with effective IP67 / TYPE 4(X) seals for all wires.
Unused cable entries: make sure that you fit IP67 / TYPE 4(X) plugs to maintain rating.
A reliable ground connection for both the sensor, and if applicable, for the metal enclosure
(above).
An effective screened cable for the input signal, and grounding of its screen to the “┴ “ terminal or
at the sensor itself, whichever is appropriate to the application.
Field mounted
Panel mounted
Other manuals for F133-P
1
Table of contents
Other Fluidwell Controllers manuals

Fluidwell
Fluidwell F131-P User manual

Fluidwell
Fluidwell N Series User manual

Fluidwell
Fluidwell D Series User manual

Fluidwell
Fluidwell F133-P User manual

Fluidwell
Fluidwell F132-P User manual

Fluidwell
Fluidwell D030-P Series User manual

Fluidwell
Fluidwell F074-A User manual

Fluidwell
Fluidwell F130-P User manual

Fluidwell
Fluidwell F124-P User manual

Fluidwell
Fluidwell F130-P User manual