Future Design FDC-9090 User manual

User's ManualUser's Manual
FDC-9090
Self-Tune Fuzzy / PID
Process / Temperature Controller
FDC-9090
Self-Tune Fuzzy /PID
Process /Temperature Controller

Warning SymbolWarning Symbol
Use the ManualUse the Manual
This Symbol calls attention to an operating procedure, practice, or
the like, which, if not correctly performed or adhered to, could result
in personal injury or damage to or destruction of part or all of the
product and system. Do NOT proceed beyond a warning symbol
until the indicated conditions are fully understood and met.
Specifications
Wiring
Programming
Page 3
Page 4
Page 5
NOTE:
It is strongly recommended that a process should
incorporate a LIMIT like L91 which will shut down the
equipment at a preset process condition in order
to preclude possible damage to products or
system.
It is strongly recommended that aprocess should
incorporate aLIMIT like L91 which will shut down the
equipment at apreset process condition in order
to preclude possible damage to products or
system.
Copyright a August 2001, Future Design Controls, all rights
reserved. No part of this publication may be reproduced,
transmitted, transcribed or stored in a retrieval system, or
translated into any language in any form by any means without
the written permission of Future Design Controls.
UM9090Rev1
2

UM9090Rev1
type J, K, T, E, B, R, S, N.
PT100 ohm RTD (DIN 43760/BS1904 or JIS)
-10 to 60 mV, configurable input attenuation
User configurable, refer to Table above
Refer to Table above
0.1 C/ C ambient typical
Protection mode configurable
100 ohms max.
60 dB
120dB
3 times / second
BB
The Fuzzy Logic is an essential feature of this versatile
controller. Although PID control has been widely accepted by
industries, it is difficult for PID control to work with some sophistic
systems efficiently, for example, systems of second order, long
time-lag, various set points, various loads, etc. Because of
disadvantage of controlling principles and fixed values of PID
control, it is inefficient to control the systems with many
variables and the result is unacceptable control for some
systems. The Fuzzy Logic control can overcome the
disadvantage of PID control only. It controls the system in a
efficient way by experiences it had before. The function of Fuzzy
Logic is to adjust the PID values indirectly in order to making the
manipulation output value MV adjusts automatically and quickly
to adapt to various processes. It enables a process to reach its
set point in the shortest time with minimum overshooting during
tuning or external disturbance.
SYSTEM
PID
FUZZY
MV PV
_
+
SV
+
+
PID+FUZZY CONTROL
PID control with properly tuned
PID + Fuzzy control
Warm Up Load Disturbance
Set point
Temperature
Time
2. Model Order Matrix2. Model Order Matrix
FDC
(1) (2) (3) (4) (5) (6) (7) (8)
(1) Power Input
4 90-264VAC
5 20-32VAC/VDC
9 Other
(2) Signal Input
5 Configurable (Universal)
9 Other
(3) Range Code
1 Configurable
9 Other
(4) Control Mode
3 PID / ON-OFF Control
(5) Output 1 Option
0 None
1 Relay rated 3A/240VAC resistive
2 SSR Drive rated 20mA/24V
3 4-20mA linear, max. load 500 ohms (Module OM93-1)
4 0-20mA linear, max. load 500 ohms (Module OM93-2)
5 0-10V linear, min. impedance 500K ohms (Module OM93-3)
9 Other
(6) Output 2 Option
0 None
(7) Alarm Option
0 None
1 Relay rated 2A/240VAC resistive
9 Other
(8) Communication
0 None
CONTENTS
3
Model:FDC 9090
Instruction Manual
Model:FDC 9090
Instruction Manual
1. INTRODUCTION
2. NUMBERING SYSTEM
3. FRONT PANEL DESCRIPTION
4. INPUT RANGE & ACCURACY
5. SPECIFICATIONS
6. INSTALLATION
1. INTRODUCTION
2. NUMBERING SYSTEM
3. FRONT PANEL DESCRIPTION
4. INPUT RANGE & ACCURACY
5. SPECIFICATIONS
6. INSTALLATION
8. OPERATION
7. CALIBRATION7. CALIBRATION
8. OPERATION
8.1 KEYPAD OPERATION
8.2 FLOW CHART
8.3 PARAMETER DESCRIPTION
8.4 AUTOMATIC TUNING
8.5 MANUAL P.I.D. ADJUSTMENT
8.6 MANUAL TUNING PROCEDURE
8.7 RAMP & DWELL
6.1 DIMENSIONS & PANEL CUTOUT
6.2 WIRING DIAGRAM
9. ERROR MESSAGES9. ERROR MESSAGES
In addition, this instrument has functions of single stage ramp
and dwell, auto-tunung and manual mode execution. Ease of use
also an essential feature with it.
This manual contains information for the installation and operation
of the Future Design Control’s model FDC-9090 Fuzzy Logic
micro-processor based controller.
1. INTRODUCTION1. INTRODUCTION
SV
PV
9090
CON
ALM
C
3. FRONT PANEL DESCRIPTION3. FRONT PANEL DESCRIPTION
Process Value Display
(0.4" red LED)
Set point Value Display
(0.3" green LED)
Control Output
Alarm Output
Scroll Key
Down Key
Return Key
Up Key
4. INPUT RANGE & ACCURACY4. INPUT RANGE & ACCURACY
Input Type
Iron-Constantan
Chromel-Alumel
Copper-Constantan
Chromel-Constantan
Pt30%RH/Pt6%RH
Pt13%RH/Pt
Pt10%RH/Pt
Nicrosil-Nisil
PT100 ohms(DIN)
PT100 ohms(JIS)
-10mV to 60mV
Range( C )B
-50to999 CB
-50 to 1370 CB
-270 to 400 CB
-50to750 CB
300 to 1800 CB
0 to 1750 CB
0 to 1750 CB
-50 to 1300 CB
-200 to 400 CB
-200 to 400 CB
-1999 to 9999
Accuracy
AB2C
AB2C
AB2C
AB2C
AB3C
AB2C
AB2C
AB2C
AB0.4 C
AB0.4 C
A0.05%
Sensor
J
K
T
E
B
R
S
N
RTD
RTD
Linear
IN
0
1
2
3
4
5
6
7
8
9
10
5. SPECIFICATIONS5. SPECIFICATIONS
INPUT
Thermocouple (T/C):
RTD:
Linear:
Range:
Accuracy:
Cold Junction Compensation:
Sensor Break Protection:
External Resistance:
Normal Mode Rejection:
Common Mode Rejection:
Sample Rate:
Proportion Band:
Reset ( Integral ):
Rate ( Derivative ):
Ramp Rate:
Dwell:
ON-OFF:
Cycle Time:
Control Action:
0 - 200 C ( 0-360 F)
0 - 3600 seconds
0 - 1000 seconds
0 - 200.0 C /minute (
0 - 3600 minutes
With adjustable hysteresis (0-20% of SPAN)
0-120 seconds
Direct (for cooling ) and reverse (for heating)
BB
B0 - 360.0 F /minute)B
CONTROL
POWER
Rating:
Consumption:
90-264VAC, 50/ 60Hz
Less than 5VA
ENVIRONMENTAL & PHYSICAL
Safety:
EMC Emission:
EMC Immunity:
Operating Temperature:
Humidity:
Insulation:
Breakdown:
Vibration:
Shock:
Net Weight:
Housing Materials:
UL873, CSA22.2/142-87, IEC1010-1
(EN61010-1)
EN50081-1
EN50082-2
-10 to 50 C
0 to 90 % RH (non-codensing)
20M ohms min. ( 500 VDC )
AC 2000V, 50/60 Hz, 1 minute
10 - 55 Hz, amplitude 1 mm
200 m/ s ( 20g )
170 grams
Poly-Carbonate Plastic
B
2

UM9090Rev1
4
6. INSTALLATION6. INSTALLATION
6.1 DIMENSIONS & PANEL CUTOUT6.1 DIMENSIONS & PANEL CUTOUT
Panel
(45 mm)
Figure 6.1 Mounting Dimensions
TOUCHKEYS FUNCTION DESCRIPTION
Scroll Key
Long Scroll
Press
for 6 seconds
Press and
Up Key
Down Key
Return Key
Long Return
Output Percentage
Monitor
Manual Mode
Execution
* F1: Fuse, S1: Power Switch
6.2 WIRING DIAGRAM6.2 WIRING DIAGRAM
8. OPERATION8. OPERATION
8.1 KEYPAD OPERATION8.1 KEYPAD OPERATION
Press
for 6 seconds
Press and
for 6 seconds
Increases the parameter
Advance the index display to the desired position.
Index advanced continuously and cyclically by pressing this keypad.
Decreases the parameter
Resets the controller to its normal status. Also stops auto-tuning,
output percentage monitoring and manual mode operation.
Allows more parameters to be inspected or changed.
1. Executes auto-tuning function
2. Calibrates control when in calibration level
Allows the set point display to indicate the control output value.
Allows the controller to enter the manual mode.
7. CALIBRATION7. CALIBRATION
FDC-9090
1
2
3
4
5
6
7
8
9
10
+
+
+
_
_
_
Alarm
Com.
Alarm
N/O
V
Control Output 1
F1 S1
90 - 264 VAC,50/60HZ
RTD
* With power on, it has to wait for 12 seconds to memorize the new values of parameters once it been changed.
Note: Do not proceed through this section unless their is a
genuine need to re-calibrate the controller. All previous
calibration date will be lost. Do not attempt re-calibration
unless you have available appropriate calibration equipment.
If calibration data is lost, you will need to return the controller
to your supplier who may apply a charge for re-calibration.
Note: Do not proceed through this section unless their is a
genuine need to re-calibrate the controller. All previous
calibration date will be lost. Do not attempt re-calibration
unless you have available appropriate calibration equipment.
If calibration data is lost, you will need to return the controller
to your supplier who may apply a charge for re-calibration.
Prior to calibration ensure that all parameter settings are
correct (input type, C / F, resolution, low range, high range).BB
1. Remove sensor input wiring and connect a standard input
simulator of the correct type to the controller input. Verify
correct polarity. Set simulated signal to coincide with low
process signal (e.g. zero degrees).
2. Use the Scroll Key until the " " appears on the PV
Display. (Refer to 8.2)
3. Use the Up and Down Keys until the SV Display
represents the simulated input.
4. Press the Return Key for at least 6 seconds(maximum 16
seconds), then release. This enters the low calibration
figure into the controller's non-volatile memory.
5. Press and release the Scroll Key. " " appears on
the PV Display. This indicates the high calibration point.
6. Increase the simulated input signal to coincide with high
11 process signal (e.g. 100 degrees).
7. Use the Up and Down Keys until the SV Display
represents the simulated high input.
8. Press the Return Key for at least 6 seconds (maximum 16
seconds), then release. This enters the high calibration
figure into the controller's non-volatile memory.
9. Turn power off the unit, remove all test wiring and replace
sensor wiring (observing polarity).
1.77 “
1.77 “
(45 mm)
94 mm
3.70 “
86 mm
3.38 “

Long
(6 seconds)
Long
(6 seconds)
Long
(6 seconds)
SET POINT VALUE DISPLAY
PROCESS VALUE DISPLAY
Level 0
Level 3
The "return" key can be pressed at any time.
This will prompt the display to return to the
Process value/Set point value.
Power Applied:
1. Displayed for 4 seconds.
(Software Version 3.6 or higher)
2. LED test.
All LED segments must be lit for 4 seconds.
3. Process value and set point indicated.
UM9090Rev1
8.2 FLOW CHART8.2 FLOW CHART
Level 1
Level 2
8.3 PARAMETER DESCRIPTION8.3 PARAMETER DESCRIPTION
INDEX
CODE
DESCRIPTION
ADJUSTMENT RANGE
**DEFAULT
SETTING
SV Set point Value Control
*Low Limit to High Limit Value Undefined
Alarm Set point Value
* Low Limit to High Limit Value.(if =0, 1, 4 or 5)
* 0 to 3600 minutes ( if =12 or 13)
* Low Limit minus set point to high Limit minus set
point value ( if =2, 3, 6 to 11 )
Ramp Rate for the process value to limit an abrupt
change of process (Soft Start)
* 0 to 200.0 C (360.0 F) / minute ( if = 0 to 9 )
* 0 to 3600 unit / minute ( if =10 )
BB
200 CB
0 C / min.B
Offset Value for Manual Reset ( if = 0 )
* 0 to 100%
Offset shift for process value
*-111Cto111CBB
Proportional Band
* 0 to 200 C ( set to 0 for on-off control)B
Integral (Reset) Time
* 0 to 3600 seconds
Derivative (Rate) Time
* 0 to 1000 seconds
Local Mode
0: No control parameters can be changed
1: Control parameters can be changed
Parameter Selection ( allows selection of additional
parameters to be accessible at level 0 security)
0.0 %
0CB
10 CB
120 sec.
30 sec.
1
Proportional Cycle Time
* 0 to 120 seconds
Relay
Pulsed Voltage
Linear Volt/mA
20
1
0
Input Mode Selection
0: J type T/C
1: K type T/C
2: T type T/C
3: E type T/C
4: B type T/C
5: R type T/C
Note: T/C-Close solder gap G5, RTD-Open G5
6: S type T/C
7: N type T/C
8: PT100 DIN
9: PT100 JIS
10: Linear Voltage or Current
Alarm Mode Selection
0: Process High Alarm
1: Process Low Alarm
2: Deviation High Alarm
3: Deviation Low Alarm
4: Inhibit Process High Alarm
5: Inhibit Process Low Alarm
6: Inhibit Deviation High Alarm
7: Inhibit Deviation Low Alarm
8: Outband Alarm
9: inband Alarm
10: Inhibit Outband Alarm
11: Inhibit Inband Alarm
12: Alarm Relay OFF as
Dwell Time Out
13: Alarm Relay ON as
Dwell Time Out
Hysteresis of Alarm 1
* 0 to 20% of SPAN
BB
BB
C / F Selection
0: F, 1: C
Resolution Selection
0: No Decimal Point
1: 1 Digit Decimal
2: 2 Digit Decimal
3: 3 Digit Decimal
(2&3mayonly be used for linear voltage or current
=10 )
Control Action
0: Direct (Cooling) Action 1: Reverse (Heat) Action
Error Protection
0: Control OFF, Alarm OFF
1: Control OFF, Alarm ON
Hysteresis for ON/OFF Control
*0 to 20 % of SPAN
Low Limit of Range
High Limit of Range
Low Calibration Figure
High Calibration Figure
NOTES: * Adjusting Range of the Parameter
** Factory settings. Process alarms are at fixed temperature points. Deviation
alarms move with the set points value.
0: None 4:
1: 5:
2: 6:
3: 7:
,
,
,,
0
T/C
RTD
Linear
0
8
10
0
0.5%
1
2: Control ON , Alarm OFF
3: Control ON, Alarm ON
0
1
1
0.5%
-50 CB
1000 CB
0CB
800 CB
5

UM9090Rev1
6
8.4 AUTOMATIC TUNING
3. Press Return Key for at least 6 seconds ( maximum 16 seconds). This
initializes the Auto-tune function. (To abort auto-tuning procedure
press Return Key and release).
2. Ensure Proportional Band 'Pb' is not set at '0'.
1. Ensure that controller is correctly configured and installed.
4. The Decimal point in lower right hand corner of PV display flashes to
indicate Auto-tune is in progress. Auto-tune is complete when the
flashing stops.
5. Depending on the particular process, automatic tuning may take up
to two hours. Processes with long time lags will take the longest to
tune. Remember, while the display point flashes the controller is
auto-tuning.
NOTE: If an AT error( ) occurs, the automatic tuning process
is aborted due to the system operating in ON-OFF control(PB=0).
The process will also be aborted if the set point is set to close to
the process temperature or if there is insufficient capacity in the
system to reach set point (e.g. inadequate heating power
available). Upon completion of Auto-tune the new P.I.D. settings
are automatically entered into the controller's non-volatile memory.
8.5 MANUAL P.I.D. ADJUSTMENT8.5 MANUAL P.I.D. ADJUSTMENT
Whilst the auto-tuning function selects control settings which should prove
satisfactory for the majority of processes, you may find it necessary to
make adjustments to these arbitrary settings from time to time. This may
be the case if some changes are made to the process or if you wish to
'fine-tune' the control settings.
It is important that prior to making changes to the control settings that
you record the current settings for future reference. Make slight changes
to only one setting at a time and observe the results on the process.
Because each of the settings interact with each other, it is easy to become
confused with the results if you are not familiar with process control
procedures.
TUNING GUIDE
TUNING GUIDE
Proportional Band
Symptom Solution
Slow Response Decrease PB Value
High Overshoot or Oscillations Increase PB Value
Integral Time (Reset)
Symptom Solution
Slow Response Decrease Integral Time
Instability or Oscillations Increase Integral Time
Derivative Time (Rate)
Symptom Solution
Slow Response or Oscillations Decrease Deriv. Time
High Overshoot Increase TimeDeriv.
8.6 MANUAL TUNING PROCEDURE8.6 MANUAL TUNING PROCEDURE
Step 1: Adjust the integral and derivative values to 0. This inhibits the
rate and reset action
Step 2: Set an arbitrary value of proportional band and monitor the
control results
Step 3: If the original setting introduces a large process oscillation, then
gradually increase the proportional band until steady cycling
occurs. Record this proportional band value(Pc).
Step 4: Measure the period of steady cycling
PV
PV(Process value)
Tc
TIME
Record this value (Tc) in seconds
Step 5: The Control Settings are determined as follows:
Proportion Band(PB)=1.7 Pc
Integral Time (TI)=0.5 Tc
Derivative Time(TD)=0.125 Tc
25
50
75
100
125
150
010 20 30 40 50 60 70 80 90
15 minutes
ON OFF
Process Value
Alarm Output
t(minutes)
The dwell function may be used to operate an external device such
as a siren to alert when a soak time has been reached.
need to be set to the value 13. The alarm contact will now
operate as a timer contact, with the contact being open on the
initial start up. The timer begins to count down once the set point
temperature is reached. After the setting at has elapsed, the
alarm contact closes.
9. ERROR MESSAGES9. ERROR MESSAGES
Symptom Cause (s) Solution (s)
Sensor break error Replace RTD or sensor
Use manual mode operation
Process display beyond
the low range set point Re-adjust value
Re-adjust value
Process display beyond
the high range set point
Analog hybrid module
damage
Incorrect operation of
auto tune procedure
Prop. Band set to 0
Manual mode is not
allowable for an ON-OFF
control system
Check sum error, values
in memory may have
changed accidentally
Replace module. Check for
outside source of damage
such as transient voltage spikes
Repeat procedure. Increase
Prop. Band to a number larger
than 0
Increase proportional band
Check and reconfigure the
control parameters
8.7 RAMP & DWELL8.7 RAMP & DWELL
The FDC-9090 controller can be configured to act as either a fixed
set point controller or as a single ramp controller on power up. This
function enables the user to set a pre-determined ramp rate to
allow the process to gradually reach set point temperature, thus
producing a 'Soft Start' function.
A dwell timer is incorporated within the FDC-9090 and the alarm
relay can be configured to provide either a dwell function to be
used in conjunction with the ramp function.
The ramp rate is determined by the ' ' parameter which can be
adjusted in the range 0 to 200.0 C/minute. The ramp rate function
is disabled when the ' ' parameter is set to ' 0 '.
B
The soak function is enabled by configuring the alarm output to act
as a dwell timer. The parameter needs to be set to the
value 12. The alarm contact will now operate as a timer contact,
with the contact being closed at power up and opening after the
elapsed time set at parameter .
If the controller power supply or output is wired through the alarm
contact, the controller will operate as a guaranteed soak controller.
In the example below the Ramp Rate is set to 5 C/minute,B
=12 and =15 (minutes). Power is applied at zero
time and the process climbs at 5 C/minute to the set point of 125
C. Upon reaching set point, the dwell timer is activated and after
the soak time of 15 minutes, the alarm contact will open, switching
off the output. The process temperature will eventually fall at an
undetermined rate.
B
B
BC

A 2 WarrantyA 2 Warranty
WARRANTY
RETURNS
No products return can be accepted without a completed Return Material Authorization ( RMA ) form.No products return can be accepted without a completed Return Material Authorization ( RMA ) form.
Future Design Controls warranties or representations of any sort regarding the fitness for
use, or the application of its products by the Purchaser. The selection, application or use
of Future Design products is the Purchaser's responsibility. No claims will be allowed for
any damages or losses, whether direct, indirect, incidental, special or consequential.
Specifications are subject to change without notice. In addition, Future Design reserves
the right to make changes without notification to Purchaser to materials or processing
that do not affect compliance with any applicable specification.
Future Design products are warranted to be free from defects in material and
workmanship for two years after delivery to the first purchaser for use. An extended
period is available with extra cost upon request. Future Design’s sole responsibility
under this warranty, at Future Design’s option, is limited to replacement or repair, free of
charge, or refund of purchase price within the warranty period specified. This warranty
does not apply to damage resulting from transportation, alteration, misuse or abuse.
Future Design Controls warranties or representations of any sort regarding the fitness for
use, or the application of its products by the Purchaser. The selection, application or use
of Future Design products is the Purchaser's responsibility. No claims will be allowed for
any damages or losses, whether direct, indirect, incidental, special or consequential.
Specifications are subject to change without notice. In addition, Future Design reserves
the right to make changes without notification to Purchaser to materials or processing
that do not affect compliance with any applicable specification.
Future Design products are warranted to be free from defects in material and
workmanship for two years after delivery to the first purchaser for use. An extended
period is available with extra cost upon request. Future Design’s sole responsibility
under this warranty, at Future Design’s option, is limited to replacement or repair, free of
charge, or refund of purchase price within the warranty period specified. This warranty
does not apply to damage resulting from transportation, alteration, misuse or abuse.
7
UM9090Rev1
Other manuals for FDC-9090
1
Table of contents
Other Future Design Temperature Controllers manuals