SIRe Advanced Fan Heater Electric
38
GB
Alarm and error codes
SIRe has different alarms and error codes for
safe and problem free operation.
If alarms or error codes have been indicated
these must be reset in order to return to
normal operation, for example activating the
heating again. Fan mode is active even when,
for example, the over heating alarm has been
indicated.
Displaying alarm and error codes
In event of alarm or error the alarm/error
code is shown in the status window. In event
of alarm/error code the unit it applies to is
displayed.
See Table - Alarms and Table – Error codes.
Reset alarm
Note! Before resetting, check that the fault is
rectified and there is nothing to prevent the
unit from being recommissioned!
When the fault is rectified, the alarm is
reset by pressing the forward arrow and selec-
ting Reset alarm and then confirm. If several
units give an alarm at the same time, the fact
that there are several alarms is indicated, but
only one is shown in the display. By resetting
that alarm the next alarm can be read.
At the first start up alarm and error codes
can occur, these can usually be reset without
action.
Power failure
Note that in case of power failure the time
settings need to be checked, if the time is not
set correctly week program will be affected.
Overheat protection
SE06-15:
The over heating protection is intended to
restrict the exhaust temperature to 70 °C.
At 70 °C an output step is tripped off. If the
temperature continues to rise all output
is interrupted at 75 °C. If the temperature
continues to rise despite this, for example
because of a faulty contactor, the fan will
start to spin at 70 °C to keep the temperature
down. At the same time there is an over
heating alarm, see Table - Alarm. At internal
temperatures of +80 °C the fan runs at
maximum speed.
If the unit cools the output is engaged again.
The alarm remains in the control unit’s dis-
play. If the unit overheats twice within an
hour, the alarm must be reset before the hea-
ting can be engaged again, the fan operates
until the alarm is reset.
SE20-30:
The over heating protection is intended to
restrict the exhaust temperature to 85 °C.
At 85 °C an output step is tripped off. If the
temperature continues to rise all output
is interrupted at 90 °C. If the temperature
continues to rise despite this, for example
because of a faulty contactor, the fan will
start to spin at 85 °C to keep the temperature
down. At the same time there is an over
heating alarm, see Table - Alarm. At internal
temperatures of 95 °C the fan runs at
maximum speed.
If the unit cools the output is engaged again.
The alarm remains in the control unit’s dis-
play. If the unit overheats twice within an
hour, the alarm must be reset before the hea-
ting can be engaged again, the fan operates
until the alarm is reset.
Note! In event of repeated alarms and over
heating alarms, carry out a thorough check
and if the fault cause cannot be found contact
authorised service personnel or Frico.