
5
E33 FPI Direct Vent Gas Insert
IMPORTANT:
SAVE THESE
INSTRUCTIONS
The FPI Gas Fireplace must be installed in
accordance with these instructions. Carefully
read all the instructions in this manual first.
Consult the building authority having jurisdic-
tion to determine the need for a permit prior to
starting the installation.
NOTE: Failure to follow the instructions could
cause a malfunction of the heater which could
result in death, serious bodily injury, and/or
property damage. Failure to follow these
instructions may also void your fire insurance
and/or warranty.
FOR YOUR SAFETY
This appliance requires air for proper combus-
tion. Always provide adequate combustion and
ventilation air. Follow instructions and informa-
tion in CSA B149.1 (in Canada) or the National
Fuel Gas CodeANS Z223.1/NFPA (in the USA),
regarding requirements for combustion and
ventilation air.
GAS PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than
1/2 psig. (3.45 kPa).
SPECIFICATIONS
At pressures over 1/2 psig, the pipe to the unit
must be disconnected.
Gas Input Capacity:
Natural Gas 38,000 Btu/h
Propane 35,500 Btu/h
Min. Input:
Natural Gas 20,000 Btu/h
Propane 19,000 Btu/h
Fuels: Approved for use with both natural gas,
and propane. Approved as is for use at 0' to
4,500' (0-1370m).
Electrical: 120V A.C. system.
Circulation Fan: Variable speed, 127 CFM.
Log Set: Ceramic fibre, 8 per set.
Vent System: 3" co-linear aluminum flex.
INSTALLATION
INSTALLATION INTO A
SOLID FUEL BURNING
FIREPLACE OR
FACTORY BUILT
FIREPLACE
The E33 Gas Inserts have been tested and ap-
proved to be vented into any masonry fireplace
or approved solid fuel burning factory built
fireplace that will allow the insert to physically
fit into the firebox. Refer to page 6 for minimum
fireplace clearances.
If the factory built fireplace* height is too low
for your Insert, you may remove the smoke
baffle plate and damper from the factory
built fireplace as long as these items are
saved and are reinstalled in the event that
the Insert is removed. NOTE:Any alterations
made to the listed solid fuel burning factory
built fireplace may void the listing of the
fireplace. Cutting any sheet-metal parts of
the fireplace, in which the gas fireplace insert
is to be installed, is prohibited.
If the factory-built fireplace has no gas ac-
cess hole(s) provided, an access hole of
1.5" (37.5mm) or less may be drilled through
the lower sides or bottom of the firebox in
a proper workmanship like manner. This
access hole must be plugged with non-com-
bustible insulation after the gas supply line
has been installed.
The fireplace and fireplace chimney must be
clean and in good working order and con-
structed of non-combustible materials and
chimney cleanouts must fit properly. Refrac-
tory, glass doors, screen rails, screen mesh,
and log grates can be removed from the
fireplace before installing the gas fireplace
insert. Smoke shelves, shields and baffles
may be removed if attached by mechani-
cal fasteners. A tight connection between
the gas fireplace insert flue collar and the
fireplace chimney must be made.
*Check with your local inspector before com-
mencing with this installation.
BEFORE YOU START
Safe installation and operation of this appliance
requires common sense, however, we are
required by the Canadian Safety Standards
and ANSI Standards to make you aware of
the following:
General Safety Information
1) The appliance installation must conform
with local codes or in the absence of local
codes, with CAN/CSAB149.1 (in Canada)
or the National Fuel Gas CodeANSI Z223.1
NFPA54 in the U.S.A. This appliance should
be installed by a qualified gas fitter technician
only.
2) Installation and repair should be done
by a qualified service person.
3) The appliance should be inspected
before use and at least annually by a
professional service person. More fre-
quent cleaning may be required due to
excessive lint from carpeting, bedding
material, animal hair, etc. It is impera-
tive that control compartments, burners
and circulating air passageways of the
appliance be kept clean.
4) See general construction and assembly
instructions. This appliance may only be
installed in a vented, noncombustible fire-
place.
5) This appliance is Listed for bedroom instal-
lations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6) Always connect this appliance to a vent
system vent that is run (or routed) to the
outside of the building envelope. Never vent
to another room or inside a building. Make
sure that the vent is properly sized and is
of adequate height to provide the proper
draft.
7) Inspect the venting system annually for
blockage and any signs of deterioration.
8) Any glass removed for servicing must be
replaced prior to operating the appliance.
9) WARNING: Failure to position the parts
in accordance with the diagrams in this
manual or failure to use only parts specifi-
cally approved with this appliance may
result in property damage or personal
injury.
10) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fireplace.