GE CAL16A User manual

NETWORK
RELAY
TYPES
CAL
16
A
AND
CAN
13
A
INTRODUCTION
With
a
few
eptions
,
the
Type
CAL
16
A
and
CAN
13
A
relays
are
Identical
In
construction
and
function
to
the
standard
secondary
network
relays
shown
in
the
Included
instruction
book
GEl
-
13580
.
The
CAN
13
A
will
prevent
reclosure
if
the
source
phase
sequence
is
reversed
and
the
network
phase
sequence
is
normal
.
The
principal
difference
af
-
fecting
both
relays
is
that
the
glass
cover
and
mounting
bracket
have
been
removed
,
and
the
relays
have
been
mounted
in
the
drawout
case
for
mounting
on
a
panel
.
Also
,
both
relays
have
2
ampere
holding
coils
in
the
reclose
circuits
,
Instead
of
the
0.3
ampere
coils
as
In
the
standard
relay
.
The
Type
CAN
13
A
relay
differs
from
the
Type
CAN
11
A
relay
In
several
points
concerning
physical
construction
and
electrical
connections
.
The
only
change
in
function
is
that
it
is
designed
to
trip
at
approximately
0.005
ampere
,
current
transformer
secondary
current
,
in
phase
with
line
-
to
-
neutral
voltage
.
It
is
intended
to
be
used
for
tripping
when
the
only
reverse
power
flowing
is
the
magnetizing
current
of
the
associated
power
transformer
.
The
principal
differences
between
the
Type
CAN
13
A
relay
and
the
Type
CAN
11
A
relay
areas
follows
:
1
.
The
reclose
contact
is
on
the
left
and
the
trip
contact
on
the
right
,
facing
the
relay
,
on
the
Type
CAN
13
A
relay
.
This
is
the
reverse
of
the
Type
CAN
11
A
relay
.
2
.
The
main
control
spring
is
used
to
adjust
trip
value
and
the
mechanical
restraint
Is
used
to
adjust
reclose
value
on
the
Type
CAN
13
A
relay
.
3
.
The
electrical
restraint
element
has
been
omitted
on
the
Type
CAN
11
A
relay
.
4
.
The
potential
coils
,
instead
of
being
connected
directly
to
the
network
side
of
the
breaker
are
,
connected
to
a
resistor
combination
across
each
pole
of
the
associated
breaker
.
This
last
feature
allows
the
potential
coils
to
be
energized
from
the
network
side
when
the
source
side
is
de
-
energized
;
or
from
the
source
side
when
the
network
side
is
de
-
energized
.
When
the
breaker
is
closed
,
the
two
sections
of
the
resistor
com
-
bination
on
each
phase
are
effectively
in
parallel
and
the
net
resistance
is
the
same
as
that
ordinarily
used
with
the
Type
CAN
11
A
relay
(
t
.
e
.
,
340
ohms
when
6054972
G
8
is
used
as
the
phase
-
shifting
trans
-
former
,
and
when
the
900
ohm
resistor
is
used
in
the
phase
circuit
for
1.5
volt
reclosure
.
)
Therefore
the
tripping
characteristic
is
the
same
except
that
the
setting
is
0.1
%
instead
of
0.2
%
of
the
relay
rating
.
RECEIVING
,
HANDLING
AND
STORAGE
CO
The
relays
,
when
not
included
as
a
part
of
a
control
panel
,
will
be
shipped
in
cartons
designed
to
protect
them
against
damage
.
Immediately
upon
receipt
of
a
relay
examine
it
for
any
damages
sus
-
tained
in
transit
.
If
injury
or
damage
from
rough
handling
is
evident
,
file
a
damage
claim
at
once
with
the
transportation
company
and
promptly
notify
the
nearest
General
Electric
Apparatus
Sales
Office
.
Reasonable
care
should
be
exercised
in
unpack
-
ing
the
relay
in
order
that
none
of
the
parts
are
injured
or
the
adjustments
distrubed
.
If
the
relays
are
not
to
be
installed
immediately
,
they
should
be
stored
in
their
original
cartons
in
a
place
that
is
free
from
moisture
,
dust
and
metallic
chips
.
Foreign
matter
collected
on
the
outside
of
the
case
may
find
its
way
inside
when
the
cover
is
removed
and
cause
trouble
in
the
operation
of
the
relay
.
=
r
r
-
8
cO
V
O
o
DESCRIPTION
RELAY
CASE
reset
mechanism
when
one
is
required
.
Each
cover
screw
has
provision
for
a
sealing
wire
.
The
case
is
suitable
for
either
surface
or
semi
-
flush
panel
mounting
and
an
assortment
of
hardware
is
provided
for
either
mounting
.
The
cover
attaches
to
the
case
and
also
carries
the
The
case
has
studs
or
screw
connections
at
both
ends
or
at
the
bottom
only
for
the
external
connections
.
The
electrical
connections
between
These
instructions
do
not
purport
to
cover
all
details
or
variations
in
equipment
nor
to
provide
for
every
possible
contingency
to
be
met
in
connection
with
installation
,
operation
or
nuintenance
.
further
information
be
desired
or
should
particular
problems
arise
which
are
not
covered
sufficiently
for
the
purchaser
*
s
purposes
/
the
matter
should
be
referred
to
the
General
Electric
Company
.
To
the
extent
required
the
products
described
herein
meet
applicable
ANSI
,
IEEE
and
HE
HA
standards
/
but
no
such
assurance
is
given
with
respect
to
local
codes
and
ordinances
because
they
vary
greatly
.
Should
3
Courtesy of NationalSwitchgear.com

GUI
-
31090
Network
Relays
Types
CAL
10
A
and
CAN
13
A
spec
live
blocks
of
the
cradle
and
case
,
also
locks
the
latch
In
place
.
The
cover
,
which
Is
fastened
to
the
case
by
thumbscrews
,
holds
the
connecting
plug
In
place
.
the
relay
units
and
the
case
studs
are
made
through
spring
tacked
contact
fingers
mounted
In
stationary
molded
Inner
and
outer
blocks
between
which
nests
a
removable
connecting
plug
which
completes
the
circuits
.
The
outer
blocks
,
attached
to
the
case
,
have
the
studs
for
the
external
connections
,
and
the
Inner
blocks
have
the
terminals
for
the
Internal
connections
.
The
relay
mechanism
Is
mounted
In
a
steel
framework
called
the
cradle
and
Is
a
complete
unit
with
all
leads
being
terminated
at
the
Inner
block
.
This
cradle
is
held
firmly
at
the
top
and
the
bottom
and
by
a
guide
pin
at
the
back
of
the
case
.
The
cases
and
cradles
are
so
constructed
that
the
relay
cannot
be
Inserted
In
the
case
upside
down
.
The
connecting
plug
,
besides
making
the
electrical
connections
between
the
re
-
To
draw
out
the
relay
unit
the
cover
la
first
removed
,
and
the
plug
drawn
out
Shorting
bars
are
provided
In
the
case
to
short
the
ourrent
transfor
-
mer
circuits
.
The
latches
are
then
released
,
and
the
relay
unit
can
be
easily
drawn
out
To
replace
the
relay
unit
,
the
reverse
order
Is
followed
.
A
separate
testing
plug
can
be
Inserted
In
place
of
the
connecting
plug
to
test
the
relav
In
place
the
panel
either
from
Its
own
source
of
current
and
voltage
,
or
from
other
sources
.
Or
,
the
relay
unit
can
be
drawn
out
and
replaced
by
another
which
has
been
tested
Ln
the
laboratory
.
in
the
case
with
a
latch
on
INSTALLATION
LOCATION
AND
MOUNTING
dimensions
for
the
Type
CAN
13
A
relay
,
in
the
size
M
2
case
,
is
shown
in
Fig
,
7
.
CONNECTIONS
The
internal
connections
for
the
Type
CAL
16
A
and
CAN
13
A
relays
are
shown
In
Figs
,
1
and
2
respectively
,
A
typical
external
connection
diagram
for
the
The
outline
and
panel
drilling
Types
CALI
6
A
andCAN
13
A
relays
is
shown
in
Fig
.
3
.
The
location
should
be
clean
and
dry
,
free
from
dust
and
excessive
vibration
,
and
well
lighted
to
facilitate
inspection
and
testing
.
The
relay
should
be
mounted
on
a
vertical
sur
-
face
.
The
outline
and
panel
drilling
dimensions
for
the
Type
CAL
16
A
relay
,
In
the
size
Ml
case
,
ia
shown
in
Fig
.
6
,
I
7
19
10
I
I
o
o
Q
Q
<
6
14
18
r
1
12
t
O
A
,
AO
ik
.
M
?
A
.
xn
>
-
‘
8
X
*
8
04
0
0
0
0
0
0
0
0
3
e
HOLD
I
M G
COIL
T
l
x
6
c
HOLD
IMG
C O
I
l
0
0
c
*
1
>
3
PM
u
.
P
I
TAlPif
:
±
R
C
10
$
E
URGE
T
F T
h
-
>
8
<
>
>
'
•
V
*
s
y
i i
8
7
U
2
f
C
3
CN
=
1
\
r
>
t
’
t
\
t
'
f
N
e
a
0
»
o
9
O
•
-
SHORT
FINGERS
3
l
7
u
.
O
O
o
*
8
6
"
"
SHORT
FIMGCR
Internal
Connection
#
For
Relay
Type
CALI
6
A
Fig
.
J
Internal
Connection
#
For
Relay
Type
CAN
ISA
Fig
.
2
A
Courtesy of NationalSwitchgear.com

Network
Relays
Types
CAL
16
A
and
CAN
13
A
GEI
-
31090
INCOMING
LINE
1
2
3
1
£
CAN
HC
7
J
TARGET
FOR
7
>
USE
WITH
8
TIMER
12
POWER
TRANS
.
^
H
.
C
.
1
CAL
11
HC
2
PHASE
-
SHIFTING
TRANSFORMER
6054972
G
-
8
TO
{
RIP
(
RECljOSE
)
<
0
3
lO
H
i
r
i
rX
11
+
H
X
H
X
vn
4
5
6
I
I
40
I
w
T
3
!
T
2
T
1
CO
I
L
J
\
CAN
13
A
CURRENT
CO
ILS
b
u
i
in
n
n
1
r
i
r
1
15
161
T
114
r
;
;
fY
I
PHASE
SHIFTING
^
I
TRANSFORMER
T
2
FT
31
6054972
G
-
8
11
Y
’
Y
n
?
I
x
\
~
lPw
8
19
[
17
18
6
J
'
J
•
HJ
:
J
i
n
n
n
j
i
rv
I
CAN
13
A
POTENTIAL
COILS
CAL
16
A
POTENTIAL
COILS
125
V
X
CIRCUIT
BREAKER
TO
NETWORK
Fig
.
3
External
Connections
For
Types
CAL
16
A
And
CAM
13
A
Relays
5
Courtesy of NationalSwitchgear.com

GEI
-
31090
Network
Relays
Types
CAL
18
A
and
CAN
13
A
TRIPPING
-
1
*
i
605
H
972
Gi
PHASE
SHIFTING
TRANSFORMER
1
V
^
v
19
0
18
X
X
17
X
o
9
8
0
5
0
*
»
—
\
—
\
—
0
6
3
•
o
i
=
*
V
u
-
\
16
1
*
1
>
CURRENT
CIRCUITS
POTENTIAL
CIRCUITS
RECLOSIRG
!
2
t
J
N
“
r
j
T
900
900
900
A
19
605
*
8972
0
«
/
MU
-
SHIFTING
TRAN
$
f
0
RM
CR
T
T
r
17
Q
!
•
H
N
H
x
X
0
H
X
6
)
\
18
16
1
)
POTENTIAL
CIRCUITS
CURRENT
CI
RCU
ITS
Schematic
Diagram
Of
Teat
Connections
For
Relay
Type
CAN
13
A
Fig
.
4
6
Courtesy of NationalSwitchgear.com

Network
Relays
Types
CAL
16
A
and
CAN
13
A
OEI
-
SIO
0
O
aw
v
i
3
i
•
t
—
r
^
r
-
COMMfCTlONt
SNOHN
A
«
|
POft
PMAlIKl
V
0
LTA
6
C
ItASIMI
POL
Am
11
M
0
IT
90
*
.
ft
(
V
(
U
(
CONNfCTIOM
TO
touici
VOLTAIC
TO
A
PH
All
MO
LAGGING
|
V
90
«
.
*
in
l
<
o
1
OKH
ACACTOI
AW
o
m
9
U
-
0
‘
0
7
0
•
0
»
J
'
)
%
Ar
^
2
'
l
POUAl
ZING
PHASING
Schematic
Diagram
Of
Test
Connections
For
Relay
Type
CAL
J
6
A
Fig
.
5
MAINTENANCE
TYPE
CAN
13
A
RELAYS
INSPECTION
AND
MECHANICAL
ADJUSTMENT
1
.
The
main
control
spring
of
the
Type
CAN
13
A
relay
Is
adjusted
so
that
the
trip
contacts
are
open
with
zero
windup
on
the
control
spring
adjusting
shaft
,
and
are
just
made
when
there
are
3
half
-
turns
windup
(
counterclockwise
)
on
the
adjusting
shaft
*
The
normal
position
of
the
spring
Is
such
that
the
right
-
hand
(
trip
)
contacts
just
make
with
the
relay
de
-
energized
*
This
can
be
checked
by
deflecting
the
right
-
hand
stationary
contact
to
the
right
and
noting
that
the
moving
contacts
do
not
move
to
the
right
.
2
.
Items
1
to
9
under
INSPECTION
AND
MECH
-
ANICAL
ADJUSTMENT
In
GEI
-
13580
apply
to
the
Type
CAN
13
A
relay
.
Item
10
under
the
same
heading
,
covering
the
electrical
restraint
ele
-
ment
,
does
not
apply
*
CALIBRATION
TESTS
AND
ADJUSTMENTS
be
Just
made
.
With
only
the
potential
colls
ener
-
gized
,
the
moving
contacts
should
pull
away
from
the
trip
contact
.
Closing
the
switch
In
the
current
cir
-
cuit
to
pass
current
through
the
H
winding
,
with
the
connections
shown
,
should
produce
a
torque
In
the
direction
to
close
the
trip
contact
.
With
the
te
$
-
connections
shown
,
a
sing
e
-
phase
current
Is
ust
*
and
the
required
single
-
phase
current
is
equal
to
1.5
times
the
desired
three
-
phase
trip
setting
.
For
example
,
If
it
is
desired
to
trip
at
0.005
amperes
balanced
three
-
phase
current
,
the
ammeter
A
should
read
0.0075
amperes
because
of
the
single
-
phase
current
.
The
trip
calibration
can
be
adjusted
above
or
below
the
factory
setting
,
or
the
factory
setting
can
be
restored
,
by
adjusting
the
main
control
spring
adjusting
shaft
(
see
photographs
of
CAN
relay
,
Fig
.
19
In
GEI
-
13580
)
.
Turning
this
shaft
clockwise
increases
the
amount
of
reverse
current
required
for
tripping
,
and
turning
the
shait
counterclockwise
decreases
the
amount
of
reverse
current
required
.
Reclosing
To
check
the
voltage
necessary
for
reclosing
connect
as
shown
in
the
lower
diagram
of
Fig
.
4
.
The
one
ohm
resistor
in
parallel
with
the
phasing
(
Y
)
winding
of
the
phase
shifting
transformers
has
such
a
low
Impedance
compared
to
the
phasing
windings
that
practically
all
of
the
current
read
by
ammeter
A
passes
through
the
resistor
,
and
the
ammeter
reading
is
equal
to
the
voltage
across
the
resistor
.
Since
this
ts
a
"
single
-
phase
"
test
,
the
voltage
applied
must
be
1
*
5
times
the
desired
three
-
phase
reclose
setting
.
For
example
,
for
a
three
-
phase
1
,
5
volt
reclose
setting
,
the
ammeter
A
should
read
2
*
25
amperes
.
Fig
.
4
shows
the
test
connections
for
checking
and
adjusting
both
the
tripping
and
reclosing
cali
-
bration
.
The
trip
setting
should
be
checked
first
because
any
adjustment
of
the
trip
setting
also
affects
the
reclose
setting
;
whereas
,
the
reclose
setting
can
be
adjusted
independently
of
the
trip
setting
and
should
therefore
be
made
last
.
Tripping
Connect
the
relay
as
shown
In
Fig
.
4
.
With
the
relay
de
-
energized
,
the
right
-
hand
contact
should
7
Courtesy of NationalSwitchgear.com

GEl
-
31090
Network
Relays
Types
CAL
16
A
and
CAN
13
A
except
at
the
Instant
the
contacts
touch
.
Interrupt
the
holding
current
by
an
external
switch
in
the
contact
circuit
,
never
at
the
contacts
.
TYPE
CAL
16
A
RELAY
The
Type
CAL
16
A
relay
Is
Identical
to
the
Type
CAL
15
A
relay
,
described
in
the
Included
Instruc
-
tion
book
GEl
-
13580
,
except
that
it
is
mounted
in
a
drawout
case
.
For
calibration
,
the
relay
should
be
connected
as
shown
In
Fig
.
5
.
The
normal
cali
-
bration
of
the
Type
CAL
16
A
relay
Is
to
close
its
contacts
when
the
phasing
voltage
(
on
studs
7
-
8
)
is
gradually
Increased
to
0.5
volt
,
leading
the
potential
voltage
(
studs
5
-
6
)
by
90
degrees
.
Adjustments
can
be
made
as
described
in
GEI
-
13580
.
The
reclose
calibration
of
the
relay
can
be
changed
by
adjusting
the
mechanical
restraint
ele
-
ment
.
Turning
the
cap
of
the
restraint
clockwise
increases
the
restraint
and
therefore
the
reclose
calibration
.
Holding
Coils
Both
holding
-
coils
of
the
Type
CAN
13
A
relay
are
rated
2
amperes
.
These
holding
coils
can
be
checked
as
part
of
the
trip
and
reclose
adjustments
above
by
connecting
an
adjustable
resistor
in
the
contact
circuit
and
adjusting
the
holding
coil
circuit
to
2
amperes
.
As
soon
as
the
trip
or
reclose
con
-
tacts
make
,
the
sealing
armature
should
definitely
seal
them
closed
,
and
there
should
be
no
sparking
8
Courtesy of NationalSwitchgear.com

Network
Relays
Types
CAL
16
A
and
CAN
13
A
GEI
-
31090
PANEL
LOCATION
SEMI
-
FLUSH
SURFACE
v
^
MTG
.
MTG
^
3
65
6
4
(
6
6
Q
n
1
£
z
:
.
~
\
f
3
N
J
.
<
0
I
$
10
STUDS
4
^
FOR
SURFACE
MTG
.
Ir
.
v
.
c
CO
ft
oi
0
+
?
‘
t
3
5
7
9
OOOOO
L
90090
NUMBERING
OF
STUDS
(
FRONT
VIEW
)
10
*
32
SCREW
(
OR
STUD
)
oi
I
O
CM
4
f
t
-
3
!
;
'
K
>
-
32
*
SMTG
.
0
SCREW
k
u
>
OUTLINE
<
a
u
.
IJ
5
to
16
27
2
27
1
UJ
2
-
j
32
32
32
-
JO
Ji
PANEL
L
cc
4
DRILL
^
6
HOLES
*
o
O
"
mjco
(
|
-
18
STUD
Z
NE
#
2
4
DRILL
VO
HCcEt
<
<
r
,
j
CM
fO
fO
'
to
K
>
UI
If
)
o
<
_
J
O
'
-
<
'
a
s
<
”
^
1
5
3
x
CM
<
3
2
X
c
*
-
2
1
-
A
5
c
10
rO
K
>
2
tL
.
If
)
i
N
-
—
1
<
y
-
H
)
VIEW
SHOWING
ASSEMBLY
OF
HARDWARE
FOR
SURFACE
MTG
ON
STEEL
PANELS
It
3
tic
3
_
L
2
3
o
^
MJFLUSH
PANEL
DRILLING
MOUNTING
(
F
4
PANEL
DRILLING
FOR
SURFAi
t
MOUNTING
(
FRONT
VIEW
)
FIg
«
6
Outline
And
Panel
Drilling
Dimensions
For
Relay
Type
CALI
6
A
9
Courtesy of NationalSwitchgear.com

GEI
-
3
J
090
Network
Relays
Types
CAL
16
A
and
CAN
13
A
PANEL
LOCATION
SEMI
-
FLUSH
SURFACE
M
'
G
.
^
—
4
-
4
*
10
-
32
SCREW
(
G
,
<
STUD
)
II
13
15
17
19
ooooo
ooooo
12
14
16
18
20
I
4
%
[
-
.
-
J
T
T
10
3
rOfT
1
(
|
-
[
8
STUDS
*
FOR
SURFACE
MTG
.
inf
?
r
-
<
£
CNJ
in
tf
>
cr
>
00
o
LC
.
"
~
-
-
3
CM
I
13
5
7
9
ooooo
I
ooooo
2
4
6
8
10
NUMBERING
OF
STUDS
(
FRONT
VIEW
)
±
(
r
^
-
IKD
“
32
>
c
p
MTG
.
|
1
y
SCREW
a
u
_
OUTLINE
i
hi
I
.
.
Q
a
8
r
-
LCio
3
o
;
arj
i
•
YDFUL
q
6
HOLES
"
J
~
T
^
O
PANEL
He
/
,
3
I
K
=
JO
fO
{
NjCO
|
|
-
I
8
STUD
<
D
8
$
m
OC
'
T
*
T
a
+
foh
^
ffi
m
co
.
in
"
3
I
—
4
—
4
<
X
>
-
o
fc
ui
Ui
j
0
lo
^
IJJ
<
/
>
-
j
J
’
R
*
ro
|
c
3
8
m
CM
tr
>
L
,
.
VIEW
SHOWING
ASSEMBLY
OF
HARDWARE
FOR
SURFACE
MTG
.
ON
STEEL
PANELS
(
F
O
PANEL
DRILLING
FOR
SURFACE
MOUNTING
(
FRONT
VIEW
)
PANEL
DRILLING
FOR
SEMI
-
FLUSH
MOUNTING
(
FRONT
VIEW
)
Outline
And
Panel
Drilling
Dimensions
For
Relay
Type
CAHI
3
A
Fig
.
7
10
Courtesy of NationalSwitchgear.com
Other manuals for CAL16A
1
This manual suits for next models
1
Table of contents
Other GE Relay manuals