Forza FDC-1502R User manual

2-
Year
warranty

Table of contents
1. Introduction
1-1. Transportation
1-2. Preliminary steps
1-3. Initial setup
1-4. Important safety instructions
1-5. Maintenance, service and faults
2. Operation
2.1 Unpacking and inspection
2.2 UPS front and rear panel views
2.3 Installation procedure
2.4 UPS connections
2.5 Turning on the UPS
2.6 Battery replacement
2.7 ForzaTracker monitoring software
3. Advanced operation
3.1 Button and function description
3.2 LCD panel
3.3 Audible alarm
3.4 Abbreviations on the LCD display
3.5 UPS parameter settings
3.6 Operation mode description
3.7 Fault codes
3.8 Warning indicators
4. Troubleshooting
5. Storage and maintenance
6. Technical specifications
1. Introduction
Thank you for purchasing the Forza FDC-1502R and FDC -3002R Online UPS. To enjoy all the features and benefits of this unit, please
read and follow all installation and operation instructions thoroughly before unpacking, installing or operating this device. After you
have read this manual, keep it in a safe place for future reference.
The information contained in this manual covers the 1500VA and 3000VA uninterruptible power system, its basic functions, operating
procedures, options available and troubleshooting guide. It also includes information on how to ship, store, handle, and install the
equipment.
1-1. Transportation
• Make sure to transport the UPS system only in the original package to protect it against shock and impact.
1-2. Preliminary steps
• Water condensation may occur if the UPS is unpacked in a very cold environment and then moved to a warmer location.
• The UPS must be thoroughly dry before being installed. Failure to do so may increase the risk of electric shock.
• Do not install the UPS system near water or in moist environments.
• Do not install the UPS system where it would be exposed to direct sunlight or near a heater or heating vent.
• Do not block ventilation holes in the UPS housing.
1-3. Initial setup
Do not connect appliances or equipment that may overload the UPS system (such as a laser printer) to the output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances, such as hair dryers, to the UPS output sockets.
Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system.
Use only CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the
building wiring outlet (shockproof outlet).
Use only CE-marked power cables to connect the loads to the UPS system.
During the installation of this equipment, make sure that the sum of the leakage currents of the UPS and the connected loads shall
not exceed 3.5 mA.
CAUTION: The unit is heavy. Lifting the unit requires a minimum of two people.
•
•
•
•
•
•
•
1-4. Important safety instructions
Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) at any time, since this
would cancel the protective earth of the UPS system and of all connected loads.
Connect the UPS only to a grounded socket that meets electrical safety guidelines.
Locate the UPS near a wall socket. Do not use an extension cord between the UPS and the socket.
In the event of an emergency, press the OFF/Enter button and disconnect the power cord from the AC mains to properly disable
the UPS.
Do not allow any kind of liquid or foreign object to enter this UPS unit. Do not place beverages or any other containers with liquid
on or nearby the unit.
The UPS can be operated by any individual with no previous experience.
•
•
•
•
•
•

1-5. Maintenance, service and faults
The voltage used by this UPS may be hazardous. The unit contains no user serviceable parts; do not attempt to disassemble the
unit. Only qualified service technicians can perform maintenance on the unit. Failure to adhere to this could cause personal injury or
equipment malfunction and void the warranty.
Caution: - risk of electric shock. Even after the unit is disconnected from the mains, components inside the UPS system are still
connected to the battery packs which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no
hazardous voltage exists in the terminals of high capacity capacitors, such as BUS-capacitors. Servicing of batteries should be
performed or supervised by experts who possess the knowledge to closely follow all required precautions.
To avoid electrical shock, turn off the unit and unplug it form the AC power source before servicing the battery.
Caution: potentially hazardous voltages from the battery can still be present even after disconnecting the UPS from the AC mains.
Therefore, the positive and negative terminals of the battery shall de disconnected prior to performing any maintenance or repair
inside the unit.
A battery can present the risk of short-circuit current and electrical shock. The following precautions should be taken:
- Remove wristwatches, rings and other metal objects
- Use only tools with insulated grips and handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting battery terminals.
- Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any
part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds
are removed during installation and maintenance.
When replacing the battery, make sure to use the same type and number of sealed lead-acid batteries specified. We recommend
using the Forza FUB-1290, a 12V 9A cell.
Do not dispose of batteries in a fire. Batteries may explode if exposed to high temperatures.
Never try to open a battery. The cell contains a toxic electrolyte which is harmful to the skin and eyes.
Replace the fuse only with the same type and amperage in order to avoid fire hazards.
Do not dismantle the UPS system.
•
•
•
•
•
•
•
•
•
•
•
2. OPERATION
2-1. Unpacking and inspection
2-2. UPS diagram
Front view
• One UPS unit
• One user manual
• One monitoring software CD (ForzaTracker)
• One USB cable
• Rack mounting hardware
• Tower support base
• Warranty certificate
Carefully inspect the UPS to check for any damages that may have occurred during shipping.
Should any evidence of damage be found or if some parts are missing, do not turn the UPS on; you must immediately
notify the carrier or dealer where you purchased the unit.
Remove the UPS from its package and make sure that all the following items are included:
2.3. Installation procedure
Choose location
Rear view
Cooling fan(s)
Emergency Power off connector
Battery bank terminal
RS-232 communication port
USB communication port
SNMP intelligent slot
Dedicated outlets for critical loads
Programmable outlets for non-critical loads
AC input
Input circuit breaker
Output circuit breakers
Modem/Phone/Network surge protection
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
FDC-1502R FDC-3002R
Install the UPS unit in any protected environment that provides adequate airflow around the unit, and free from excessive dust, corrosi-
ve fumes and conductive contaminants. Do not operate your UPS in an environment where the ambient temperature or humidity is
high. For best performance, keep the indoor temperature between 0° C and 40° C. Place the UPS unit at least 20 cm away from
monitors to avoid interference.

2.3.1 Initial setup
• For safety considerations, the UPS is shipped out from the factory with battery wires disconnected.
• Before installing the UPS, the user must first reconnect the wires. To do so, follow the steps illustrated below.
2-4. UPS connections
2-4.1 UPS input connection
• Plug the UPS into a two-pole, three-wire, grounded receptacle only.
• Avoid using extension cords or adapter plugs.
• Connect a single line modem/phone/fax cable into the network surge-protection “IN” jack on the rear panel of the UPS.
• Connect a network cable from the OUT jack on the rear of the UPS to a port on a PC or network device such as a router.
2-4.2 UPS output connection
2.4.3 Disabling and enabling the EPO function
For socket-type outputs, there are two kinds of outputs: programmable outlets and general outlets. Connect non-critical devices
to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to
critical devices by setting shorter backup times for non-critical devices.
To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of the communication cable to the
USB/RS-232 port, and the other end to the communication port of your PC. With the monitoring software installed, you can schedule
UPS shutdown/start-up and monitor its status through a PC.
The UPS is equipped with an intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400 card in the
UPS, it will provide advanced communication and monitoring options.
Note: The USB port and RS-232 port cannot be used at the same time.
CAUTION: For 1.5K model, to reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum
branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.
CAUTION: For 3K model, to reduce the risk of fire, connect only to a circuit provided with 30 amperes maximum
branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.
Rack-mount installation
The unit comes with mounting brackets for the standard 19-inch (46.5cm) rack.
CAUTION: Do NOT use the mounting brackets to lift the unit. The mounting brackets are only for securing the unit to the rack.
This UPS can be either placed on a desktop, mounted in a rack or installed in an upright position. Define the proper display orienta-
tion based on the configuration chosen to install this UPS.
Step 1
Remove the front panel.
Step 1
Tower installation
Allows the user to install the UPS in the upright position.
Step 2
Step 2
Connect the AC input and then
reconnect battery wires.
Step 3
Replace the front panel.
Step 1
Unfold and align the tower
support base.
Step 2
Place the UPS vertically on
the base.
Step 3
Verify that the UPS is stable and
firmly attached to the base.
•
Connect the network surge protection
Network/Fax/Phone port
The UPS has two network cable RJ45 connectors for network lines.
Keep pins 1 and 2 closed for UPS normal operation. To activate the EPO feature, remove the wire between pin 1 and 2.
Communication ports
USB port RS-232 port Intelligent slot
IN OUT
Closed for UPS normal
operation

Use the supplied CD or go to the website: http://www.forzaups.com/us/driver-downloads/.
After clicking the software icon, choose the required operation system.
Follow the on-screen instructions to install the software.
When you finished downloading all required files, enter the serial No (installation password): 5242-87f6-64re-di8d-986u to install
the software (include the hyphens).
In order to access as Administrator, input the password: 111296.
When your computer restarts, the management software will appear as a light blue round icon located in the system tray, near the
clock.
Note: For Mac and Linux users, please refer to the ForzaTracker user guide found in our website.
1.
2.
3.
4.
5.
6.
Step 1
Remove the front panel of the UPS.
Step 2
Disconnect the battery wires.
Step 3
Remove the two screws and proceed to
pull out the battery compartment.
Step 4
Remove the top cover of the
compartment and replace the
batteries.
Step 5
When done, replace the cover of the
battery compartment and screw it to the
unit chassis.
Step 6
Reconnect the battery wires.
Step 7
Replace the front panel of the UPS.
2.5 Turning on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial
charge period.
2-7 ForzaTracker monitoring software
ForzaTracker is a new generation of UPS monitoring software, which provides user-friendly interface to monitor and control your UPS
system. This unique software provides safe auto-shutdown for multi-computer systems during power failures. With this software, users
can monitor and control any UPS on the same LAN no matter how far they might be from the UPS.
2.6 Battery replacement (Service personnel only)
NOTICE: This UPS is equipped with internal batteries and only qualified service personnel shall be allowed to replace the batteries.
Note: Once the batteries are removed, the connected equipment is no longer protected from power outages.
CAUTION!! Make sure to follow all safety precautions and warnings during the replacement procedure.
3. Advanced operation
3-1. Description of buttons and functions
ON/MUTE SELECT OFF/ENTER
ON/Mute button
OFF/Enter button
Select button
Turn on the UPS: Press and hold the ON/Mute button for at least 2 seconds
to turn on the UPS.
Mute the alarm: When the UPS is on battery mode, press and hold this
button for at least 3 seconds to disable or enable the alarm system.
This command would not apply when warnings or errors occur.
Up key: Press this button to display previous selection in the UPS
configuration menu.
Switch to UPS self-test mode: Press and hold ON/Mute button for 3 seconds
to perform the self-test in AC mode, ECO mode, or converter mode.
Turn off the UPS: Press and hold this button for at least 2 seconds to turn
off the UPS in battery mode. The UPS will remain in standby mode under
normal power conditions or transfer to Bypass mode provided it has been
enabled previously by pressing this button.
Confirm selection key: Press this button to confirm the selection in the
UPS configuration menu.
Switch LCD message: Press this button to change the LCD message for
input voltage, input frequency, battery voltage, output voltage and output
frequency.
Setting mode: Press and hold this button for 3 seconds to enter the UPS
configuration menu while UPS is in standby or bypass mode.
Down key: Press this button to display the next selection in the UPS
configuration menu.
Button Function
Installation procedure for Windows users:

Battery mode
Low battery
Overload
Fault
Bypass mode
Sounds every 4 seconds
Sounds every second
Sounds every 0.5 second
Continuous sound
Sounds every 10 seconds
3-2. LCD panel
3-3. Audible alarm
ON/Mute +
Select button
Select + OFF/Enter
Button
Switch to bypass mode: When the utility power is normal, press ON/Mute
and Select buttons simultaneously for 3 seconds to transfer the UPS to
bypass mode. This action will be ineffective if the input voltage is not within
an acceptable range.
Button Function
Exit setting mode or return to the upper menu: When the UPS is on setting
mode, press the ON/Mute and Select buttons simultaneously for 0.2
seconds to return to the upper menu. If it is already in top menu, press
these two buttons at the same time to exit the setting mode
Rack or Tower display switch: Press the Select and OFF/Enter buttons
simultaneously for 3 seconds. The display changes from/to Rack to/from
Tower.
Rack display
Load info
Load info
Battery info
UPS status
Battery info
Warning and fault info/
Setting operation
Backup
time
info
Input/output
and Battery info
Warning & Fault info/
Setting operation
Backup time info
Input/output
and Battery info
UPS status
Tower display
Load information
UPS status
Battery information
Display Function
Backup time information
Overload indicator
Indicates the load or the UPS output is short circuited.
Indicates that the programmable management outlets are working.
The UPS is on and supplying utility power to the connected equipment.
Indicates that the UPS is working in converter mode.
Indicates the UPS is working in bypass mode.
Indicates the UPS is supplying power to the loads directly from the mains.
Indicates that the UPS alarm is disabled.
Indicates the battery charger is working.
Low battery level and low voltage indicator.
Battery fault indicator.
Battery level indicator at 0-24%, 25-49%, 50-74%, and
75-100% of its capacity.
BATTERY
25% 50% 75% 100%
Indicates input voltage, input frequency, battery voltage, output voltage
and output frequency. V: voltage, Hz: frecuency
Settings
Input/Output & Battery information
Load information
Display
Indicates the remaining backup time in pie chart.
Function
Backup time information
Fault information
Indicates the remaining backup time in numbers.
H: hour, M: minute.
Warns that an internal fault has been detected.
Indicates that configuration parameters are being set.
Load level indicator at 0-24%, 25-49%, 50-74%, and 75-100%
of its capacity
Warning and fault code indicators. The meaning of the codes is listed
in the section below.
INPUT BATT OUTPUT
V
Hz
25%
LOAD
50% 75% 100%

Interface Setting
For 200/208/220/230/240 VAC, you may choose any of the
following output voltages
200: the output voltage is 200VAC
208: the output voltage is 208VAC
220: the output voltage is 220VAC
230: the output voltage is 230VAC (Default)
240: the output voltage is 240VAC
For 100/110/150/120/127 VAC you may choose any of the
following output voltages
100: the output voltage is 100VAC
110: the output voltage is 110VAC
115: the output voltage is 115VAC
120: the output voltage is 120VAC (Default)
127: the output voltage is 127VAC
3-4. Abbreviations on the LCD display
3-5. UPS parameter settings
01: Output voltage settings
Enable
Disable
Escape
High loss
Low loss
ON
OK
Site fault
EPO
Over temperature
Charger failure
Frecuency is unstable in bypass mode
EEPROM error
Fan failure
Battery replacement
Abreviation Display content Meaning
HS
LS
ON
OK
sf
EE
FU
ch
ep
fA
Parameter 2
Parameter 1
Two parameters need to be configured in order to set up
the UPS. Refer to following diagram.
Parameter 1: it is used for the different configuration
options. Please refer to the table below.
Parameter 2: it represents the setting information or
values of each program.
02: Frequency Converter enable/disable
Interface Setting
Activates or cancels the converter mode.
CF ENA: Enable converter mode
CF DIS: Disable converter mode (Default)
03: Output frequency settings
Interface Setting
Use this menu to define the initial frequency on battery mode:
BAT 50: The output frequency is set to 50Hz
BAT 60: The output frequency is set to 60Hz
If the converter mode is enabled, the following options
will be available:
CF 50: The output frequency is set to 50Hz
CF 60: The output frequency is set to 60Hz
04: ECO enable/disable
Interface Setting
Activates or cancels the ECO mode.
ENA: the ECO mode is enabled
DIS: the ECO mode is disabled (Default)
05: AECO enable/disable
Interface Setting
Activates or cancels the advanced ECO mode.
ENA: the advanced ECO mode is enabled
DIS: the advanced ECO mode is disabled (Default)

06: ECO voltage range setting
07: Bypass enable/disable
Interface Setting
Use this menu to set the acceptable high voltage point and
low voltage point for ECO & AECO mode by pressing
Down key or Up key.
HS: High loss voltage in ECO & AECO modes.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
(Default: +12V)
For 100/110/115/120/127 VAC models, the setting range in
parameter 3 is from +3V to +12V of the nominal voltage.
(Default: +6V)
LS: Low loss voltage in ECO & AECO modes.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage.
(Default: -12V)
For 100/110/115/120/127 VAC models, the setting voltage
in parameter 3 is from -3V to -12V of the nominal voltage.
(Default: -6V)
08: Bypass voltage range setting
Interface Setting
Parameter 3:Use it to activate or cancel the Bypass mode.
ENA: Bypass enabled
DIS: Bypass disabled
Interface Setting
Parameter 2 & 3:Press the UP or Down key to choose the
acceptable high and low voltage values for Bypass operation
HS: High voltage adjustment in bypass mode
For 200/208/220/230/240 VAC:
230-264: High voltage setting ranges from 230VAC to 264VAC
as set in parameter 3. (Default: 264VAC)
LS: Low voltage adjustment in bypass mode
For 200/208/220/230/240 VAC:
170-220: Low voltage setting ranges from 170VAC to 220VAC
as set in parameter 3. (Default: 170VAC)

Interface Setting
DIS: Disables the runtime limit timer, in which case backup
time will depend on battery capacity. (Default)
Note: When setting this parameter to “0”, the backup time
will only last 10 seconds.
Use this setting to configure the backup time on battery
mode for general outlets.
0-999: Sets the backup time in minutes, from 0-999 for
general outlets on battery mode.
Interface Setting
HS: Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: Sets the frequency high loss point from 51Hz to
55HZ (Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz: Sets the frequency high loss point from 61Hz to
65Hz (Default: 63.0Hz)
LS: Bypass low frequency point
For 50Hz output frequency models:
45-49Hz: Sets the frequency low loss point from 45Hz to
49HZ (Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz: Sets the frequency low loss point from 55Hz to
59Hz (Default: 57.0Hz)
Use this menu to set the acceptable high frequency point
and acceptable low frequency point for Bypass mode by
pressing the Down key or Up key.
09: Bypass frequency range setting
11: Backup time setting for programmable outlets
Interface Setting
Parameter 3:Sets the backup time limits for the
programmable outlets.
0-999: Use this setting to define the programmable outlets
backup time in minutes, from 0-999, in order to connect
non-critical devices on battery mode. (Default:999)
10: Programmable outlets enable/disable
Interface Setting
Parameter 3:Activates or cancels the programmable
outlet feature.
ENA: Programmable outlets enabled
DIS: Programmable outlets disabled (Default)
Interface Setting
Use this setting to configure the charger current to be applied.
When the UPS is equipped with an additional charge, ther
available setting options are 2/3/4.
2/3/4: Sets the maximum charger current in 2/3/4 amperes.
Long-run models have settings of 1/2/4/6/8. available.
.1/2/4/6/8: Sets the maximum charger current in 1/2/4/6/8
amperes. (Default: 8A)
Interface
Use this setting to configure the boost voltage level.
225-240: Sets the charger boost voltage from 225 to
240 (unit: 0.01V/cell). (Default: 236)
12: Backup time setting for general outlets
13: Battery total Ah setting
14: Maximum charger current setting
15: Charger boost voltage setting
Interface Setting
Use this setting to configure the total battery capacity in
Ah for the UPS sytem.
7-999: Sets the battery total capacity from 7-999 in Ah.
Please set the correct battery total capacity if an external
battery bank is connected.

16: Charger float voltage setting
00: Exit setting
3-6. Operation mode description
Interface
Use this setting to determine the float voltage level.
220-233: Sets the charger float voltage from 220 to
233 (unit: 0.01V/cell). (Default:228)
Operation mode
Online mode
ECO mode
(Efficiency
Corrective
Optimizer)
Frequency
Converter mode
Battery mode
AECO mode
(Advanced
Efficiency
Corrective
Optimizer)
Description LCD display
Rack display Tower display
Bypass mode
Standby mode
Fault
When the input voltage is within acceptable range, the UPS
will supply pure and stable AC power to connected loads.
The UPS will also charge the battery in online mode.
Energy saving mode:
When the input voltage is within the voltage regulation range
(±3%V max), the UPS will bypass voltage to loads for
energy saving. PFC and INVERTER are still active in this
mode.
When the input voltage is within the voltage regulation range
(±3%V max), the UPS will bypass voltage to loads for
energy saving. PFC and INVERTER are disabled in this
mode.
When input frequency is between 40Hz and 70Hz, the UPS
can be set at a constant output frequency, of 50Hz or 60Hz.
The UPS will still charge the battery when operating in this
mode.
When the input voltage exceeds the acceptable range or
during a power failure, the UPS will start supplying power
from the battery while the alarm will beep every 5 seconds.
When input is within acceptable voltage range but the UPS
is overloaded, the UPS will transfer to bypass mode or it can
be manually changed to bypass mode using the front panel
controls. The alarm will sound once every 10 seconds in this
case.
The UPS is powered off and there is no power supplied to
the loads, but batteries can still be charged.
The UPS is in fault mode when it fails to provide output
power to the loads. The fault icon flashes on the LCD
display even though the UPS information is still being
displayed on the screen.

3-7. Fault codes 4. Troubleshooting guide
If the UPS system does not operate correctly, use the table below to troubleshoot the problem.
3-8. Warning indicators
Beeps once every 2 seconds
Beeps once every 2 seconds
Beeps once every 2 seconds
Beeps once every 2 seconds
Beeps once every 2 seconds
Beeps once every 2 seconds
Beeps once every 2 seconds
Beeps once every second
Beeps once every 2 seconds
Beeps once every 2 seconds
Beeps once every 2 seconds
EPO enable
Over temperature
Charger failure
Battery fault
Bypass out of range
Unstable bypass frequency
Low battery
Overload
Battery is not connected
Overcharge
Site wiring fault
Warning Icon (blinking) Code Alarm
EEPROM error
Fan failure
Battery replacement
Beeps once every 2 seconds
Beeps once every 2 seconds
Beeps once every 2 seconds
Even though the mains supply
is normal, there are no status
indicators or alarms.
The icon and the warning code
become illuminated on the
LCD display, and the alarm starts
beeping once every 2 seconds.
The and the icons become
illuminated on the LCD display,
and the alarm starts beeping once
every 2 seconds.
The and icons become
illuminated on the LCD display
and the alarm starts beeping
once every 2 seconds.
Fault code 27 and the
become illuminated on the LCD
display, and the alarm starts
beeping continuously.
The and icons
become illuminated on the LCD
display, and the alarm starts
beeping every second.
Fault code 43 becomes illuminated
along with the icon on
the LCD display, and the alarm
starts beeping continuously
The AC input is connected
to the UPS outlet.
The AC input cable is not
properly connected.
Line and neutral
conductors of UPS input
are reversed.
The external or internal
battery connection
is incorrect.
Battery voltage is too low
or the charger fails
UPS is overloaded
UPS is overloaded.
Devices connected to the
UPS are fed directly from
utility power via the Bypass
After repetitive overloads,
the UPS is locked in
Bypass mode. Connected
devices are fed directly
from utility power.
The UPS shuts down
automatically upon
detecting the overload
condition in the output
Battery voltage is too high
or the charger is fault
Rotate mains power socket by 180°
and then connect to UPS system
Check if all batteries are
properly connected.
Contact your dealer or service center
Please contact the dealer
or service center
Remove excess loads from the
UPS output
Remove excess loads from UPS output
Remove excess loads from the UPS
output first. Shut down the UPS
completely before restarting the unit
once again
Remove excess loads from the UPS
output and restart the unit once again
EPO function is enabled
Check to make sure the power cord is
firmly connected to a AC wall socket
Set the circuit in its closed position
to disable the EPO function
Plug the power cord to a wall socket.
Symptom Possible cause Remedy
Fault code 28 and the
icon become illuminated on the
LCD display and the alarm starts
beeping continuously.
Fault event Fault
code Fault
code IconFault event
01
02
03
11
12
13
14
27
28
41
43
45
Inverter output is short circuited
Battery voltage too high
Battery voltage too low
Excessive temperature
Overload
Charger failure
Bus start failure
Bus over
Bus under
Inverter soft start failure
High inverter voltage
Low inverter voltage

MPN
General
Input
Output
Battery
Alarms/Indicators
Physical appearance
Additional information
Capacity
FDC-1502R
1500VA/1350W
Double conversion
200-240VAC
40Hz-70Hz
NEMA 5-15P
220VAC
47Hz-53Hz or 57Hz-63Hz
>90%
Pure Sine Wave
4 NEMA 5-15R
0ms
0.9
4ms4ms
Included
12V/9 Ah (3)
4 min at full load
4 hours to 90% capacity
RS-232, USB
42.1lb
6.0ft
Battery mode: Sounds
every 4 seconds
Low battery: sounds every
second
Overload: Sounds
every 0.5 second
Fault: Continuous sound
Graphical LCD with blue
backlight
ForzaTracker
or optional SNMP card
15x17.3x3.5in
Two years for UPS,
One year for battery
50Hz±0.25Hz or 60Hz±0.3Hz
L-N: 624J
L-G: 420J
N-G: 420J
FDC-3002R
6.0ft
23.6x17.3x3.5in
66.4lb
Two years for UPS,
One year for battery
3000VA/2700W
Double conversion
200-240VAC
40Hz-70Hz
L-N: 624J
L-G: 420J
N-G: 420J
NEMA 5-15P
220VAC
47Hz-53Hz or 57Hz-63Hz
>91%
Pure Sine Wave
6 NEMA 5-20R
0ms
0.9
Included
12V/9 Ah (6)
4.5 min at full load
4 hours to 90% capacity
RS-232, USB
Battery mode: Sounds
every 4 seconds
Low battery: sounds every
second
Overload: Sounds
every 0.5 second
Fault: Continuous sound
Graphical LCD with blue
backlight
ForzaTracker
or optional SNMP card
50Hz±0.25Hz or 60Hz±0.3Hz
Topology
Nominal voltage
Frequency
Joules
AC plug style
Nominal voltage
Frequency (synchronized)
Frequency (battery)
Efficiency (AC mode)
Waveform
Total outles
Battery type and quantity
Backup time
Recharge time
Visual indicators
Audible
Cord length
Dimensions
Weight
Warranty
Communication ports
USB management
Transfer time (line to battery)
Transfer time (inverter to bypass)
Power factor
Yes YesModem/phone/network
surge protection
Power management
software
6. Specifications
5. Storage and maintenance
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has
been exceeded, the batteries must be replaced. In this case, please contact your dealer or service center.
Storage
Charge the UPS for at least 5 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location. During
storage, recharge the battery in accordance with the following table:
Fault code 14 becomes illuminated
and the alarm starts beeping
continuously.
Fault codes 01, 02, 03, 11, 12, 13
and 41 become illuminated on the
LCD display, and the alarm starts
beeping continuously.
Fault code is shown as 45 on LCD
display. At the same time, the alarm
starts beeping continuously.
Battery backup time is shorter
than its nominal value.
The UPS shuts down
automatically upon
detecting the overload
condition in the output.
Defective batteries
Batteries are not fully
charged.
Charge the batteries for at least
5 hours and then check their
capacity. If the problem persists,
consult your dealer.
Contact your dealer for
a replacement
A UPS internal fault has
occurred. There are two
possible causes:
1. Power is continued to
be supplied to the load,
but is done directly from
the AC grid via a bypass.
2. Power is no longer
supplied to the load
Check the output wiring and
if connected devices are
short-circuited.
Please contact the dealer or
service center.
Symptom Possible cause Remedy
There is no output
voltage from the charger
and the battery voltage is
below 10V/PC.
Please contact the dealer or
service center.
Batteries must not be discarded as regular household waste! As part of the
company’s eco-friendly approach, we encourage you to follow all applicable local
waste regulations to dispose of your used devices and batteries properly.
Storage temperature Recharge frequency Runtime
-25°C - 40°C
-40°C - 45°C
Every 3 months
Every 2 months
1-2 hours
1-2 hours
This manual suits for next models
1
Table of contents
Other Forza UPS manuals

Forza
Forza FX-1500LCD User manual

Forza
Forza FDC-1002T-C User manual

Forza
Forza FIO-P11K12 User manual

Forza
Forza Atlas 2-3KVA User manual

Forza
Forza HT-752LCD-A User manual

Forza
Forza Elipse Series User manual

Forza
Forza SL-802UL-A User manual

Forza
Forza FDC-106K User manual

Forza
Forza FDC-2012R-I User manual

Forza
Forza HT-650LCD User manual

Forza
Forza HT-752LCD-C User manual

Forza
Forza SL-1501UL User manual

Forza
Forza FDC-1000T User manual

Forza
Forza HT-750LCD User manual

Forza
Forza FDC-106KMR-ISO User manual

Forza
Forza FDC-1002T-A User manual

Forza
Forza DC-140USB User manual

Forza
Forza XG-1201LCD User manual

Forza
Forza FDC-1001RUL User manual

Forza
Forza FDC-1002T User manual