
Installation
Checklist for
installation
For information about installation, please refer to the sections stated below
1Switch off the power supply before establishing a mains connection
2Mount the Fronius Smart Meter (see "Installation" on page 8)
3Connect automatic circuit breakers or automatic circuit breakers and disconnectors
(see"Protective circuit" on page 8)
4Connect the mains cable to the Fronius Smart Meter (see "Cabling" on page 8)
5Connect the output terminals of the Fronius Smart Meter to the Fronius system mon-
itoring using a suitable cable (see "Connecting the data communication cable to
the inverter" on page 9)
6If necessary, set terminating resistors (see "Terminating resistors" on page 10)
7Tug on each wire and plug to make sure that they are securely connected to the ter-
minal blocks.
8Switch on the power supply to the Fronius Smart Meter
9Check the firmware version of the Fronius system monitoring. To ensure compatibil-
ity between the inverter and Fronius Smart Meter, the software must always be kept
up-to-date. The update can be started via the inverter website or via Solar.web.
10 If several Fronius Smart Meters are installed in the system, set the address (see
"Setting the address" under "Setting the address of the Fronius Smart Meter" on
page 13)
11 Set the meter location via the Fronius system monitoring web interface under "Set-
tings - Meter - Settings" (see "Configuring the web interface" on page 14)
Installation The Fronius Smart Meter can be mounted on a 35 mm DIN rail. The housing comprises
4 DUs (division units, max. 72 mm).
Protective circuit The Fronius Smart Meter is a hard-wired device and requires a disconnecting device (cir-
cuit breaker, switch or disconnector) and overcurrent protection (automatic circuit
breaker).
The Fronius Smart Meter consumes 10 - 30 mA. The nominal capacity of the disconnect-
ing devices and the overcurrent protection is determined by the wire thickness, the mains
voltage and the required breaking capacity.
- Disconnecting devices must be mounted within sight and as close as possible to the
Fronius Smart Meter; they must also be easy to use.
- The disconnecting devices must satisfy the requirements of IEC 60947-1 and IEC
60947-3, as well as all national and local regulations for electrical systems.
- Use overcurrent protection rated for max. 63 A.
- To monitor more than one mains voltage, use connected automatic circuit breakers.
- The overcurrent protection must protect the mains terminals marked L1, L2 and L3.
In rare cases, the neutral conductor has an overcurrent protection which must simul-
taneously interrupt neutral and unearthed lines.
Cabling IMPORTANT!
Always switch off the power supply before connecting the mains voltage lines to the
Fronius Smart Meter.
8