Frico FC Series User manual

Control system FC
.... 6
SE .... 13
NO
Original instructions
Standalone level - FC111, FC113
.... 20
GB

FC111/113
2
FC111
230V~
400V2~
L2 L2 PE PE LIN LOUT
NN
A1 A2 B1 B2
GND
GND
GND
0-10V
OUT
GND
GND
HI
HI
LO
LO
+12V
+12V
BUS 1 BUS 2
230V~
G12
GND
HI
LO
+12V
BUS 1 BUS 2
GND
HI
LO
+12V
FCPOBH
Sensor
FCCH
G12
Sensor
Max 16A
Sensor
FCBB
FCRTX
FCOTX
L2 L2 PE PE LIN LOUT
NN
A1 A2 B1 B2
GND
GND
GND
0-10V
OUT
GND
GND
HI
HI
LO
LO
+12V
+12V
BUS 1 BUS 2
400V2N~
G12
GND
HI
LO
+12V
BUS 1 BUS 2
GND
HI
LO
+12V
FCPOBH
Sensor
FCCH
G12
Sensor
Max 16A
Sensor
FCBB
FCRTX
FCOTX

FC111/113
3
FC113
GND
GND
HI
HI
LO
LO
+12V
+12V
BUS 1 BUS 2
GND
GND
HI
HI
LO
LO
+12V
+12V
BUS 1 BUS 2
GND
GND
HI
HI
LO
LO
+12V
+12V
BUS 1BUS 2
400V3~
FC111/113 - FCPOBH/FCPOB3H
A1 A2 B1 B2
GND
GND
GND
0-10V
OUT
GND
GND
HI
HI
LO
LO
+12V
+12V
BUS 1 BUS 2
G12
GND
HI
LO
+12V
BUS 1 BUS 2
GND
HI
LO
+12V
FCPOB3H
Sensor
FCCH
G12
Sensor
Sensor
FCBB
FCRTX
FCOTX
NNUVWL1L3 L2
400V 3N~
PE PE
Max 3x13A
För att minska risken för störningar ska kommunikationsbussen vara terminerad (avslutad) i
vardera änden dvs. i de enheter som sitter i början respektive i slutet av bussen. Vid leverans
är alla bussar förterminerade med ett 120 Ohms motstånd mellan HI and LO på BUS2. Vid
vidarekoppling tas motståndet bort.
Som alternativ till resistans kan termineringsswitchen på kortet sättas i läge ”ON”.
SE
NO
GB
To reduce the risk of interference, the communication BUS should be terminated at each end, i.e. in
the units that are located at the start and at the end of the BUS respectively. On delivery, all buses
are pre-connected with a 120 Ohm resistor between terminals HI and LO on BUS2. When making
further connections, remove the resistor.
As an alternative to resistance, the termination switch on the board can be set to the "ON" position.
For å redusere faren for forstyrrelser skal kommunikasjonsbussen være terminert (avsluttet) i
hver ende, dvs. i de enhetene som er plassert i begynnelsen henholdsvis i slutten av bussen. Ved
levering er alle busser på forhånd terminert med en motstand på 120 Ohm mellom HI og LO på
BUS2. Ved viderekobling fjernes motstanden.
Som alternativ til resistans kan termineringssvitsjen på kortet settes i stillingen ”ON”.

FC111/113
4
FC111, FC113
FCCH FCPOBH
FCPOB3H
FCB05
FC111 / FC113
Ty p Ingår i Beskrivning HxBxD
[mm]
FCCH FC111/FC113 Kontrollpanel, IP44 89x89x26
FCPOBH F C 111 Styrenhet, 16A, 230V~/400V2~, IP44 105x105x38
FCPOB3H FC113 Styrenhet, 3x13A, 400V3~, IP44 149x149x43
FCBC05 FC111/FC113 Kommunikationskabel, 5 m L: 5 m
Ingående komponenter
SE
Type Inngår i Beskrivelse HxBxD
[mm]
FCCH FC111/FC113 Kontrollpanel, IP44 89x89x26
FCPOBH F C 111 Styreenhet, 16A, 230V~/400V2~, IP44 105x105x38
FCPOB3H FC113 Styreenhet, 3x13A, 400V3~, IP44 149x149x43
FCBC05 FC111/FC113 Kommunikasjonskabel, 5 m L: 5 m
Inngående komponenter
NO
Type Included in Description HxWxD
[mm]
FCCH FC111/FC113 Control panel, IP44 89x89x26
FCPOBH F C 111 Control box, 16A, 230V~/400V2~, IP44 105x105x38
FCPOB3H FC113 Control box, 3x13A, 400V3~, IP44 149x149x43
FCBC05 FC111/FC113 Communication cable, 5 m L: 5 m
Components included
GB

FC111/113
5
FCBC05/10/25
FCSC10/25
FCPOBH / FCPOB3H
FCBC10
FCBB FCRTX FCOTX
FCSC10 FCSC10 FCSC10
Ty p Beskrivning HxBxD
[mm]
FCPOBH Styrenhet för systemutbyggnad, 16A, 230V~/400V2~, FC111, IP44 105x105x38
FCPOB3H Styrenhet för systemutbyggnad, 3x13A, 400V3~, FC113, IP44 149x149x43
FCBB Svartkroppsgivare, IP44 89x89x43
FCRTX Extern rumstemperaturgivare, IP20 39x39x23
FCOTX Utetemperaturgivare, IP44 39x39x23
FCBC05 Extra kommunikationskabel, 5 m L: 5 m
FCBC10 Extra kommunikationskabel, 10 m L: 10 m
FCBC25 Extra kommunikationskabel, 25 m L: 25 m
FCSC10 Extra givarkabel, 10 m L: 10 m
FCSC25 Extra givarkabel, 25 m L: 25 m
Tillval
SE
Type Beskrivelse HxBxD
[mm]
FCPOBH Styreenhet for systemutbygging, 16A, 230V~/400V2~, FC111, IP44 105x105x38
FCPOB3H Styreenhet for systemutbygging, 3x13A, 400V3~, FC113, IP44 149x149x43
FCBB Black bulb sensor, IP44 89x89x43
FCRTX Ekstern romtemperaturføler, IP20 39x39x23
FCOTX Utetemperaturføler, IP44 39x39x23
FCBC05 Ekstra kommunikasjonskabel, 5 m L: 5 m
FCBC10 Ekstra kommunikasjonskabel, 10 m L: 10 m
FCBC25 Ekstra kommunikasjonskabel, 25 m L: 25 m
FCSC10 Ekstra giverkabel, 10 m L: 10 m
FCSC25 Ekstra giverkabel, 25 m L: 25 m
Ekstrautstyr
NO
Type Description HxWxD
[mm]
FCPOBH Control box for system extension, 16A, 230V~/400V2~, FC111, IP44 105x105x38
FCPOB3H Control box for system extension, 3x13A, 400V3~, FC113, IP44 149x149x43
FCBB Black bulb sensor, IP44 89x89x43
FCRTX External room temperature sensor, IP20 39x39x23
FCOTX Outdoor temperature sensor, IP44 39x39x23
FCBC05 Extra communication cable, 5 m L: 5 m
FCBC10 Extra communication cable, 10 m L: 10 m
FCBC25 Extra communication cable, 25 m L: 25 m
FCSC10 Extra sensor cable, 10 m L: 10 m
FCSC25 Extra sensor cable, 25 m L: 25 m
Options
GB

FC111/113
20
GB
Start up
1.Check that all components and accessories are
enclosed.
2.Assemble and connect system, consult wiring
diagrams.
3.Power-up the system.
4.The system automatically identifies all components,
even when they are added at a later stage.
System solution
A system consists of a control panel, FCCH, as well as an
optional number of control units, FCPOBH/FCPOB3H (1-63
units), sensors and heaters. The set-point temperature for
the system is selected on the control panel.
In the system, groups are created that comprise one
FCPOBH/FCPOB3H, sensor and heater. At most, each group
can consist of one or more heaters with a total rated current
of 16A (FCPOBH) or 3 x 13A (FCPOB3H).
The control panel houses a built-in temperature sensor
which can be used, alternatively the groups which are fitted
with external room temperature sensors have better sensor
positioning for local temperature control per group.
Black bulb sensor
With black bulb sensors, the operative temperature is
measured and the control adapted to suit radiant heaters.
When the black bulb sensors are connected (accessory
FCBB), the system will automatically detect this and the
room value will be recorded from the black bulb sensor.
Heating blocked dependent on outdoor temperature
With outdoor temperature sensors (accessory FCOTX),
heating is automatically blocked when the outdoor
temperature exceeds 15 °C. This function can be
deactivated, see Settings.
C. System with several groups of external
room sensors in each group
External room temperature sensors
control each group.
D. System with several groups, of which,
at least two groups have external room
sensors and at least one group does not
have an external room sensor
External room temperature sensors control
each group.
Group/groups without sensors are controlled
by the control panel's temperature sensor.
B. System with one external room sensor
One external room temperature sensor in
the system controls all groups.
A. System without external room sensors
The control panel's temperature sensor is
controlling.

3
4
FC111/113
21
GB
Overview
Control panel
Keypad
1 Increase
2 Decrease
3 Menu / OK / Confirm
4 Timer
5 Cancel / Back
4 and 5 appear on the first press of menu
button.
Screen
6 Current room temperature (standby mode) /
Set point temperature (active mode)
Indicators
7 Operating mode
8 Status
5
1
2
6
8
7
+
Press and hold (2 sec) Quick command
Display lock on/off
Display lock
Colour (LED) Status
White
OFF
Red flashing
Purple
Indicator Status (right-hand LED)
Heat on
Heat off
Alarm
Heating blocking
Colour (LED) Operating mode
Indicator Operating Mode (left-hand LED)
During start-up, the text Inlt appears on
screen, then the current room temperature is
displayed.
When the screen is in standby mode, the light
intensity is reduced. Pressing any button will
simply display the set point temperature.
The FC111/113 is delivered with preset values.
The preset set point temperature is 21 °C
and can be easily adjusted using the up/down
arrows. The FC111/113 can also be adjusted to
your own requirements, consult the following
pages.
Normal mode
Comfort mode
Comfort mode - temporary
Reduced (night mode)
Reduced (night mode) - temporary
Timer
OFF
White
White flashing
Green
Green flashing
Yellow

FC111/113
22
GB
User menu
Press and hold for 2 seconds.
Browse between the menu options.
Confirm
Home screen
See the table on the following page for the choices
which are possible.
Timer
The set point temperature can be changed for
a limited period using the timer (15 minutes
to 45 days).
15 minutes - 45 days (’ minute, h hour, d day)
Set the desired time.
Set the desired room temperature (set
point temperature).
Confirm
Press to activate keypad.
Press to start timer at the preset values
(1 h, 24 °C) or the most recently used
values).
Confirm
Press and hold for 2 seconds.
Or to adjust the time and temperature values:
While the timer is counting down, the
screen alternates between displaying
the time remaining and the set point
temperature. The current temperature is
not shown in the timer mode.
When time is up the unit returns to previous
settings.

dAtE -
tHi 21 °C
tLo 18 °C
Prog
HEAt
AL A -
AL H -
OFF -
SEt -
CLr -
FC111/113
23
GB
Display alarm history.
Switch off the system. To switch off the system, select
(OFF) using OK. Wait 10 sec.
The system is then switched on
by pressing OK and selecting
(On) with up/down arrow and
confirming with OK.
Description
Default
settings
FunctionsMenu
options
For week program.
Set the following:
- year
- month
- day
- time (00:00)
For week program. Set the desired room
temperature (set point temperature) for
comfort mode.
For week program. Set the desired room
temperature (set point temperature) for
reduced mode.
Weekly program, see separate section.
Increase/decrease with up/down
arrow. Confirm each step with
OK.
Increase/decrease with up/down
arrow. Confirm with OK.
Increase/decrease with up/down
arrow. Confirm with OK.
Switch between (OFF) and P1-P9
with up/down arrow. Confirm
with OK.
(off)
(function
not activa-
ted)
Switch heating on/off. Switch between (On) and (OFF)
with up/down arrow. Confirm
with OK.
On (on)
Display active alarm. Switch between alarms with up/
down arrow.To see the serial
number for an alarm, press OK.
If no alarm: no A.
Switch between alarms with up/
down arrow.To see the serial
number for an alarm, press OK.
If no alarm: no A.
Factory reset. Resets values to factory set-
tings.
Press OK. Select (YES), by keep-
ing OK depressed for 2 seconds
(countdown).
Change settings, see separate section Set-
tings.
User menu

*
P0, P1 05:30 - 08
17 - 22
07 - 23
P2 06:30 - 10
19 - 23:30
07:30 - 23:30
P3 06 - 09
16 - 23
07 - 23
P4 06 - 22
P5 17 - 23
07 - 23
P6 06 - 18
P7 09 - 21
P8 09 - 22
09 - 20
P9 09 - 18
09 - 14
FC111/113
24
GB
Week program
The FC has nine preset weekly programs (P0/
P1-P9).
To activate weekly program, the following must be
set in the user menu:
- Date (dAtE)
-Temperature, comfort mode (tHi)
-Temperature, reduced mode (tLo)
The adaptive start function allows the control
to learn when it needs to start in order to
attain a given set point temperature at a given
time of the day in the environment in which
it is used. This function can be deactivated
(see Settings menu).
Preset programs
Mon-Fri:
Sat-Sun:
Residence
Description Comfort mode
*) Other times: Reduced (night mode)
Residence,
late
Residence,
short
Shop, late
Shop
Weekend
Residence,
day only
Office
Office, late
Mon-Sun:
Mon-Fri:
Mon-Fri:
Mon-Fri:
Sat-Sun:
Fri:
Sat-Sun:
Mon-Fri:
Sat-Sun:
Mon-Fri:
Sat-Sun:
Mon-Fri:
Sat-Sun:
Select P0/P1-P9.
Confirm to start the program.
Weekly program is selected and activated in User
Menu:
Setting week programs
Selection of preset program P0/P1 - P9
Temporarily override the weekly program
It is easy to temporarily disregard the set point
temperature which is preset in the weekly program.
Set the desired temporary set point
temperature.
Confirm
The temporary set point temperature will apply until
the next program step.
Power failure
Note! A power loss longer than 7 days may
require an adjustment of time and date.
The week program is affected if the clock is
not correctly set.
Press and hold for 2 seconds.
Browse to Prog.
Confirm

#
547
360
359
374
376 150 (15.0 °C) -200 - +400 (-20.0 - +40.0 °C)
438
FC111/113
25
GB
Settings
Settings are changed in User Menu:
Press and hold for 2 seconds.
Browse to SEt.
Confirm
Enter password using up/down arrows, confirm
each digit with OK. Password: 1932.
Enter the number for the setting that will be
changed using up/down arrows, confirm each digit
with OK. See table.
Select desired value according to table.
Confirm
Settings
Functions Default settings
Adaptive start
Airing mode*
Airing mode*, block-
ing time
Heating blocking
Heating blocking,
Temperature
Daylight saving/sum-
mer time and winter
time.
Description
1 (function activated) 0 (function not activated) / 1 (function activated)
See weekly program.
1 (function activated) 0 (function not activated) / 1 (function activated)
900 sec 300 - 6000 sec
1 (function activated) 0 (function not activated) / 1 (function activated)
Heating blocking, which requires outdoor sen-
sor (accessory FCOTX).
1 (function activated) 0 (function not activated) / 1 (function activated)
Automatic time change-over.
Heating blocking, which requires outdoor sen-
sor (accessory FCOTX).
*Airing mode, which saves energy, e.g. when windows are open. With the preset values: Should there be
a sudden drop in temperature, e.g. when opening a window, the set point temperature is lowered to 10 °C
for 900 sec (15 min). If the temperature does not drop any further after this, the control will return to the
previous setting.
Ensure that the product still satisfies Ecodesign Regulation's requirements when functions are
deactivated.

A 5
A 8
A 12
A 14
A 7
A 9
A 10
A 11
A 13
FC111/113
26
GB
Trouble shooting
Contact lost with control panel or
control unit • If the component is removed
intentionally, the alarm must be reset
manually. See below.
• Check the connections.
• The alarm resets automatically, if the
component is detected again.
• If the alarm persists after resetting,
contact Frico.
• Check the connections.
• If the alarm persists after resetting,
contact Frico.
Contact lost with external room temperature
sensor
Contact lost with outdoor temperature sensor
Contact lost with black bulb sensor
External room temperature sensor fault
Fault on the control panel's temperature
sensor
Incorrect sensor connection
Outdoor temperature sensor fault
Black bulb sensor fault
Error code ActionCause
When error codes are displayed, the system continues to
operate with the components that are functioning. If all
room temperature sensors, including the temperature sensor
in the control panel, have lost contact, the system will run at
25% heat output.
If the problems continue, please contact Frico for support.
Reset alarm
To reset manually, press X for 2 seconds where the serial
number for an alarm is displayed (see User Menu). The
majority of the alarms reset automatically, once the problem
is corrected.


Art.no 157809, 2019-04-03, HH/CH
Main office
Frico AB Tel: +46 31 336 86 00
Industrivägen 41
Sweden www.frico.net
For latest updated information and information
about your local contact: www.frico.net.
This manual suits for next models
3
Table of contents
Other Frico Control System manuals
Popular Control System manuals by other brands

Vicon
Vicon NOVA V1400 installation manual

TELECO AUTOMATION
TELECO AUTOMATION TVRPS868E01 Installer instruction manual

Aritech
Aritech RF-4041-07-2 Installation sheet

Stagnoli
Stagnoli E24 manual

HandyTrac
HandyTrac Key Control System installation & operating manual

oventrop
oventrop Regumat F-130 Installation and operating instructions